Hydromatic II Chiller Operation Manual
Table Of Contents
- Introduction
- Getting Started
- System Overview
- Operational Overview
- Initial Configuration
- System Menu Items
- Operation
- Fault Handling
- Wiring Diagrams
- Specifications
- Glossary
- Appendix 1: System menu overview
- Appendix 2: Organizing IDs in the CAN system
- Appendix 3: Ordering a system
Page 5
Rev 1.07 ©2015 Micro Air Corp 10/26/2015
System Overview
The Hydromatic system operates as a master – slave system. Each control in the
system is considered a slave. The master function can be assigned to any slave in the
system. The master function operates independently from the slave function within that
control. A slave is designated as a master by making the group ID and unit ID the same
value. Additional slaves can be added by setting their unit ID as the next numerically
higher unit ID and assigning them to the same group ID as the master. A system pump
control will also be configured during setup.
The master controls all operations once the system is configured. Individual slave
compressors are started as needed and cycled regularly to equalize run time when
possible.
Additional details on setting unit numbers may be found in Appendix 2:
Organizing IDs in the CAN system.
Operational Overview
Cooling
The first stage of cooling is started when the loop return water temperature rises
above the cooling set point by the amount programmed in the differential parameter. One
slave is selected by the master to start its compressor. If the stage is programmed to have
more than one compressor, each additional compressor will start one at a time, after the
expiration of the staging delay. Additional increases in loop return water temperature by
the amount programmed in the differential parameter will start subsequent stages until all
available stages are operating.
The first stage of cooling is shut down when the loop water temperature reaches:
(Set point + (number of active stages * differential) – hysteresis)
Differential and hysteresis is the value set by their programmable parameter value
for the above equation.
Each subsequent reduction in loop return water temperature by the amount set in
the hysteresis parameter will shut down the next stage. If the loop water return
temperature reaches the cooling set point, all compressors will shut down.
Heating
Heating operation is similar in function to cooling operation utilizing the heating
set point along with differential and hysteresis to control loop return water temperature.
If the sea water temperature drops below the temperature set in the EL Heat Transition
parameter, any operating compressors will be turned off and only electric heaters will be
used to heat loop water. The heaters will be used for the remainder of the cycle even if
the sea water temperature increases above the electric only temperature set point. Electric
heaters must be available and the optional sea water sensor installed for this function.










