Instruction Manual

Logic Functions - Book 1
MODCELL SERIAL COMMUNICATION BLOCK
4-31
50-54 Discrete Read/Write List 1 - 5 (DRWLISTn) ................................................................... C – R
These values represent configured lists which make up the discrete read/write lists (1 through
5) for this Modbus port. List 1 has a memory range of (00001 - 00099); list 2 has a memory
range of (00101 - 00199); list 3 has a memory range of (00201 - 00299); list 4 has a memory
range of (00301 - 00399); and list 5 has a memory range of (00401 - 00499). The selected
configured list must be configured, have a buffer allocated, and every variable in the list must
be a discrete data type or NONE. Nested lists are not allowed.
NONE No configured list. Read as 0.
CL10 to CL4096 The number of the Configured List (CL) block that makes up the
discrete read/write list for this Modbus port. Read as the number of
the Configured List (10 to 4096).
55-59 Discrete Read Only List 1 - 5 (DROLISTn)..................................................................... C – R
These values represent configured lists which make up the discrete read only lists (1 through
5) for this Modbus port. List 1 has a memory range of (10001 - 10099); list 2 has a memory
range of (10101 - 10199); list 3 has a memory range of (10201 - 10299); list 4 has a memory
range of (10301 - 10399); and list 5 has a memory range of (10401 - 10499). The selected
configured list must be configured, have a buffer allocated, and every variable in the list must
be a discrete data type or NONE. Nested lists are not allowed.
NONE No configured list. Read as 0.
CL10 to CL4096 The number of the Configured List (CL) block that makes up the
discrete read/write list for this Modbus port. Read as the number of
the Configured List (10 to 4096).
60-64 Single Register Read/Write List 1 - 5 (SRWLISTn)........................................................ C – R
These values represent Modbus lists which make up the single read/write register for the lists
(1 through 5) for this Modbus port. List 1 has a memory range of (40001 - 40099); list 2 has a
memory range of (40101 - 40199); list 3 has a memory range of (40201 - 40299); list 4 has a
memory range of (40301 - 40399); and list 5 has a memory range of (40401 - 40499). The
Modbus list block specified must be configured.
NONE No Modbus list. Read as 0.
ML1 to ML4096 The number of the Modbus List (ML) block that makes up the single
read/write register list for this Modbus port. Read as the number of
the Modbus List (1 to 4096).
65-69 Single Register Read Only List 1 - 5 (SROLISTn) ......................................................... C – R
These values represent Modbus lists which make up the single read only register for the lists
(1 through 5) for this Modbus port. List 1 has a memory range of (30001 - 30099); list 2 has a
memory range of (30101 - 30199); list 3 has a memory range of (30201 - 30299); list 4 has a
memory range of (30301 - 30399); and list 5 has a memory range of (30401 - 30499). The
Modbus list block specified must be configured.
NONE No Modbus list. Read as 0.
ML1 to ML4096 The number of the Modbus List (ML) block that makes up the single
read only register list for this Modbus port. Read as the number of
the Modbus List (1 to 4096).