Instruction Manual
Logic Functions - Book 1
ANALOG OUTPUT MODULE BLOCK (AOM)
5-51
5.5.2 Analog Output Module Block Parameters
The mnemonics, valid values, and data types for all fields that may be selected for display
and/or be used in making softwiring connections are listed in Table 5-10. The following further
defines the analog output module block configuration parameters.
Table 5-10. Analog Output Module Block Attributes, Valid Values, Mnemonics, and Data Types
Field Name /
Attribute
Mnemonic Valid Values CWR Data Type Attr
Version VERSION – – R Long State 00
Block Length BLKLEN – – R Count 01
State
STATE RUN (0) – – R Short State 02
Bad Inputs
BADINP Rejected (0), Accepted (1) CWR Discrete 03
Diagnostic Group
SUPPGRP NONE, 1 to 7 CWR Long State 04
I/O Mismatch
MODMMS ENABLE (0), SUPPRESS (1) CWR Discrete 05
Unacked I/O Mismatch
MODMMU NO (0), YES (1) – WR Discrete 06
Active I/O Mismatch
MODMMA NO (0), YES (1) – – R Discrete 07
AO module comm. error
COMMERRS
ENABLE (0), SUPPRESS (1) CWR Discrete 08
Unacked AO comm. Error
COMMERRU
NO (0), YES (1) – WR Discrete 09
Active AO comm. Error
COMMERRA
NO (0), YES (1) – – R Discrete 10
AO module Error
AOMERRS ENABLE (0), SUPPRESS (1) CWR Discrete 11
Unacked AO module Error
AOMERRU NO (0), YES (1) – WR Discrete 12
Active AO module Error
AOMERRA NO (0), YES (1) – – R Discrete 13
I/O Mismatch MODMM FALSE (0), TRUE (1) – – R Discrete 14
Board Number BOARD 1 – – R Long State 15
Slot Number SLOT 1 to 32 – – R Long State 16
Module ID MODID FD0500 – – R Hex 17
Extended Error EXTERR 0 to 65535 – WR Count 18
Mode
MODE MANUAL (0), AUTO (1) CWR Discrete 19
Action
ACTION REVERSE (0), DIRECT (1) CWR Discrete 20
Input Range, Top
INHI Floating Pt Value, E.U. CWR Floating Pt 21
Input Range, Bottom
INLO Floating Pt Value, E.U. CWR Floating Pt 22
Output Range, Top
OUTHI Floating Pt Value, Sig. Rng. CWR Floating Pt 23
Output Range, Bottom
OUTLO Floating Pt Value, Sig. Rng. CWR Floating Pt 24
Output to use on restart
RESTART PREVIOUS (0), PRESET (1) CWR Discrete 25
Output to use on failsafe
FSACT HOLD (0), PRESET (1) CWR Discrete 26
Restart preset value PRESET Floating Pt Value, E.U. CWR Floating Pt 27
Failsafe preset value
FSOUT Floating Pt Value, E.U. CWR Floating Pt 28
Track status
TRKSTAT NO TRACK (0), TRACK (1) – WR Discrete 29
Track status data quality
TRKQ GOOD (0), BAD (1) – WR Discrete 30
Scaled result
RSC Floating Pt Value, E.U. – WR Floating Pt 31
Scaled readback
RBSC Floating Pt Value, E.U. – – R Floating Pt 32
Local
Input
INPUT LSP or Floating Pt Value, E.U. CWR Floating Pt 33
Readback
RB Floating Pt Value, Sig. Rng. – – R Floating Pt 34
Readback Quality
RBQ GOOD (0), BAD (1) – – R Discrete 35
Initial result
(Result)
R Floating Pt Value, Sig. Rng. C – R Floating Pt 36
Result Quality
RQ GOOD (0), BAD (1) – WR Discrete 37