Instruction Manual

Logic Functions - Book 1
ANALOG INPUT BLOCKS (VCI, TII, TI, RI, RTI, RTTI)
7-12
Table 7-3. Thermocouple Input Block Attributes, Valid Values, Mnemonics, and Data Types
Field Name /
Attribute
Mnemonic Valid Values CWR Data Type Attr
Version VERSION 1 – – R Long State 00
Block Length BLKLEN – – R Count 01
State
STATE RUN(0), HOLD(1), OFF(2),
DEBUG(3)
CWR Short State 02
Bad Inputs Accepted
BADINP NO (0), YES (1) CWR Discrete 03
Diagnostic Group Supp.
SUPPGRP NONE, 1, 2, 3, 4, 5, 6, 7 CWR Long State 04
Calculation Error
CERRS ENABLE (0), SUPPRESS (1) CWR Discrete 05
Calc. Error Unacked
CERRU NO (0), YES (1) – WR Discrete 06
Calc. Error Unacked Quality
CERRUQ NO (0), YES (1) – WR Discrete 07
Calc. Error Active
CERRA NO (0), YES (1) – WR Discrete 08
Calc. Error Active Quality
CERRAQ NO (0), YES (1) WR Discrete 09
Set quality bad on calc err?
SETQBAD NO (0), YES (1) CWR Discrete 10
Temperature Scale
SCLTYPE FAHRENHEIT(0),CELSIUS(1),
RANKINE(2), KELVIN(3)
CWR Short State 11
Filter Type
FILTYPE NONE(0), AUTO(1), USER(2) CWR Short State 12
Filter Time
FILTIME 0 to 1000 (minutes) CWR Floating Pt 13
Output Calibrate - Zero
ZERO value (in temperature units) CWR Floating Pt 14
Output Calibrate - Span
SPAN value (multiplier) CWR Floating Pt 15
Quality Limit - Top
QUALHI value (in temperature units) CWR Floating Pt 16
Quality Limit - Bottom
QUALLO value (in temperature units) CWR Floating Pt 17
Initial Value (
Result
)
R value (in temperature units) CWR Floating Pt 18
Result Data Quality RQ GOOD (0), BAD (1) – WR Discrete 19
Cold Junction Comp. Input CJCINP NONE, value, LSP CWR Floating Pt 20