MicroMod Automation, Inc. The Company MicroMod Automation is dedicated to improving customer efficiency by providing the most cost-effective, application-specific process solutions available. We are a highly responsive, application-focused company with years of expertise in control systems design and implementation. We are committed to teamwork, high quality manufacturing, advanced technology and unrivaled service and support.
IB-23C003 CONTENTS –––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– CONTENTS Page SECTION 1 - INTRODUCTION 1.1 1.2 1.3 1.3.1 1.3.2 1.4 1.5 DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . EXPLANATION OF SERIAL AND CATALOG NUMBER . . . . . . . . . . . . . . . . . . PRODUCT DESCRIPTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1731N Mini Link Board for AT Style PC ............
IB-23C003 CONTENTS ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– TABLES Table 2-1 2-2 2-3 2-4 2-5 2-6 3-1 A-1 A-2 B-1 B-2 B-3 ii Personal Computer Device Inventory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DIP Switch SW2, PC/AT Serial Port Base Address ...................... Mini Link Hardware Interrupts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Mini Link Interrupt Polarity . . . . . . . . . . . . . . . .
IB-23C003 INTRODUCTION SECTION 1 INTRODUCTION 1.1 DESCRIPTION The 1731N Mini Link with 1732N ICN Interface Board, Figure 1-1, provides a general purpose serial interface to MOD 30 and MODCELL instruments via the Instrument Communications Network (ICN). The 1731N Mini Link supports one ICN and the 1732N ICN Interface Board supports a second ICN.
IB-23C003 INTRODUCTION Physically the Mini Link is a PC/AT plug-in module which completely emulates the 1720N Communications Link (refer to IB-23C001) for up to two Instrument Communications Networks. The base configuration consists of: • An Integral PC/AT Serial Port (dedicated to the Mini Link) This serial port is DIP switch and jumper configurable to perform as an I/O-mapped memory device at I/O base addresses 000h through 3F8h.
IB-23C003 INTRODUCTION Sample Serial No. 1731N Z 10 1 01 A – 555 Base Number Unused Catalog Number Electrical Code ICN Interface Firmware Model/Design Level Sequential Identification Number 1.3 PRODUCT DESCRIPTIONS The following product is maintained at the serial and catalog number level. descriptions included in this section give a brief overview of its functions and features. The 1.3.
IB-23C003 INTRODUCTION 1.3.2 1732N ICN Interface Board The ICN Interface Board is an ICN controller card only and is used to add a second ICN to the 1731N when the option board was not originally specified. The central processor is the 63B09E using an 8-bit bus and a 2 mHz dual phase clock.
IB-23C003 INTRODUCTION 1.4 TECHNICAL SUMMARY POWER REQUIREMENTS 1731N Mini Link Board for AT Style PC +5VDC at 0.8 Amp provided by personal computer +24VDC at 0.2 Amp generated on Mini Link board PHYSICAL CHARACTERISTICS Card Dimensions (Including Card Edge Connector) 1731NZ10101A Length: 13.26 inches (336.80 mm) Width: 4.75 inches (120.65 mm) Height: 0.70 inches (17.
IB-23C003 INTRODUCTION PERFORMANCE CHARACTERISTICS Absolute Maximum Ratings* Temperature Under Bias: 0°C to +60°C ( 32°F to 140°F) Storage Temperature: –40°C to +85°C (–40°F to 185°F) Power Dissipation: 10W Ambient Temperature Specifications Operating: +4°C to +49°C +(40°F to +120°F) Storage: -40°C to +74°C (–40°F to +165°F) Relative Humidity 5 to 90% RH at 32°C I/O Mapping: Supports I/O mapping on any 8-byte boundary between 000h and 3F8h (cannot be installed as a memory mapped device).
IB-23C003 INTRODUCTION 1.5 RELATED DOCUMENTATION Additional reference information on ICN/Link communications can be found in the following documents.
IB-23C003 INTRODUCTION 1-8
IB-23C003 INSTALLATION SECTION 2 INSTALLATION 2.1 PREPARING THE PERSONAL COMPUTER Prepare your PC/AT as follows: 1. Turn off the system unit. 2. Turn off all external options (printer, display, etc.). 3. Unplug the system unit power cord from the electrical outlet. 4. Unplug any external options from the electrical outlet. 5. Remove the system unit cover mounting screws. 6. Remove the system unit cover. 7. Use Table 2-1 as a worksheet to record the types of devices already installed in your system unit.
IB-23C003 INSTALLATION 2.2 DETERMINING MINI LINK BASE ADDRESS/INTERRUPT LEVEL The total I/O address space required by the Mini Link is eight bytes in length. To guarantee operation, the selected base address must be at least eight bytes below any base address listed in Table 2-1. Generally, if there are no serial devices (mouse, modem, or RS-232 serial card) any of the standard COMx locations can be selected. These addresses have been reproduced in this document. See the Section 2.
IB-23C003 INSTALLATION 2.4 SWITCH AND JUMPER SETTINGS This section contains a brief description of the Mini Link switches and jumpers with an application table for each. A quick reference table of all switches, jumpers, and their functions is in Appendix A. 2.4.1 Serial Ports The Mini Link has two serial ports. Each serial port can be configured with an independent baud rate and CTS signal for access by two controlling consoles.
IB-23C003 INSTALLATION Hardware Interrupts and Polarity for PC/AT Serial Port The Mini Link hardware interrupt levels may be set as shown in Table 2-3. polarity is set as shown in Table 2-4. Interrupt Table 2-3. Mini Link Hardware Interrupts Jumper IN Interrupt Level W15 W16 W17 W18 W19 IRQ3 Y N N N N IRQ4 N Y N N N IRQ5 N N Y N N IRQ6 N N N Y N IRQ7 N N N N Y Table 2-4.
IB-23C003 INSTALLATION Table 2-6. Mini Link External Serial Port Baud Rates Jumper IN BAUD W12 W11 W10 W9 W8 76800* Y N N N N 38400* N Y N N N 19200 N N Y N N 9600 N N N Y N * Not recommended for use with currently available software. Clear-To-Send (CTS) for Serial Ports 1 and 2 Both the PC/AT and the External Serial Ports are outfitted with a CTS connection. In most cases, the CTS signal will not be needed.
IB-23C003 INSTALLATION 2.4.2 ICN ICN Isolation The Mini Link is fitted with Opto-isolation components capable of providing a minimum of 3000 VDC electrical insulation between the Instrument Communication Network and the PC/AT digital circuitry. This option is jumper-selectable by disabling the connection on W23 (remove this jumper to enable optical isolation). If optical isolation is enabled, the ICN connector must be fitted with a ground wire.
IB-23C003 PROGRAMMING MINI LINK INTERRUPTS SECTION 3 PROGRAMMING MINI LINK INTERRUPTS 3.1 GENERAL The IBM PC/AT has reserved hardware interrupts for common devices (printers, disk drives, etc.) within the interrupt level range (IRQ3-IRQ7) of the Mini Link. The Mini Link does not support the high order (8-15) interrupt request lines available on the IBM PC/AT. To operate the Mini Link on COM1, COM2, COM3 or COM4, the jumper settings from Tables 2-2, 2-3 and 2-4 must be employed exactly as they appear.
IB-23C003 PROGRAMMING MINI LINK INTERRUPTS Interrupt Service Routine Location It is the user's responsibility to install an Interrupt Service Routine at an appropriate memory location (according to the configured hardware interrupt) which does not interfere with concurrently operated software or hardware. In most cases, these interrupt service routines will be simple Transmit/Receive operations with user conditions determining success or failure of the routines.
IB-23C003 TROUBLESHOOTING THE MINI LINK SECTION 4 TROUBLESHOOTING THE MINI LINK 4.
IB-23C003 TROUBLESHOOTING THE MINI LINK 4.3 FROZEN DISPLAY/NO RESPONSE FROM PC KEYBOARD This type of problem is usually indicative of address or interrupt conflict on the personal computer I/O channel. You must establish a clear range of eight bytes I/O address space (in the range 000h to 3FFh) to successfully operate the Mini Link. In addition, there can be no other installed devices using the same interrupt request line as the Mini Link.
IB-23C003 APPENDIX A - JUMPERS AND SWITCHES APPENDIX A JUMPERS AND SWITCHES S-3002-134A Figure A-1. Switch and Jumper Locations for 1731N Mini Link Table A-1. Alphanumeric Listing of Jumpers and Switches for 1731N Mini Link Ref. Function Ref.
IB-23C003 APPENDIX A - JUMPERS AND SWITCHES Figure A-2. Switch and Jumper Locations for 1732N ICN Interface Board Table A-2. Alphanumeric Listing of Jumpers and Switches for 1732N ICN Interface Board Ref. Function J2 Select ICN1 Baud Rate of 31,250 bps J3* Select ICN1 Baud Rate of 62,500 bps U1 Mini Link ICN1 Device Address * Firmware support for this baud rates is currently unavailable.
IB-23C003 APPENDIX B - CONNECTOR DESCRIPTIONS APPENDIX B CONNECTOR DESCRIPTIONS Table B-1.
IB-23C003 APPENDIX B - CONNECTOR DESCRIPTIONS Table B-2. Mini Link RS-232 Connector Pinout * I/O Pin Signal Name I/O 1 GND GND 2 RXDATA I 3 TXDATA O 4 NC - 5 GND GND 6 NC - 7 RTS I 8 CTS O 9* NC - Pin 9 can be configured to present Mini Link's 5VDC (for test purposes only) by using jumper W22. Table B-3. Mini Link ICN0 and ICN1 Connector Pinout * Terminal Signal Name* 1 IBUS(+) 2 IBUS(–) GND GND Two- or Three-Wire Connection for ICN0 and ICN1.
The Company’s policy is one of continuous product improvement and the right is reserved to modify the information contained herein without notice, or to make engineering refinements that may not be reflected in this bulletin. Micromod Automation assumes no responsibility for errors that may appear in this manual. © 2004 MicroMod Automation, Inc. Printed in USA IB-23C003, Issue 2 04/2005 MicroMod Automation, Inc. 75 Town Centre Drive Rochester, NY USA 14623 Tel. 585-321 9200 Fax 585-321 9291 www.