Use and Care

11
// www.micromatic.com
4.3 ELECTRONIC (DIGITAL) TEMPERATURE CONTROL
HOW TO SEE THE SET POINT
1. Push and immediately release the key, the set point will be displayed.
2. Push and immediately release the key or wait about ve (5) seconds to return
to normal display.
HOW TO CHANGE THE SET POINT
1. To change the set point number, push the key for more than two (2) seconds.
2. The number of the set point will be displayed and the “ ” or “ ” LED will blink.
3. To change the set number push the arrow up or down keys within ten (10) seconds.
4. To hold the new set point number push the key again or wait ten (10) seconds.
NOTE: The minimum value that you can set in the controller is 32°F (0°C) and the
maximum value you can set is 40°F (4.4°C)
4.4 DEFROST
The equipment with electronic controller will not require manual defrost due the
equipment has an automatic defrost every 6 hours. If a manual defrost is required
push and hold the defrost button for 5 seconds then the equipment will start defrost.
For equipment with manual thermostat a manual defrost could be required, unplug the
equipment from the power supply for 15 minutes and leave the door open. Continue
until ice melts.