TROUBLESHOOTING
PROCEDURE FOR MOLD SETTERS
 a control zone does not reach 
setpoint value.
Locate faulty zone.
Go to temperature page.
Press on menu PARAM.
Scroll in parameters with the + key until « applied 
power (%)» is shown.
Or press menu zOOM and select the faulty zone on 
the wide display.
Check if the bar graph shows maximum power.
If the applied power shown equals 100% and the zone 
does not heat up, 3 reasons should be investigated:
- The heating element is over dimensioned in comparison 
to the power the INCOE control card can deliver and 
the fuses will blow at any time. (Maximum current 16A 
or 5A depending on card type).
- The power card has two fuses (one on phase, and 
the second on neutral). One or both are maybe faulty
- A wire between the control card and the tool is not 
connected or miswired.
The resistance may also be faulty.
For any other conditions, any service to the inside 
an M Series cabinet should be carried out by authorized 
personnel.