combine wireless field device s important diagnosis information and communication states. 1:
good; 0: bad.
Device Variable Code _ HEALTHY parameter is indication of device variable healthy status. These
parameters combine important diagnostic information and communication status from wireless
field device. 1: good. 0: bad.
State is relevant to wireless communication, and marks the device state in wireless network. 1: on-
line 0:off-line.
Hart State is the field device running state, following is the detailed info for Hart State.
Table 4-2 Device Status
Bit Code Description
0x80 Device malfunction: The device detected a serious error or failure that
compromises device operation.
0x40 Configuration changed: An operation was performed that changed the
device's
configuration.
0x20 Cold start: A power failure or Device Reset has occurred.
0x10 More status available: More status information is available via Command 48, Read
Additional Status Information.
0x08 Loop current fixed: The Loop Current is being held at a fixed value and is not
responding to process variations.
0x04 Loop current saturated: The Loop Current has reached its upper (or lower)
endpoint limit and cannot increase (or decrease) any further.
0x02 Non-Primary variable out of limits: A Device Variable not mapped to the PV is
beyond its operating limits.
0x01 Primary variable out of limits: The PV is beyond its operating limit.
3. The way to import register map file:
The user may use the way of importing file to set gateway register map, only CSV file is supported.
1) Click Select file , choose the window to upload file.
2) Choose CSV file to upload.
3) Click Import to upload the file.
4) If the upload is successful, it will show Upload a file successfully .
Caution
CSV file shall be edited in the particular format.
1. Table format, includes register start address and register name.
2. Register name format is device tag, device variable ,device ID , and device variable name
value is shown in
Table 4-1
.
3. Register start address must be in the defined range, shown in Table 4-3.
4. Register addresses should not be overlapped.
5. The file size is 500KB at most.