Instruction Manual

Logic Functions - Book 1
DIGITAL OUTPUT MODULE BLOCKS (DOM, DDOM, WDOM)
5-20
DOM 09
Unacked DOM Module Error
(DOMERRU) ......................................................................– WR
DDOM 09
Unacked DDOM1 Module Error
(DDOERRU1)................................................................– WR
DDOM 12
Unacked DDOM2 Module Error
(DDOERRU2)................................................................– WR
WDOM 09
Unacked WDOM Module Error
(WDOMERRU) ...............................................................– WR
If this diagnostic error is enabled, the unacknowledged DO module diagnostic status indicates
if the diagnostic is or is not acknowledged. The status can be acknowledged or read as
follows.
YES 1 Diagnostic error is unacknowledged.
NO 0 Diagnostic error is acknowledged.
DOM 10
Active DOM Module Error
(DOMERRA)........................................................................... – – R
DDOM 10
Active DDOM1 Module Error
(DDOERRA1) .................................................................... – – R
DDOM 13
Active DDOM2 Module Error
(DDOERRA2) .................................................................... – – R
WDOM 10
Active WDOM Module Error
(WDOMERRA).................................................................... – – R
If this diagnostic error is enabled, the active DO module diagnostic status indicates if the error
is active even after acknowledgement. The status can be read as follows.
YES 1 Diagnostic error is active.
NO 0 Diagnostic error is not active.
DOM 11
I/O Module Mismatch
(MODMM) ...................................................................................... – – R
DDOM 14
I/O Module Mismatch
(MODMM) ...................................................................................... – – R
WDOM 11
I/O Module Mismatch
(MODMM) ...................................................................................... – – R
Even though the I/O mismatch diagnostic may be suppressed and its value not stored with the
active I/O mismatch attribute, the actual I/O mismatch condition can still be determined by this
attribute (value is unsuppressed). This attribute is used to determine if there is an I/O
mismatch when changing the I/O mismatch diagnostic from suppressed to enabled.
YES 1 Diagnostic error is active.
NO 0 Diagnostic error is not active.
DOM 12
Board Number
(BOARD)................................................................................................... – – R
DDOM 15
Board Number
(BOARD)................................................................................................... – – R
WDOM 12
Board Number
(BOARD)................................................................................................... – – R
This is the board number that the physical module is configured for. Currently, the only valid
value is one.
DOM 13
Slot Number
(SLOT).......................................................................................................... – – R
DDOM 16
Slot Number
(SLOT).......................................................................................................... – – R
WDOM 13
Slot Number
(SLOT).......................................................................................................... – – R
This is the first slot number that the physical module is configured for. The valid values are 1
to 32 for DOM modules and 1 to 13, 15, 17, or 19 to 31 for DDOM and WDOM modules.
DOM 14
Action
(ACTION)................................................................................................................ CWR
DDOM 17
Action
(ACTION1).............................................................................................................. CWR
DDOM 27
Action
(ACTION2).............................................................................................................. CWR
WDOM 14
Action
(ACTION)................................................................................................................ CWR
The action is applied to the result before being sent to the output module and it is applied to
the output again to get the readback value.
REVERSE 0 The result is inverted before being sent to the output module.
DIRECT 1 The result is sent to the output module without change.