Instruction Manual
Logic Functions - Book 1
DIGITAL OUTPUT MODULE BLOCKS (DOM, DDOM, WDOM)
5-17
Table 5-4. Wide Digital Output Module Block Attributes, Valid Values, Mnemonics, and Data Types
Field Name /
Attribute
Mnemonic Valid Values CWR Data Type Attr
Version VERSION 1 – – R Long State 00
Block Length BLKLEN – – R Count 01
State
STATE RUN (0) – – R Short State 02
Bad Inputs
BADINP Rejected (0), Accepted (1) CWR Discrete 03
Diagnostic Group
SUPPGRP NONE, 1 to 7 CWR Long State 04
I/O mismatch
MODMMS ENABLE (0), SUPPRESS (1) CWR Discrete 05
Unacked I/O Mismatch
MODMMU NO (0), YES (1) – WR Discrete 06
Active I/O Mismatch
MODMMA NO (0), YES (1) – – R Discrete 07
WDOM Module Error
WDOMERRS
ENABLE (0), SUPPRESS (1) CWR Discrete 08
Unacked DO Module Error
WDOMERRU
NO (0), YES (1) – WR Discrete 09
Active DO Module Error
WDOMERRA
NO (0), YES (1) – – R Discrete 10
I/O Module Mismatch MODMM FALSE (0), TRUE (1) – – R Discrete 11
Board Number
BOARD 1 – – R Long State 12
Slot Number
SLOT 1 to 32 – – R Long State 13
Action
ACTION REVERSE (0), DIRECT (1) CWR Discrete 14
Mode
MODE MANUAL (0), AUTO (1) CWR Discrete 15
Output to use on restart
RESTART PREVIOUS (0), PRESET (1) CWR Discrete 16
Preset Output Value
PRESET FALSE (0), TRUE (1) CWR Discrete 17
Failsafe Output Value
FSOUT FALSE (0), TRUE (1),
FS HOLD (2)
CWR Short State 18
Track Status TRKSTAT NO TRACK (0), TRACK (1) – WR Discrete 19
Track Status Quality TRKQ GOOD (0), BAD (1) – WR Discrete 20
Initial Scaled Result Value
RSC FALSE (0), TRUE (1) CWR Discrete 21
Scaled Readback
RBSC FALSE (0), TRUE (1) – – R Discrete 22
Input
INPUT LSP, FALSE (0), TRUE (1) CWR Discrete 23
Readback
RB FALSE (0), TRUE (1) – – R Discrete 24
Readback Quality RBQ GOOD (0), BAD (1) – – R Discrete 25
Result
R FALSE (0), TRUE (1) – – R Discrete 26
Result
Quality
RQ GOOD (0), BAD (1) – WR Discrete 27