Instruction Manual

Logic Functions - Book 1
ANALOG INPUT MODULE BLOCKS (VCIM, TIM, RIM, WRIM)
5-41
VCIM 12
Unacked Input Module Error
(VCIMERRU)..................................................................... – WR
TIM 12
Unacked Input Module Error
(TIMERRU) ....................................................................... – WR
RIM 12
Unacked Input Module Error
(RIMERRU) ....................................................................... – WR
WRIM 12
Unacked Input Module Error
(WRIMERRU).................................................................... – WR
If the module error diagnostic is enabled, this unacknowledged status indicates if the
diagnostic is or is not acknowledged. The status can be acknowledged or read as follows.
YES 1 Diagnostic error is unacknowledged.
NO 0 Diagnostic error is acknowledged.
VCIM 13
Active Input Module Error
(VCIMERRA) ......................................................................... – WR
TIM 13
Active Input Module Error
(TIMERRA)............................................................................ – WR
RIM 13
Active Input Module Error
(RIMERRA)............................................................................ – WR
WRIM 13
Active Input Module Error
(WRIMERRA) ........................................................................ – WR
If the module error diagnostic is enabled, the active status indicates if the error is active even
after acknowledgement. The status can be read as follows.
YES 1 Diagnostic error is active.
NO 0 Diagnostic error is not active.
14
I/O Module Mismatch
(MODMM).......................................................................................– – R
Even though the I/O mismatch diagnostic may be suppressed and its value not stored with the
active I/O mismatch attribute, the actual I/O mismatch condition is still determined. This
unsuppressed I/O mismatch is used to determine if an I/O mismatch exists when changing the
I/O mismatch diagnostic from suppressed to enabled.
YES 1 Diagnostic error is active.
NO 0 Diagnostic error is not active.
15
Board number
(BOARD)....................................................................................................– – R
This is the board number that the physical module is configured for. Currently, the only valid
value is 1.
16
Slot number
(SLOT)...........................................................................................................– – R
This is the slot number that the physical module is configured for. Valid values are 1 to 32 for
the VCIM, TIM, and RIM and 1 to 16 for the WRIM.
17
Module id
(MODID) ............................................................................................................– – R
The module id is read as part of the initialization process. This value is compared with the
configured block type to determine if there is a module mismatch.