User Manual

IB-23C650M
CONTROLLER ATTRIBUTE LISTING - REGISTER DATA
Tuning Parameter Data (registers) Cont’d
Reg.
#
Description Register Value
2050R
Displayed Value
55
R W
Gain or heat gain value 1 to 30000 0.1 to 3000.0
56
R W
Reset or heat reset 10 to 12000 0.01 to 120.00
repeats/minute
57
R W
Preact value 0 to 30000 0.0 to 3000.0
seconds derivative
response
58
R W
Manual reset value 0 to 1000 0.0 to 100.0%
59
R W
Remote set-point ratio or AMRB ratio -30000 to 30000 -300.00to 300.00
60
R W
Remote set-point bias or AMRB bias
Register #9, bits 1 & 0 = 0
Register #9, bits 1 & 0 = 1
Register #9, bits 1 & 0 = 2
Register #9, bits 1 & 0 = 3
-30000 to 300000
-30000 to 300000
-30000 to 300000
-30000 to 300000
-3000 to 30000
-300.0 to 3000.0
-30.00 to 300.00
-3.000 to 30.000
61
R W
Time proportioning cycle time or heat
cycle time
10 to 3000 1.0 to 300.0 sec.
62
R W
On/off differential gap
Register #9, bits 1 & 0 = 0
Register #9, bits 1 & 0 = 1
Register #9, bits 1 & 0 = 2
Register #9, bits 1 & 0 = 3
0 to 1000
0 to 1000
0 to 1000
0 to 1000
0 to 100
0.0 to 10.0
0.00 to 1.00
0.000 to 0.100
63
R W
Heat/cool output crossover 1 to 3000 0.1 to 300.0%
64
R W
Crossover output off hysteresis 0 to 250 0.0 to 25.0 in %
output centered on
crossover value
(±25%)
65
R W
Cool gain value 1 to 30000 0.1 to 3000.0
66
R W
Cool reset value 10 to 1200 0.1 to 120.0
repeats/minute
67
R W
Cool cycle time value 10 to 3000 1.0 to 300.0 sec.
68
R W
Position proportioning deadband value 0 to 500 0.0 to 50.0%
69
R W
Position proportioning preact value 0 to 500 0.0 to 50.0%
45