User's Manual

http://www.microcyber.cn
27
Device ID:
The long address of the wireless field device that generated the data. Note: The device
ID is not recommended for users to fill in. When the device label is selected, the device ID will be
automatically mapped.
3. How to import OPC mapping files:
You can configure the OPC mapping of the gateway by importing files. Only CSV files are
supported.
1)
Click the "Browse..." button to pop up the window for selecting the upload file.
2)
Select the CSV file to upload.
3)
Click the "Import" button to upload the file.
If the upload is successful, it will jump to the page to display "Upload file is successful."
If the upload fails, it will jump to the page saying "Failed to upload the file."
Note
CSV files must be written in the prescribed format:
Table mode, including the OPC mapping name column.
The format of the name is composed of the device label, device variable, and device ID. For
the value of the device variable name, see
Table 4-1
.
The maximum file size is 500KB.
Click the "Export" button to store the OPC mapping table of the gateway as a CSV file on the
PC/laptop.
4.6 HART-IP
HART-IP allows the HART protocol to be transmitted over Ethernet and provides valuable HART
data. Field device measurement and diagnostic information can be integrated into the control
system.
The TCP port number of HART-IP is: 8882;
The UDP port number of HART-IP is: 8885.