MODCELL 2050R Indicating Process Controller 2050R Model B Version 2.8 2051R Model B Version 2.
MicroMod Automation, Inc. The Company MicroMod Automation is dedicated to improving customer efficiency by providing the most cost-effective, applicationspecific process solutions available. We are a highly responsive, application-focused company with years of expertise in control systems design and implementation. We are committed to teamwork, high quality manufacturing, advanced technology and unrivaled service and support.
IB-23C650 CONTENTS CONTENTS Page Introduction Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Identification Information . . . . . . . . . . . . . . . . . . . . . . . Installation General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IB-23C650 CONTENTS CONTENTS (Cont’d) Engineering Displays . . . . . . . . . . . . . . . . . . . . . . . . . Status Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bar Graphs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Alarm Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Restart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operation in Automatic Mode . . . . . . . . . . . . . . . . . . . . Auto/Manual Transfer . . . . . .
IB-23C650 CONTENTS CONTENTS (Cont’d) Page Diagnostics Input Failure and Power Failure Detection . . . . . . . . . . Diagnostic Messages . . . . . . . . . . . . . . . . . . . . . . . . . Input Failure Messages and Responses . . . . . . . . . . . . Operational Failure Messages . . . . . . . . . . . . . . . . . . . Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . Calibration Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Parts and Maintenance . . . . . . . . . . . . .
IB-23C650 CONTENTS ILLUSTRATIONS (Cont’d) Figure 21 Effect of Ratio Adjustment in a Direct Ratio Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Effect of Ratio Adjustment in an Inverse Ratio Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Effect of Ratio Adjustment on a Ratio Relationship . . . 24 A/M Ratio Bias Station . . . . . . . . . . . . . . . . . . . . . . 25 Example of an A/M Ratio Station Application . . . . . . .
IB-23C650 INTRODUCTION INTRODUCTION FEATURES • Isolated universal process and remote set-point input • Four internal set-points • No jumpers required to define instrument parameters • Ratio/bias on process and remote set-point • Totalizer • Ramp/soak profile • On-demand auto-tuning • Retransmission of process, set-point, or input number 2 • Output tracking of electrical input number 2 • Linearization with sq. rt.
IB-23C650 INTRODUCTION Ranging of the RTD and Thermocouple is automatic. The process input is isolated from the rest of the instrument. A 24V dc transmitter power supply is provided for use with a two-wire mA dc input on both process and remote setpoint inputs. When the controller is equipped with an option card, RS-485 communication capability is provided via either a 2-wire or 4-wire bus.
IB-23C650 INTRODUCTION Data Plate 3
IB-23C650 INTRODUCTION Blank Page 4
IB-23C650 INSTALLATION INSTALLATION GENERAL Read these instructions thoroughly before starting installation. Installation personnel should be qualified technicians. Observe all electrical code requirements and safety standards during installation. Installing the controller involves: • Unpacking • Mounting • Wiring Connections Displays and Cleaning The display is protected by an overlay that can be removed after installation.
IB-23C650 INTRODUCTION Notes: 1. When mounting housing in panel cutout or rack and panel mounting bezel, turn retaining screws until point of screw touches rear of panel or bezel. Overtightening of retaining screws will distort housing. Housing must be square after retaining screws are tightened. 2. MODCELL 2051R does not use the gasket and has a bezel width of 2.735” (69.47 mm). The panel cutout may be for the 2050R Figure 1. Mounting Dimensions.
IB-23C650 INSTALLATION MOUNTING The controller must be installed in an approved enclosure or installed in a means acceptable to the authority having jurisdiction for electrical installations. Select a mounting location where there is minimum vibration. The ambient temperature must be between 32 and 131°F (0 and 55°C) with a relative humidity of 25-95% RH (noncondensing). The panel must provide rigid support for the 3.2-pound (1.45 kg) controller and any other panel devices.
IB-23C650 INSTALLATION WIRING GUIDELINES The power wiring connections and input/output (I/O) connections are made with the controller installed in its operating location and with the power off. The rear view of the controller housing in Figure 2 shows the terminals available for inputs and outputs (rear cover removed). CAUTION Do not connect any wires to terminals 36, 37, 38, 39, and 40. Connections to these terminals can cause an instrument malfunction. The recommended wiring procedure is as follows: 1.
IB-23C650 INSTALLATION Chassis Relay A (NO) Relay A (C) Relay A (NC) Relay B (NO) Relay B (C) Relay B (NC) Relay C (NO) Relay C (C) Relay C (NC) TX Power CAUTION Volt Input RTD Src mA Inpt + Input – Do not make connections to these terminals mA Output COM TX Power 2 Volt Input 2 RS-485 Connections see Supplement IB-23C650M RTD Src 2 DI2 mA Inpt2 + DI1 Inpt2 – mA Outpt2 COM Chassis Not Connected AC Line, DC+ AC Neutral, DC– Chassis S-3017-7A(3) Ground Connection Figure 2.
IB-23C650 INSTALLATION POWER CONNECTIONS WARNING Avoid electrical shock. AC power wiring must not be connected at the distribution panel (ac source) until all wiring procedures are completed. All power wiring must be in compliance with the requirements of the National Electrical Code or Canadian Electrical Code. In any installation where the power source does not have one side of the line connected as a neutral conductor, both sides of the line must be overcurrent protected.
IB-23C650 INSTALLATION GROUND CONNECTIONS The primary power ground system consists of the plant electrical ground (equipment grounding conductors). AC ground and chassis ground are connected when the termination housing is connected to the control module. If this path is insufficient to dampen out noise spikes on the ac line, the chassis ground may be connected directly to panel ground. The circuit common for all signals is negative.
IB-23C650 INSTALLATION The combination device suppresses transients and effectively reduces other noise forms such as electromagnetic (EMI) and radio frequency (RFI) interferences. These devices can be connected to multiple units to reduce overall cost. Input signals • Twisted wire pairs are essential. The wire type should be stranded, not solid. The largest wire gauge allowed is best and the more twists per foot the better. A 2-inch lay (6 twists per foot) should be the minimum used.
IB-23C650 INSTALLATION PROCESS INPUT SIGNAL CONNECTIONS Process input connections are shown as follows: • Thermocouple Inputs - see Figure 3 • RTD Inputs - see Figure 4 • mA Inputs from 2-Wire Transmitters - see Figure 5 • mA Inputs from Non 2-Wire Transmitters - see Figure 6 • Volt Inputs - see Figure 7 • mV Inputs - see Figure 8 • Digital Inputs - see Figure 9 • Motorized Valve Inputs - see Figure 10 • Slidewire Inputs - see Figure 10 NOTE: Input 2 is available when an option card is installed.
IB-23C650 INSTALLATION THERMOCOUPLE INPUT UNGROUNDED GROUNDED Thermocouple Shield Twisted or Shielded Pair Thermocouple Wire + + Shield t° t° Note – – Red Wire Note Note: Connect 100 ohm thermistor supplied with instrument for cold junction compensation. Figure 3. Thermocouple Input Connections Thermocouple input specifications are: Thermocouple: Automatic ranging and linearization Type B*: 752 to 3002°F (400 to 1650°C) *Performance accuracy is not guaranteed below 752°F.
IB-23C650 INSTALLATION RTD INPUT 3-WIRE RTD 2-WIRE RTD t° Shield t° Note Shield Note: 4-Wire RTD connected same as 3-wire RTD with fourth lead unused. Figure 4. RTD Input Connections RTD input specifications are: RTD Type: 3-Wire Platinum, 100 ohm, RTD Ranging and Linearization: Automatic over range of 0 to 400 ohms, –328 to 1562°F (–200 to 850°C) Standards: Per IEC751 and DIN43760 Total Circuit Resistance (including leadwires): 430 ohms Sample Time: 0.25 seconds Resolution: 0.012 ohms or 0.
IB-23C650 INSTALLATION MILLIAMPERE INPUT - 2-WIRE TRANSMITTER Internal Transmitter Power Supply (22 mA Max. Loop Current) External Transmitter Power Supply (50 mA max. loop current) 2-Wire Transmitter 2-Wire Transmitter – – + G + G Shield to be left unconnected at this end. – + External Power Supply Figure 5.
IB-23C650 INSTALLATION MILLIAMPERE INPUT - NON 2-WIRE TRANSMITTER Non 2-Wire Transmitter Power – + G Shield to be left unconnected at this end. Note: Non 2-Wire Transmitter may also be ungrounded. Figure 6. Non 2-Wire Milliampere Input Connections Milliamp input specifications are: Input Range: 0 to 54 mA dc, Limited to below 70 mA Input Span: Operator settable from 1mA to 50 mA Input Impedance: 50 ohms nominal Resolution: 2.5 microamps maximum, 0.016% of a typical milliamp span Accuracy: ±0.
IB-23C650 INSTALLATION VOLT INPUT GROUNDED UNGROUNDED V Source V Source – + – G + Shield to be left unconnected at this end. Shield to be left unconnected at this end. Figure 7. Voltage Input Connections Volt input specifications are: Input Range: –10 mV to +6 V dc Input Impedance: 10M ohms minimum Resolution: 120 microvolts maximum, 0.003% of a typical 4 volt span Accuracy: 0.05% of input Temperature Effect: 0.01% per degree C Linearizations: Square law Sample Time: 0.
IB-23C650 INSTALLATION MILLIVOLT INPUT GROUNDED UNGROUNDED mV Source mV Source – + – G + G Shield to be left unconnected at this end. See Note See Note Shield to be left unconnected at this end. Note: Terminals 12 & 13 must be wired together for MV input. Figure 8. Millivolt Input Connections Millivolt input specifications are: Input Range: –10 to 120 mV dc Input Impedance: 10M ohms minimum Resolution: 3 microvolts maximum, 0.003% of a typical 100 mV span Accuracy: 0.
IB-23C650 INSTALLATION DIGITAL INPUT CONTROLLER +5V Digital Input 2 1.2K To Microprocessor 4.5K Same as #31 Digital Input 1 Note: External device sinks current. Figure 9. Digital Input Connections NOTE: Circuit common is disconnected from terminal #29 on instruments built for EU EMC compliance (electrical code 12). The common return for these instruments must be connected to one of the other common terminals, #2 or #9.
aaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaa aaaaaaaaa K2 15 14 13 12 11 +/L -/N aaaaaaaaaaaaaa aaaaaaa aaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaa 46 45 44 Close L N 8 7 6 5 4 Inst.
IB-23C650 INSTALLATION OUTPUT SIGNAL CONNECTIONS Output connections are shown as follows: • mA Outputs - see Figure 11 • Voltage Outputs - see Figure 12 • Relay Outputs - see Figure 13 The analog control output is always a milliamp signal as shown in Figure 11. When an application requires a voltage signal, a precision dropping resistor must be connected across the output terminals to generate the required voltage as shown in Figure 12. Output 2 is available when an option card is installed.
IB-23C650 INSTALLATION MILLIAMPERE OUTPUT + – Output Load Figure 11. Milliampere Output Connections Milliampere Output specifications are: Range: 0 to 54 mA maximum, non-isolated Resolution: 14 microamps, 0.09% of a typical 16 milliamp span Accuracy: ±0.2% of of setting Temperature Effect: 0.01% per degree C Load Resistance: at 22 mA: 1000 ohms maximum at 54 mA: 400 ohms maximum Open Circuit Voltage: 25.
IB-23C650 INSTALLATION VOLT OUTPUT (0 to 10 Volts dc) Precision Dropping Resistor Typical Value: 250 ohms ±0.01% (less than 10ppm) Maximum Value: 400 ohms + – Output Receiver Figure 12. Voltage Output Connections Note: 24 For 0 to 10 Vdc signal to receiver, controller output current range must be set at 0 to 40.0 mA dc when using 250 ohm resistor.
IB-23C650 INSTALLATION DIGITAL OUTPUT CONTROLLER Output Load NO External Power Supply NC + – Figure 13. Digital Output Connections Note: Connections shown are for Relay A. See Figure 2 for identification of terminals for relays B and C.
IB-23C650 INSTALLATION Blank Page 26
IB-23C650 SETUP SETUP CAUTION Be sure the process can be maintained in safe conditions before turning on controller power. The controller may not be properly configured to meet the specific requirements of the process until setup has been performed. GENERAL PREPARATIONS After installation is complete, begin setup by preparing the controller as follows: 1. At ac power source, connect power to controller. When power is turned on, the front panel character displays illuminate.
IB-23C650 SETUP SETUP FUNCTIONS For ease of use, the firmware has been divided into functional groups. The first group is for daily continuing operation, and the remaining groups are for setup and tuning. The method of moving from one group to another and the operational loop associated with each group are shown in Figure 14. Data entries are made by scrolling through the steps in each setup group, and making an appropriate response to each step.
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaaaaaa aaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaa
IB-23C650 SETUP Table 1. Base Configuration Step Step Description Top Display 1 Base Configuration Menu. UP moves to DISPLAYS **MENU**. DN moves to INPUTS **MENU**. SCRL advances to Step 2 (read only in auto). BASE CFG 2 Main Power Frequency. UP or DN selects 50 or 60 HERTZ. SCRL advances to Step 3. MAIN PWR 3 Process Input Type. UP or DN selects process input type. SCRL advances to: Step 3.1 if input type is THERMCPL, Step 3.
IB-23C650 SETUP Table 1. Middle Display Bottom Display 60 HERTZ Optimize input line frequency rejection by 50 HERTZ correctly identifying the power line frequency. TYPE MILLIAMP VOLT THERMCPL RTD MILLIVLT SLIDEWIR TC TYPE Entry Description None. **MENU** FREQ Base Configuration Process input types are: = 0 to 54 mA dc input = 0 to 6 V dc input = Thermocouple input = RTD input = –10 to 120 mV dc input = 0 to 100% slidewire (potentiometer) wiper position TYPE * Where * = J, K, E, R, S, T, B, or N.
IB-23C650 SETUP Table 1. Base Configuration Step Step Description Top Display 3.2.1 Process Calibration Correction. (cont’d) 4 Input 2 Enable. (Requires Option Board) UP selects YES or DN selects NO. SCRL advances to: Step 4.1 (Input 2 Type) from YES, or Step 5 (Output type) from NO. INPUT 2 4.1 Input 2 Type. UP or DN selects input 2 type. SCRL advances to: Step 4.1.1 if input type is THERMCPL, Step 4.1.2 if input type is RTD, or Step 5 (Output type) otherwise. INPUT 2 4.1.
IB-23C650 SETUP Table 1. Middle Display Bottom Display Entry Description 3. 4. 5. ENABLE NO = YES = TYPE MILLIAMP VOLT THERMCPL RTD MILLIVLT SLIDEWIR TC TYPE Base Configuration Be sure that any length of thermocouple extension wire or RTD lead wire used in the installation is connected for this procedure. If it is not possible to use the extension or lead wire, an equivalent resistor should be used.
IB-23C650 SETUP Table 1. Base Configuration Step Step Description Top Display 4.1.2.1 Input 2 Calibration Correction. UP or DN sets correction temperature. SCRL advances to Step 5. 5 Output Type. UP or DN selects output type. SCRL advances to Step 5.1. 5.1 Control Action. UP or DN selects control action. SCRL advances to: Step 5.2 if output type is CUR PROP, Step 5.3 if output type is HC/CR or HC/CC, Step 5.4 if output type is HC/RR, Step 5.
IB-23C650 SETUP Table 1. Middle Display xxx.x Bottom Display Base Configuration Entry Description xx.x Where xxx.x = input 2 temperature and xx.x = temperature correction (+15 to -15 degrees). See Step 3.2.1. for additional information. TYPE CUR PROP = POS PROP = HC/RR HC/CR HC/CC ON/OFF TIM PROP ACTION ACTION = = = = = DIRECT = increasing process input produces increasing controller calculated output. REVERSE = increasing process input produces decreasing controller calculated output.
IB-23C650 SETUP Table 1. Base Configuration Step Step Description 5.4 Cool Band Output Action. UP or DN selects cool band output action. SCRL advances to Step 6. 5.5 Valve Calibration. UP begins valve calibration at Step 5.5.1. SCRL advances to Step 6. Top Display COOL OUT VALVE In Steps 5.5.1 and 5.5.2, use of the UP and DN keys run the valve motor.
IB-23C650 SETUP Table 1. Middle Display ACTION Bottom Display Entry Description DIRECT = REVERSE = CALIB Base Configuration relay output is open or mA output #2 is MA.LOW at 0% displayed cool output and relay is closed or mA output #2 is MA.HIGH at 100% displayed cool output. relay output is closed at 0% displayed cool output and open at 100%, or mA output #2 is MA.HIGH at 0% and is MA.LOW at 100% displayed cool output.
IB-23C650 SETUP Table 1. Base Configuration Step Step Description Top Display 5.5.5 Repeat Calibration. UP selects YES or DN selects NO. SCRL advances to: Step 6 from NO, or Step 5.5.1 from YES. Note: Valve operation should be checked by returning to the operation Displays and controlling the valve in manual. 6 Hold Power-Up Message. UP selects YES or DN selects NO. SCRL advances to Step 7. HOLD PWR 7 Power-Up Mode. UP or DN selects power-up mode value.
IB-23C650 SETUP Table 1. Middle Display CALIBRAT Bottom Display Base Configuration Entry Description NO = YES = Don’t repeat the procedure. Repeat the calibration procedure. Note: If NO is selected, the calibration will remain bad. UP MSG NO = YES = MODE LAST = AUTO = MANUAL = ENABLE ENABLE ENABLE Don’t hold ‘POWER FAILED’ message at power-up. Hold ‘POWER FAILED’ message at power-up until scroll key is pressed. Power up in the same mode (Auto/Manual) as at power down. Power up in auto mode.
IB-23C650 SETUP Table 1. Base Configuration Step Step Description Top Display 11 Totalizer Enable. UP selects YES or DN selects NO. SCRL advances to Step 12. TOTALIZE 12 RS-485 Communications Enable. (Requires Option Board) UP selects YES or DN selects NO. SCRL advances to Step 13. RS-485 13 Tune Password. UP or DN sets tune password value (value must be other than zero to lock configuration menus in Step 19 ). SCRL advances to Step 14. TUNE 14 Configure Password.
IB-23C650 SETUP Table 1. Middle Display Bottom Display Entry Description ENABLE NO = ENABLE YES = NO = YES = PASSWORD Base Configuration Don’t allow TOTALIZE **MENU** setup or TOT variable select display. Allow totalizer setup and display. Don’t allow RS-485 **MENU** setup and display. Allow RS-485 **MENU** setup and display.
IB-23C650 SETUP Table 1. Base Configuration Step 16 Step Description Main Board Calibration Data. UP begins calibration. See Calibration Data section and Table 15. SCRL advances to Step 17. • • • 17 • • • Option Board Calibration Data. UP begins calibration. See Calibration Data section and Table 15. SCRL advances to Step 18. • • • • • • Top Display MAIN BRD • • • OPTN BRD • • • 18 Default Database. UP selects request to default the database (Are You Sure), Step 18.1.
IB-23C650 SETUP Table 1. Middle Display Bottom Display Base Configuration Entry Description Entry point for main board calibration. See Calibration Data section for details on these steps. CALIBRAT Caution: These are factory calibration values and should be altered only on the advice of authorized service personnel. Changing any or all of the 4 calibration values will cause the instrument to mark the main instrument calibration valid.
IB-23C650 SETUP Table 1. Base Configuration Step Step Description Top Display 18.2 Configuration has Changed. SCRL advances to Step 19. CONFIG 19 Lock configuration menus UP or DN selects YES or NO SCRL advances to Step 20. LOCK CFG 20 Software Revision Number. SCRL advances to Step 21. SOFTWARE 21 Display Revision Number. SCRL advances to Step 1.
IB-23C650 SETUP Table 1. Middle Display CHANGED MENUS Bottom Display Base Configuration Entry Description This is just a reminder that the instrument needs to be re-configured now that the database has been defaulted. YES = When both tune and configure passwords are other than zero, don’t allow operator to leave Displays Menu unless either tune or configure password is entered at CFT/TUNE PASSWORD. NO = Read access to all menus is available.
IB-23C650 SETUP Table 2. Input Setup Menu Step Step Description Top Display 1 Inputs Menu. UP moves to BASE CFG **MENU**. DN moves to DIG INPT **MENU**. SCRL to begin setup at Step 2. 2 Decimal Point. UP or DN positions decimal point. SCRL to advance to Step 3. 3 Process Input Setup. UP begins setup at: Step 3.1 if input type is RTD or thermocouple, or Step 3.2 if input type is mA, mV, V, or slidewire. SCRL to advance to: Step 4 if input 2 is enabled, or Step 5 otherwise. PROC INP 3.
IB-23C650 SETUP Table 2. Input Setup Menu Middle Display Bottom Display None. **MENU** POINT SETUP UNITS Entry Description 0. 0.0 0.00 0.000 = Display units = Display tenths = Display hundredths (electrical inputs only) = Display thousandths (electrical inputs only) Positioning of the decimal point in this menu sets the decimal location for ‘engineering unit’ entries in all menus. If values have already been set up, they may have to be changed depending on decimal positioning in this menu. None.
IB-23C650 SETUP Table 2. Input Setup Menu Step Step Description 3.4 Process Input Linearization Type. UP or DN selects type. SCRL to advance to Step 3.5 3.5 Process Input Engineering Units, High. UP or DN sets engineering units. SCRL to advance to: Step 3.7 if process input linearization type is SQR ROOT, or Step 3.6 otherwise.
IB-23C650 SETUP Table 2. Input Setup Menu Middle Display Bottom Display LIN TYPE NONE SQR ROOT UNITS HI Entry Description xxxx –3000 to 30000 for mV, V, mA, and slidewire (minimum span = 2) For thermocouple range limits, see thermocouple input specification on page 12. (minimum span for: types B, R, and S = 300°C, 540°F types E, J, K, N, and T = 100°C, 180°F) For RTD range limits, see RTD input specifications on page 13.
IB-23C650 SETUP Table 2. Input Setup Menu Step Step Description Top Display 3.6 Process Input Engineering Units, Low. UP or DN sets engineering units. SCRL to advance to Step 3.7. PROC ENG 3.7 Process Fault Output. UP or DN sets value. SCRL to advance to Step 3.8 if FIXED, Step 3.9 if LAST. PR FAULT 3.8 Fixed Fault Output UP or DN sets value. SCRL to advance to Step 3.9. 3.9 Process Fault Detection Level Percentage. UP or DN sets percent. SCRL to advance to Step 3.10.
IB-23C650 SETUP Table 2. Input Setup Menu Middle Display UNITS LO Bottom Display Entry Description xxxx –3000 to 30000 Note: Fixed at 0 when process input linearization type is SQR ROOT. OUTPUT LAST This is the output required during an input fault. FIXED When an input failure is detected, controller is put in manual and calculated output switches to the fault output value.
IB-23C650 SETUP Table 2. Input Setup Menu Step Step Description 3.10 Recovery Option. UP or DN selects option. SCRL to advance to: Step 4 if input 2 is enabled, or Step 5 otherwise. 4 Input 2 Setup. (Requires Option Board) UP begins setup at: Step 4.7 if output type is POS PROP, or Step 4.1 if input 2 type is thermocouple or RTD, or Step 4.2 if input type 2 is mA, mV, V, or slidewire SCRL to advance to Step 5. 4.1 Input 2 Temperature Units. UP or DN selects units. SCRL to advance to Step 4.5. 4.
IB-23C650 SETUP Table 2. Input Setup Menu Middle Display OPTION Bottom Display Entry Description MANUAL = Makes instrument return to the manual mode after the input failure is corrected. LAST = Makes instrument return to the mode it was in when the input failure occurred. If input 2 is being used as a remote bias or ratio value input, the value will be displayed as follows: xxx.xx. SETUP UNITS MA. HI or MV. HI or VOLTS HI or POSITION MA. LO or MV.
IB-23C650 SETUP Table 2. Input Setup Menu Step Step Description Top Display 4.5 Input 2 Engineering Units, High. UP or DN sets engineering units. SCRL to advance to: Step 4.7 if input 2 linearization type is SQR ROOT, or Step 4.6 otherwise. IN2 ENG 4.6 Input 2 Engineering Units, Low. UP or DN sets engineering units. SCRL to advance to Step 4.7.
IB-23C650 SETUP Table 2. Input Setup Menu Middle Display UNITS HI Bottom Display Entry Description xxxx –3000 to 30000 for mV, V, mA, and slidewire (minimum span = 2) For thermocouple range limits, see thermocouple input specification on page 12. (minimum span for: types B, R, and S = 300°C, 540°F types E, J, K, N, and T = 100°C, 180°F) For RTD range limits, see RTD input specifications on page 13. (minimum span = 20°C, 36°F) See description on Process Input Engineering Units High, Step 3.5.
IB-23C650 SETUP Table 2. Input Setup Menu Step Step Description Top Display 4.7 Input 2 Fault Action. UP or DN selects action. SCRL to advance to: Step 4.8 for LOCAL, or Step 4.9 otherwise. I2 FAULT 4.8 Input 2 Fault Value. UP or DN sets value. SCRL to advance to Step 4.9. I2 FAULT 4.9 Input 2 Fault Detection Level Percentage. UP or DN sets percent. SCRL to advance to Step 5.
IB-23C650 SETUP Table 2. Input Setup Menu Middle Display ACTION Bottom Display Entry Description Output type is NOT Position Proportioning: NONE = No action taken on input 2 failure. LOCAL = On input 2 failure, make the setpoint mode (or amrb ratio or bias source) local, and set it to the fault value below. Output type is Position Proportioning: NONE = No action taken on input 2 failure. HOLD POS = On input 2 failure, hold the current valve position.
IB-23C650 SETUP Table 2. Input Setup Menu Step 5 Step Description Engineering Units Label. UP to begin label entry. SCRL to advance to Step 6. Top Display ENG UNIT 1. When UP is pressed to begin entry, the first label character will begin to flash (if not a space). 2. Use UP or DN to select the desired character. (Selecting UP first begins at ‘A’; selecting DN first begins at ‘9’.) 3. SCRL to the next character and use UP or DN to set it. 4. Repeat through the last character. 5.
IB-23C650 SETUP Table 2. Input Setup Menu Middle Display LABEL Bottom Display Entry Description xxx Where x = any of the characters listed under Tag Name in the Tune Menu (Table 11). This is the label appended to the numeric process and set-point displays. When possible, a space will appear between the numeric value and the label. However, if 5 characters are required for the value, the space will be lost. If 6 are required, the third label character will be lost.
IB-23C650 SETUP Table 3. Digital Input Setup Menu Step Step Description Top Display 1 Digital Input Menu. UP moves to INPUTS **MENU**. DN moves to MA. OUTP **MENU**. SCRL to begin setup at Step 2. 2 Digital Input 1. UP begins digital input 1 configuration at Step 2.1. SCRL to advance to Step 3. 2.1 Digital Input 1 Function. UP or DN selects function. SCRL to advance to: Step 3 from NONE, or Step 2.1.1 from AUTO/MAN, or Step 2.1.10 from ALRM ACK or OUTP TRK, or Step 2.1.6 from TOTALIZE, or Step 2.1.
IB-23C650 SETUP Table 3. Digital Input Setup Menu Middle Display Bottom Display Entry Description **MENU** None. INPUT 1 None.
IB-23C650 SETUP Table 3. Digital Input Setup Menu Step Step Description Top Display 2.1.3 Manual to Auto Transition Allowed. UP or DN selects YES or NO. SCRL to advance to Step 2.1.10. MAN-AUTO 2.1.4 Ramp/Soak Digital Input 1 Function. UP or DN selects function. SCRL to advance to Step 2.1.5. RAMPSOAK 2.1.5 Ramp/Soak Command Lockout. UP or DN selects YES or NO. SCRL to advance to Step 2.1.10. R/H,RSET or RUN/HOLD or SKIP 2.1.6 Totalizer Digital Input 1 Function. UP or DN selects function.
IB-23C650 SETUP Table 3.
IB-23C650 SETUP Table 3. Digital Input Setup Menu Step Step Description Top Display 2.1.7 Totalizer Command Lockout. UP or DN selects YES or NO. SCRL to advance to Step 2.1.10. 2.1.8 Remote/Local Key Lockout. UP or DN selects YES or NO. SCRL to advance to: Step 2.1.9 if input 2 is present and available for for use as remote set-point, or Step 2.1.10 otherwise. R/L KEY 2.1.9 Local to Remote Transition Allowed. UP or DN selects YES or NO. SCRL to advance to Step 2.1.10. LOC-REM 2.1.
IB-23C650 SETUP Table 3. Digital Input Setup Menu Middle Display LOCKOUT Bottom Display Entry Description YES = Locks out the front panel totalizer commands indicated R/H,RSET = Run/hold, reset commands locked if run/stop selected RESET = Reset commands locked if run/reset selected RUN/HOLD = Run/hold commands locked if run/hold selected NO = Allows all front panel commands to the totalizer algorithm Also see note in 2.1.2 above.
IB-23C650 SETUP Table 3. Digital Input Setup Menu Step Step Description Top Display 3.1 Digital Input 2 Function. UP or DN selects function. SCRL to advance to: Step 4 from NONE, or Step 3.1.1 from AUTO/MAN, or Step 3.1.10 from ALRM ACK or OUTP TRK, or Step 3.1.6 from TOTALIZE, or Step 3.1.4 from RAMPSOAK, or Step 3.1.8 from SETP SEL. 3.1.1 Digital Auto to Manual Fixed Output Enable. UP or DN selects YES or NO. SCRL to advance to: Step 3.1.2 from NO, or Step 3.1.1.1 from YES. DIG A-M 3.1.1.
IB-23C650 SETUP Table 3.
IB-23C650 SETUP Table 3. Digital Input Setup Menu Step Step Description Top Display 3.1.5 Ramp/Soak Digital Input 2 Command Lockout. UP or DN selects YES or NO. SCRL to advance to Step 3.1.10. R/H,RSET or RUN/HOLD or SKIP 3.1.6 Totalizer Digital Input 2 Function. UP or DN selects function. SCRL to advance to Step 3.1.7. TOTALIZE 3.1.7 Totalizer Digital Input 2 Command Lockout. UP or DN selects YES or NO. SCRL to advance to Step 3.1.10. R/H,RSET or RESET or RUN/HOLD 3.1.
IB-23C650 SETUP Table 3. Digital Input Setup Menu Middle Display LOCKOUT Bottom Display Entry Description YES = Locks out the front panel ramp/soak commands indicated R/H,RSET = Run/hold, reset commands locked if run/stop selected RUN/HOLD = Run/hold commands locked if run/hold selected SKIP = Skip commands locked if run/skip selected NO = Allows all front panel commands to the ramp/soak algorithm Also see note in 2.1.2 above.
IB-23C650 SETUP Table 3. Digital Input Setup Menu Step Step Description Top Display 3.1.9 Local to Remote Transition Allowed. UP or DN selects YES or NO. SCRL to advance to Step 3.1.10. 3.1.10 Digital Input 2 Action. UP or DN selects REVERSE or DIRECT. SCRL to advance to: Step 4 if either digital input function is SETP SEL or both functions are SETP SEL and input 2 is enabled, or Step 1 otherwise. DIG IN 2 4 Digital Set-Point Selection List. UP or DN selects set-point. SCRL to return to Step 1.
IB-23C650 SETUP Table 3. Digital Input Setup Menu Middle Display ALLOWED Bottom Display Entry Description NO = Digital input transition selects any set-point for which it is configured, except remote YES = Digital input transition selects any set-point for which it is configured When both digital inputs are used for set-point selection, this choice applies to both. They are not independent.
IB-23C650 SETUP Table 4. Milliamp Output Setup Menu Step Step Description Top Display 1 Milliamp Output Menu. UP moves to DIG INPT **MENU**. DN moves to RELAYS **MENU**. SCRL to begin setup at Step 2. 2 Output Current at 100%. UP or DN sets value. SCRL to advance to Step 3. OUTPUT 3 Output Current at 0%. UP or DN sets value. SCRL to advance to: Step 4 if output type is HEAT/COOL, or Step 6 otherwise. OUTPUT 4 Heat Output High Limit. UP or DN sets value. SCRL to advance to Step 5.
IB-23C650 SETUP Table 4. Milliamp Output Setup Menu Middle Display **MENU** MA. HIGH Bottom Display Entry Description None. xx.x 01.0 to 54.0 mA dc The current produced by 100% output from the control algorithm. (i. e. ,100% = 20 mA dc) MA. LOW xx.x 0 to (mA high – 1) mA dc The current produced by 0% output from the control algorithm. Example: 0% = 4 mA dc HI LIMIT xx.x 0.1 to 110.0% of heat output span The maximum value for heat output. HI LIMIT xx.x 0.1 to 110.
IB-23C650 SETUP Table 4. Milliamp Output Setup Menu Step Step Description Top Display 9.1 Fixed Output Value. UP or DN sets fixed initial power up output value. SCRL to advance to: Step 10 if output 2 is installed, and output type is NOT HC/CC, or Step 11 if output 2 is installedand output type is HC/CC, or Step 1 otherwise (output 2 is NOT installed). FIXD PWR 10 Retransmission Variable. UP or DN selects variable.
IB-23C650 SETUP Table 4. Milliamp Output Setup Menu Middle Display UP OUTPT Bottom Display Entry Description xx.x –8.0 to 110.0. Limited by output high and low limits above.
IB-23C650 SETUP Table 5. Output Relays Setup Menu Step Step Description Top Display 1 Output Relays Menu. UP moves to MA. OUTP **MENU**. DN moves to RAT BIAS **MENU** if A/M ratio bias is enabled, or to SETPTS **MENU**. SCRL to begin setup at Step 2. 2 Relay A Setup. UP begins setup at Step 2.1. SCRL to advance to Step 3. RELAY A 2.1 Relay A Function. UP or DN selects function. SCRL to advance to: Step 2.1.1 if function is ALARMS, or Step 3 otherwise. RELAY A 2.1.1 Relay A Alarm Trip Action.
IB-23C650 SETUP Table 5. Output Relays Setup Menu Middle Display Bottom Display Entry Description **MENU** None. SETUP None. FUNCTION TRIP ACT NONE ALARMS TOTALIZE RAMPSOAK REM/LOC AUTO/MAN MANUAL CMP ONLY 1 2 3 4 • • • Note: If relay is used for control (per output type in BASE CGF), ‘CONTROL’ will appear for one second and displays will advance to Relay B Setup. = Relay action controlled from front panel = Relay action controlled by computer 15 possible combinations of the four display alarms.
IB-23C650 SETUP Table 5. Output Relays Setup Menu Step Step Description Top Display 3.1.1 Relay B Alarm Trip Action. UP or DN selects alarm combination. SCRL to advance to Step 4. RELAY B 4 Relay C Setup. UP begins setup at Step 4.1. SCRL to return to Step 1. RELAY C 4.1 Relay C Function. UP or DN selects function. SCRL to advance to: Step 4.1.1 if function is ALARMS, or Step 1 otherwise. RELAY C 4.1.1 Relay C Alarm Trip Action. UP or DN selects alarm combination. SCRL to return to Step 1.
IB-23C650 SETUP Table 5. Output Relays Setup Menu Middle Display TRIP ACT Bottom Display Entry Description 1 15 possible combinations of the four display 2 alarms. Any of the alarms in the chosen set 3 will cause the relay to trip. 4 • • • Valid combinations are: 1, 2, 3, 4, 12, 13, 14, 23, 24, 34, 123, 124, 134, 234, and 1234. 1234 None.
IB-23C650 SETUP Table 6. RS-485 Setup Menu Step 1 Step Description RS-485 Menu. (requires option board) UP moves to RELAYS **MENU**. DN moves to RAT BIAS **MENU** if A/M ratio bias is enabled, or to SETPTS **MENU** otherwise. SCRL advances to Step 2. 2 Go to Table 1, RS-485 Setup Menu, in the MODBUS Communications Supplement IB-23C650M. All information pertaining to RS-485 setup and Modbus communications is provided in the supplement.
IB-23C650 SETUP Table 6. RS-485 Setup Menu Middle Display **MENU** Bottom Display Entry Description None.
IB-23C650 SETUP Table 7. Auto/Manual Ratio Bias Setup Menu Step Step Description Top Display 1 A/M Ratio Bias Menu. UP moves to RELAYS **MENU**. DN moves to TOTALIZE **MENU** if integrator/totalizer is enabled, or to ALARMS **MENU** otherwise. SCRL to begin setup at Step 2. RAT BIAS 2 Type of Ratio Bias Station. UP or DN selects type. SCRL to advance to: Step 3 from RATIO, or Step 4 from BIAS, or Step 7 from RAT BIAS. RAT BIAS 3 Source for Ratio Only Type. UP or DN selects source.
IB-23C650 SETUP Table 7. Auto/Manual Ratio Bias Setup Menu Middle Display **MENU** TYPE Bottom Display Entry Description None. RATIO = Ratio only station BIAS = Bias only station RAT BIAS = Ratio and bias station SOURCE LOCAL REMOTE Remote source requires option board. SOURCE LOCAL REMOTE Remote source requires option board. BALANCE STANDARD = Outputs may bump when switching from manual to auto AUTO = Bumpless transfer when switching from manual to auto. Not valid if source is remote.
IB-23C650 SETUP Table 7. Auto/Manual Ratio Bias Setup Menu Step Step Description 7 Ratio Source for Ratio and Bias Type. UP or DN selects source. SCRL to advance to: Step 8 from LOCAL, or Step 9 from REMOTE. 8 Bias Source for Ratio and Bias Type. UP or DN selects source. SCRL to advance to Step 9. 9 Ratio Balance for Ratio and Bias Type. UP or DN selects type. SCRL to advance to: Step 10 from STANDARD, or Step 1 from AUTO. 10 Bias Balance for Ratio and Bias Type. UP or DN selects type.
IB-23C650 SETUP Table 7. Auto/Manual Ratio Bias Setup Menu Middle Display SOURCE Bottom Display Entry Description LOCAL Initial value can be set in "TUNE MENU", Table 12, and Ratio can be changed in operator's display. REMOTE Initial value can be viewed in "TUNE MENU", Table 12, and Ratio can be viewed in operator's display. Note: Only one remote source is allowed. If ratio is REMOTE, bias must be LOCAL. SOURCE LOCAL Same as Step 7. REMOTE Same as Step 7. Note: Only one remote source is allowed.
IB-23C650 SETUP Table 8. Set-Point Setup Menu Step Step Description Top Display 1 Set-Point Menu. UP moves to RELAYS **MENU**. DN moves to RAMPSOAK **MENU** if ramp/soak is enabled, or to TOTALIZE **MENU** if integrator/totalizer is enabled, or to ALARMS **MENU** otherwise. SCRL to begin setup at Step 2. 2 Local Set-Point. UP begins set-point configuration at Step 2.1. SCRL to advance to Step 3. LOC SETP 2.1 Local Set-Point Fixed. UP or DN selects YES or NO. SCRL to advance to Step 2.2.
IB-23C650 SETUP Table 8. Set-Point Setup Menu Middle Display **MENU** Bottom Display Entry Description None. None. FIXED NO = Allows changes in Displays menu YES = This local set-point can be changed at the Initial Value entry only, Step 2.4. HI LIMIT xxxx Low limit to 30000 LO LIMIT xxxx –3000 to high limit INIT VAL xxxx Low limit to high limit The current value of this local setpoint. None.
IB-23C650 SETUP Table 8. Set-Point Setup Menu Step Step Description Top Display 3.4 Local Set-Point 2 Low Limit. UP or DN sets value. SCRL to advance to Step 3.5. SETPT 2 3.5 Local Set-Point 2 Initial Value. UP or DN sets value. SCRL to advance to Step 4. SETPT 2 4 Local Set-Point 3. UP begins set-point 3 configuration at Step 4.1. SCRL to advance to Step 5. SETPT 3 4.1 Local Set-Point 3 Enable. UP or DN selects YES or NO. SCRL to advance to Step 4.2. SETPT 3 4.2 Local Set-Point 3 Fixed.
IB-23C650 SETUP Table 8. Set-Point Setup Menu Middle Display Bottom Display Entry Description LO LIMIT xxxx –3000 to high limit INIT VAL xxxx Low limit to high limit The current value of this local setpoint. None. ENABLE NO = This set-point cannot be selected YES = Set-point selectable from front panel and/or digital input(s) FIXED NO = Allows changes in Displays menu YES = This local set-point can be changed at the Initial Value entry only, Step 4.5.
IB-23C650 SETUP Table 8. Set-Point Setup Menu Step Step Description Top Display 5.2 Local Set-Point 4 Fixed. UP or DN selects YES or NO. SCRL to advance to Step 5.3. SETPT 4 5.3 Local Set-Point 4 High Limit. UP or DN sets value. SCRL to advance to Step 5.4. SETPT 4 5.4 Local Set-Point 4 Low Limit. UP or DN sets value. SCRL to advance to Step 5.5. SETPT 4 5.5 Local Set-Point 4 Initial Value. UP or DN sets value. SCRL to advance to Step 6. SETPT 4 6 Power-up Set-Point Source.
IB-23C650 SETUP Table 8. Set-Point Setup Menu Middle Display FIXED Bottom Display Entry Description NO = Allows changes in Displays menu YES = This local set-point can be changed at the Initial Value entry only, Step 5.5. HI LIMIT xxxx Low limit to 30000 LO LIMIT xxxx –3000 to high limit INIT VAL xxxx Low limit to high limit The current value of this local setpoint.
IB-23C650 SETUP Table 8. Set-Point Setup Menu Step Step Description Top Display 6.1 Input 2 is Missing. This warning will time out in 1 second and return to step 6 with a choice of LOC SETPT. 6.2 Fixed Set-Point Value. UP or DN sets value. SCRL to advance to Step 7. FIXD PWR 7 Set-Point Tracking. UP or DN sets value. SCRL to return to Step 1.
IB-23C650 SETUP Table 8. Set-Point Setup Menu Middle Display MISSING UP SETPT TRACKING Bottom Display Entry Description REM SETP None. xxxx –3000 to 30000, within local set-point limits NO = Set-point tracking not activated YES = Activate set-point tracking. Tracks process input when controller in manual. No setpoint/process deviation when switching from manual to auto. Note: Local set-points 1-4 will not track if configured to be ‘fixed’. Remote set-point cannot track.
IB-23C650 SETUP Table 9. Ramp/Soak Profile Setup Menu Step Step Description Top Display 1 Ramp/Soak Menu. UP moves to SETPTS **MENU**. DN moves to TOTALIZE **MENU** if integrator/totalizer is enabled, or to ALARMS **MENU** otherwise. SCRL to begin setup at Step 2. RAMPSOAK 2 Ramp/Soak Repeat. UP selects YES or DN selects NO. SCRL to advance to Step 3. RAMPSOAK 3 Soak Hysteresis. UP or DN sets value. SCRL to advance to Step 4. SOAK 4 Ramp Hysteresis. UP or DN sets value.
IB-23C650 SETUP Table 9. Ramp/Soak Profile Setup Menu Middle Display **MENU** REPEAT HYST Bottom Display Entry Description None. NO = Stops ramp/soak cycle after last segment YES = Repeats ramp/soak cycle after last segment xxxx 0 to 30000 Value of hysteresis band for guaranteed soaks. HYST xxxx 0 to 30000 Value of hysteresis band for guaranteed ramps.
IB-23C650 SETUP Table 9. Ramp/Soak Profile Setup Menu Step Step Description Top Display 7.1.1 Segment 1 Start Value. UP or DN sets value. SCRL to advance to Step 7.1.2. SEG 1 7.1.2 Segment 1 End Value. UP or DN sets value. SCRL to advance to: Step 7.1.3 if start and end values are the same, or Step 7.1.4 if start and end values are different. SEG 1 7.1.3 Segment 1 Soak Time. UP or DN sets time. SCRL to advance to: Step 7.1.5 if relay A is set for ramp/soak (in Relays), or Step 7.1.
IB-23C650 SETUP Table 9. Ramp/Soak Profile Setup Menu Middle Display START SP Bottom Display Entry Description xxxx Between ‘Local Set-point Low Limit’ and ‘Local Set-point High Limit’ Note: If a decimal point change is made in the INPUTS **MENU** after configuring the ramp / soak profile, the profile will require reconfiguration. END SP xxxx Between ‘Local Set-point Low Limit’ and ‘Local Set-point High Limit’ SOAK TIM xxx.x 0 to 3000.0 (hours or minutes, per Time Units, Step 6) RMP RATE xxx.
IB-23C650 SETUP Table 9. Ramp/Soak Profile Setup Menu Step Step Description Top Display 7.1.5 Segment 1 Relay A State. UP or DN selects ON or OFF. SCRL to advance to: Step 7.1.6 if relay B is set for ramp/soak, or Step 7.1.7 if relay C is set for ramp/soak, or Step 7.1.8 otherwise. SEG 1 7.1.6 Segment 1 Relay B State. UP or DN selects ON or OFF. SCRL to advance to: Step 7.1.7 if relay C is set for ramp/soak, or Step 7.1.8 otherwise. SEG 1 7.1.7 Segment 1 Relay C State. UP or DN selects ON or OFF.
IB-23C650 SETUP Table 9. Ramp/Soak Profile Setup Menu Middle Display Bottom Display Entry Description RELAY A ON State of the relay during segment. OFF RELAY B ON State of the relay during segment. OFF RELAY C ON State of the relay during segment. OFF NO = YES = Time is counted only if process variable is GUARANTD within hysteresis deadband set above (Step 3 or 4) None.
IB-23C650 SETUP Table 9. Ramp/Soak Profile Setup Menu Step Step Description Top Display 7.10.2 Segment 10 End Value. UP or DN sets value. SCRL to advance to: Step 7.10.3 if start and end values are the same, or Step 7.10.4 if start and end values are different. SEG 10 7.10.3 Segment 10 Soak Time. UP or DN sets time. SCRL to advance to: Step 7.10.5 if relay A is set for ramp/soak (in Relays), or Step 7.10.6 if relay B is set for ramp/soak, or Step 7.10.7 if relay C is set for ramp/soak, or Step 7.10.
IB-23C650 SETUP Table 9. Ramp/Soak Profile Setup Menu Middle Display END SP Bottom Display Entry Description xxxx Between ‘Local Set-point Low Limit’ and ‘Local Set-point High Limit’ SOAK TIM xxx.x 0 to 3000.0 (hours or minutes, per Time Units, Step 6) RMP RATE xxx.x Change per unit time (hours or minutes) in engineering units See Note in Step 7.1.4. RELAY A ON State of the relay during segment. OFF RELAY B ON State of the relay during segment.
IB-23C650 SETUP Table 9. Ramp/Soak Profile Setup Menu Step Step Description Top Display 7.10.7 Segment 10 Relay C State. UP or DN selects ON or OFF. SCRL to advance to Step 7.10.8. SEG 10 7.10.8 Guaranteed Ramp or Soak. UP or DN selects YES or NO. SCRL to return to Step 1.
IB-23C650 SETUP Table 9. Ramp/Soak Profile Setup Menu Middle Display RELAY C GUARANTD Bottom Display Entry Description ON State of the relay during segment.
IB-23C650 SETUP Table 10. Integrator/Totalizer Menu Step Step Description Top Display 1 Totalizer Menu. UP moves to RAMPSOAK **MENU** if ramp/soak is enabled, or to RAT BIAS **MENU** if ratio bias is enabled, or to SETPTS **MENU** otherwise. DN moves to ALARMS **MENU**. SCRL to begin setup at Step 2. 2 Wrap at Predetermined Count. UP or DN selects YES or NO. SCRL to advance to Step 3. 3 Set Threshold Value. UP or DN sets value. SCRL to advance to Step 4. INPUT 4 Totalizer Status.
IB-23C650 SETUP Table 10. Integrator/Totalizer Menu Middle Display Bottom Display None. **MENU** PRED CNT Entry Description NO = Counts until turned off or until maximum count (9,999,999) is reached. At maximum count, totalizer will hold until operator resets. = Counts until predetermined count is reached, then resets to preset value and YES starts counting again. THRSHOLD xxxx 0 to ‘Engineering Units High Value’ in engineering units for electrical inputs.
IB-23C650 SETUP Table 10. Integrator/Totalizer Menu Step Step Description Top Display 7 Totalizer Scale Decimal Point. UP or DN sets decimal point. SCRL to advance to Step 8. SCALE 8 Totalizer Scale Factor. UP or DN sets scale factor. SCRL to advance to Step 9. SCALE 9 Totalizer Preset Value. UP begins entry of preset value at most significant digit (It will flash). Then UP or DN sets digit, SCRL to next digit. Repeat for all digits. SCRL to advance to Step 10. 10 Totalizer Predetermined Count.
IB-23C650 SETUP Table 10. Integrator/Totalizer Menu Middle Display Bottom Display DEC PT FACTOR VALUE 0. 0.0 0.00 0.000 xxxx Entry Description Sets decimal location for scale factor in Step 8. = 1 to 30000 = .1 to 3000.0 = .01 to 300.00 = .001 to 30.000 0.001 to 30000 (Set decimal point in Step 7). See also flow rate time base (Step 6), and the Totalizer Operation section. xxxxxxx .
IB-23C650 SETUP Table 11. Alarm Settings Menu Step Step Description Top Display 1 Alarms Menu. UP moves to TOTALIZE **MENU** if totalizer is enabled, or to RAMPSOAK **MENU** if ramp/soak is enabled, or to RAT BIAS **MENU** if ratio bias is enabled, or to SETPTS **MENU** otherwise. DN moves to TUNE **MENU**. SCRL to begin setup at Step 2. 2 Beep on Occurrence Of. UP or DN selects type. SCRL to advance to Step 3. 3 Alarm Acknowledge Required. UP selects YES or DN selects NO.
IB-23C650 SETUP Table 11. Alarm Settings Menu Middle Display Bottom Display None.
IB-23C650 SETUP Table 11. Alarm Settings Menu Step Step Description Top Display 5 Priority 1 Relay Action. UP or DN selects action. SCRL to advance to: Step 6 if acknowledge is required on priority 2 process alarms, or Step 7 otherwise. P1 RELAY 6 Priority 2 Relay Action. UP or DN selects action. SCRL to advance to Step 7. P2 RELAY 7 Alarm 1 Setup. UP begins setup at Step 7.1. SCRL to advance to Step 8. ALARM 1 7.1 Alarm 1 Type. UP or DN selects type.
IB-23C650 SETUP Table 11.
IB-23C650 SETUP Table 11. Alarm Settings Menu Step Step Description Top Display 7.1.3 Alarm 1 Priority. UP or DN selects 1 or 2. SCRL to advance to Step 7.1.4. ALARM 1 7.1.4 Alarm 1 Hysteresis. UP or DN sets value. SCRL to advance to Step 8. ALARM 1 8 Alarm 2 Setup. UP begins setup at Step 8.1. SCRL to advance to Step 9. ALARM 2 8.1 Alarm 2 Type. UP or DN selects type. SCRL to advance to: Step 8 if type is NONE, or Step 8.1.1 if output type is heat/cool, or Step 8.1.2 otherwise. ALARM 2 8.1.
IB-23C650 SETUP Table 11. Alarm Settings Menu Middle Display Bottom Display Entry Description 2 = Lower priority 1 = Higher priority PRIORITY xxxx 0 to 1000, in engineering units HYST Hysteresis is an adjustable deadband at alarm trip-point. Alarm output turns off only after process value has moved into safe region by an amount equal to hysteresis. Applies to both process and deviation alarms. None.
IB-23C650 SETUP Table 12. Tune Menu Step Step Description Top Display 1 Tune Menu. UP moves to ALARMS **MENU**. DN moves to DISPLAYS **MENU**. SCRL to begin setup at Step 2. 2 Tag Name. UP begins tag entry. First tag character will flash. Then UP or DN sets character (Selecting UP first begins selections at ’A’; selecting DN first begins selection at ’9‘.) SCRL to next character. Repeat for all characters, SCRL to beginning.
IB-23C650 SETUP Table 12. Tune Menu Middle Display **MENU** NAME Bottom Display Entry Description None.
IB-23C650 SETUP Table 12. Tune Menu Step Step Description Top Display 7 Reset Enable. UP selects YES or DN selects NO. SCRL to advance to: Step 7.1 from YES if output type is HEAT/COOL, or Step 7.3 from YES if output type is any other, or Step 7.4 from NO. RESET 7.1 Reset Value Heat. UP or DN sets value. SCRL to advance to Step 7.2. RESET 7.2 Reset Value Cool. UP or DN sets value. SCRL to advance to Step 8. RESET 7.3 Reset Value. UP or DN sets value. SCRL to advance to Step 8. 7.
IB-23C650 SETUP Table 12. Tune Menu Middle Display ENABLE Bottom Display Entry Description YES = Enable integral response NO = Don’t enable integral response HEAT xxx.xx 0.01 to 120.00 repeats/minute COOL xxx.xx 0.01 to 120.00 repeats/minute RESET xxx.xx 0.01 to 120.00 repeats/minute MAN RSET NO = Must calculate manual reset value when switching from manual to auto: MR = Output – (Gain x Error) YES = Fixes manual reset at value in Step 7.4.1 RESET xxx.x 0.0 to 100.
IB-23C650 SETUP Table 12. Tune Menu Step Step Description Top Display 8 Preact Value. (cont’d) Step 13 if A/M ratio bias is not enabled and output type is POS PROP, or Step 15 if A/M ratio bias is not enabled and output type is TIM PROP or ON/OFF, or Step 16 if A/M ratio bias is not enabled and output type is HEAT/COOL, or Step 1 otherwise. 9 Remote Set-Point Ratio. (requires option board) UP or DN sets value. SCRL to advance to Step 10. REM SETP 10 Remote Set-Point Bias.
IB-23C650 SETUP Table 12. Tune Menu Middle Display RATIO Bottom Display Entry Description xxx.xx -300.00 to 300.00 Ratio value applied to remote set-point. If ratio function is not required, set value to 1. BIAS xxxx –3000 to 30000 (decimal point per Inputs) Bias value added to or subtracted from remote set-point. If bias function is not required, set value to 0. RATIO xx.xx 0.01 to 300.00 Initial value of local ratio applied to process input.
IB-23C650 SETUP Table 12. Tune Menu Step Step Description Top Display 13 Position Proportioning Deadband. UP or DN sets value. SCRL to advance to Step 14. POS PROP 14 Position Proportioning Preact. UP or DN sets value. SCRL to return to Step 1. POS PROP 15 Time Proportioning Cycle Time. UP or DN sets value. SCRL to return to Step 1. 16 Heat/Cool Output Crossover. UP or DN sets value. SCRL to advance to Step 17. CROSSOVR 17 Crossover Transition Band Width. UP or DN sets value.
IB-23C650 SETUP Table 12. Tune Menu Middle Display DEADBAND Bottom Display Entry Description xx.x 0.0 to 50.0% Percent difference in calculated output and valve position (input 2) required to actuate open relay on increasing output or closed relay on decreasing output. PREACT xx.x 0.0 to 50.0% This is the percent overshoot that would occur is preact were set to zero. See the Position Proportioning Control section for information on determining values for position proportioning deadband and preact.
IB-23C650 SETUP Blank Page 122
IB-23C650 BASIC OPERATION BASIC OPERATION INTRODUCTION Operator activities related to ongoing operations are performed in the DISPLAYS MENU. Some operator activities may also be associated with tuning (TUNE MENU), alarm settings (ALARMS MENU), and set-point manipulation (SETPTS MENU) especially during startup. Other activities in menus labeled RELAYS, MA OUTP, DIG INPT, INPUTS, and BASE CFG are for various setup, configuring, and calibration procedures.
IB-23C650 INTRODUCTION Alarm Light Alarm Scroll Key Loop Tag Display Tag Key Process Variable Display Manual Key Auto Key Status Displays Remote/Local Key Scroll Key Up Key Down Key Lower Engineering Display Process Variable Bar Graph Set-Point Output Variable Bar graph Bar Graph Figure 15.
IB-23C650 BASIC OPERATION CONTROL KEYS The operator control keys are: Alarm: Press to stop flashing and beeping alarm indication. Press repeatedly to view list of existing conditions (unacknowledged diagnostics, priority 1 then 2, then acknowledged alarms). Bottom display indicates ACKED or UNACKED alarms. Use UP key to acknowledge. All other keys are inactive until you return to the normal display. Tag: Press to advance from the top of any menu to the top of the DISPLAYS MENU.
IB-23C650 BASIC OPERATION Up (UP): Used in the configuration mode to answer prompts by toggling between YES and NO or other option, and to increment values where applicable. Also used in the DISPLAYS MENU to ramp up the set-point or output variable, whichever was selected or to acknowledge alarms. Down (DN): Used in the configuration mode to answer prompts by toggling between YES and NO or other options, and to decrement values where applicable.
IB-23C650 BASIC OPERATION Bottom: Lower Engineering Display Indicates engineering unit values for output,set-point, ratio and bias as indicated by the third status display. An engineering units label can also be displayed. Assumes other roles during routines such as ramp/soak, totalizer, alarms, etc. STATUS DISPLAYS There are three 3-character status displays located to the right of the bar graphs. TOP DISPLAY Manual: Instrument is in manual control and the output may be adjusted manually.
IB-23C650 BASIC OPERATION MIDDLE DISPLAY Remote: Set-point is derived from a remote location and is brought into the instrument through the remote set-point input on the option card. Local: Set-point is derived at the instrument and may be fixed in the SETPTS MENU or adjusted in the DISPLAYS MENU. Local 2: Local set-point number 2 is derived at the instrument and may be fixed in the SETPTS MENU or adjusted in the DISPLAYS MENU.
IB-23C650 BASIC OPERATION Totalize: The totalized count is being displayed in the lower engineering display. See operation of Totalizer. Autotune: Autotune has been enabled in the BASE CNFG MENU. At this display’s menu prompt, pressing the UP key will initiate the Autotune routine. Ramp/ Soak: Ramp/soak has been enabled in the BASE CFG MENU. Pressing the UP key provides ramp/soak status such as run/hold, time left per segment, active segment, cycle, reset and skip. See operation of Ramp/Soak.
IB-23C650 BASIC OPERATION BAR GRAPHS Three 50-segment bar graphs provide visual indication of process, set-point and either output or deviation. Process Variable Set-Point Variable Output Process Variable Set-Point Variable Deviation (as set up in the Inputs Menu) Deviation bar shows a minimum of two highlighted lines (both highlighted when deviation is zero). Deviation is shown above or below these lines.
IB-23C650 BASIC OPERATION RESTART Power up mode, set-point and output conditions can be defined so that at an instrument power up condition the controller will assume these positions and values. Power up data is stored in non-volatile memory and is read into the operating memory at instrument power up. Controller mode at power up is defined in the BASE CFG MENU and may be set at auto, manual, or last, where last causes the controller to power up in the same mode as it was when power was lost.
IB-23C650 BASIC OPERATION OPERATION IN AUTOMATIC MODE This section describes operations for local set-points, remote or multiple setpoints, and A/M ratio bias while the controller is in the automatic mode. For automatic ramp/soak and totalizer operations, refer to those operations sections. Note: If tune or configure passwords have been employed, the passwords will be required to change any values. Automatic Operation with Local Set-Point [AUT] indicates that the controller is in automatic mode.
IB-23C650 BASIC OPERATION Automatic Operation with Remote or Multiple Set-Points The controller may be in either auto or manual as selected in the power up mode section of the BASE CFG MENU. If the controller is in automatic, the front face will resemble the example below. Note: Remote set-point requires the option board be installed. [AUT] indicates that the controller is in automatic. The set-point may be [LOC], [LO2], [LO3], [LO4] or [REM], depending on which set-points were enabled in the SETPTS MENU.
IB-23C650 BASIC OPERATION To perform a set-point bumpless transfer, complete the following steps: 1) With set-point displayed, press the R/L key to advance the controller through the menu-enabled set-points. [BAL] appears in the third status display. 2) Press the UP or DN key until the lower engineering display reaches “0.“ This adjusts the active set-point to the value of the new set-point, in this case the value of LO2. 3) Press the scroll key to enable the new set-point.
IB-23C650 BASIC OPERATION Automatic Operation with A/M Ratio Bias If ratio, bias or ratio/bias was enabled in the RAT BIAS MENU, the instrument display will resemble the examples below. [AUT] indicates that the station is in automatic mode. Ratio and/or bias source is local or remote as selected in RAT BIAS MENU (remote requires installation of an option board). Remote/Local switch is disabled [RAT] indicates that the ratio value is displayed in the lower engineering display.
IB-23C650 BASIC OPERATION AUTO/MANUAL TRANSFER Transfer from auto to manual is accomplished by pressing the manual key. Either of the digital inputs may be used to select manual if configured to do so. When the controller is in manual mode the upper status display will show [MAN]. Transfer from manual to automatic is made by pressing the auto key. Either of the two digital inputs may be used to select auto if configured to do so. When in automatic, the upper status display will show [AUT].
IB-23C650 BASIC OPERATION Auto/Manual Transfer for On-Off Control If the controller is set up for on-off control, the bumpless transfer feature does not apply when switching from automatic to manual. When switched to manual, the on-off controller output is always initialized at 0%. The transfer is bumpless only if the automatic output happens to be at 0% when switched. Operation in manual is the same as for a time proportioning controller.
IB-23C650 BASIC OPERATION OPERATION IN MANUAL This section describes operations for local set-points, remote or multiple setpoints, and A/M ratio bias while the controller is in the manual mode. For manual ramp/soak and totalizer operations, refer to those operations sections. Manual Operation with Local Set-Points The instrument is initially in manual mode with set-point displayed in the lower engineering display, as indicated by [SPT] in the third status display.
IB-23C650 BASIC OPERATION When the controller is set up for on/off control, the manual output is a time proportioning signal. This gives the output infinite adjustability between 0 and 100% rather than limited to the two-state 0 and 100% values of the automatic mode. In manual the output can be adjusted to any value needed to maintain the process at the set-point.
IB-23C650 BASIC OPERATION Press the scroll key to display the output in percent in the lower engineering display. [OUT] appears in the third status display. DN/UP status display indicates the UP and DN keys are active and can be used to adjust the output value in manual. Press the scroll key again to return the set-point in the lower engineering display. Remote or multiple set-point transfer is made by pressing the R/L key (press and release) [BAL] appears in the third status display.
IB-23C650 BASIC OPERATION Use the following steps to prepare to switch from a local to a remote set-point: 1) Press the R/L key until [REM] is displayed in the middle status display. 2) [BAL] appears in the third status display with the difference between the remote set-point and the current setpoint displayed in the lower engineering display. 3) Press the UP or DN key until the lower engineering display reaches “0.“ 4) Press scroll to enact the remote source as the new set-point source.
IB-23C650 BASIC OPERATION Manual Operation with A/M Ratio Bias If ratio, bias, or ratio/bias was enabled in the RAT BIAS MENU, the instrument display will resemble the examples below: [MAN] indicates that the station is in manual mode. Ratio and/or bias source is local or remote as selected in RAT BIAS MENU (remote requires installation of an option board). [RAT] indicates that the ratio value is displayed in the lower engineering display.
IB-23C650 BASIC OPERATION OPERATION USING DIGITAL INPUTS Digital inputs 1 and 2 can be used to control auto/manual transfer, acknowledge alarms, start totalization or ramp/soak operations, and select between enabled local or remote set-points. This section discusses using digital inputs for auto/manual transfer and set-point selection. For information on totalization and rampsoak operations, refer to the Totalization Operation and Ramp/Soak Operation sections.
IB-23C650 BASIC OPERATION If the digital input action is configured to be REVERSE, a closed contact will be treated as an open contact and vice versa. Note: Unless “A/M key lockout” is enabled in the DIG INPT MENU, the controller mode can be changed at the front panel regardless of the digital input state, causing possible conflict. To effect auto/manual transfer using digital inputs, complete the following steps: 1.
IB-23C650 BASIC OPERATION 2. Select whether to lock out the front panel from making set-point transfers, whether transitions are allowed between local and remote set-points, and the digital input action (DIRECT or REVERSE). 3. Choose which set-points to select between in the digital set-point selection list (e.g., LOC, LO2). Refer to Table 3 for information on the DIG INPT MENU. 4. Enable the digital input in the DISPLAYS MENU.
IB-23C650 BASIC OPERATION A transition in the state of either digital input (opened to closed, or closed to opened) will now cause a set-point transfer. For example, if the digital inputs are set up for set-point selection between LOC, LO3, LO4, and REM (using DIRECT action, with Input 2 enabled and local/remote transfer allowed), a state change of the digital inputs to DI-1 closed and DI-2 opened will cause a transfer to LO4.
IB-23C650 BASIC OPERATION combination of the four display alarms. Monitoring and acknowledging alarms are basic operator activities. Acknowledgment of alarms may or may not be required depending on the alarm set up in the ALARMS MENU. During power-up the alarm relay(s) remained powered down until an accurate process input reading was made. Relays selected as alarms will be in a fail-safe condition (powered when alarm is not active) until the alarm is active.
IB-23C650 BASIC OPERATION ALARM AND RELAY STATUS WITH ACKNOWLEDGMENT Normal Operation, Relay Energized Alarm Ceases Alarm Occurs ACK’d Alarm still exists Steady LED Relay De-energized Alternating Process Variable and Alarm Message, Flashing LED, Relay De-energized ACK’d Alarm Ceases before ACK Alternating Process Variable and Alarm Message, Flashing LED, Relay Energized ALARM AND RELAY STATUS WITH ACKNOWLEDGMENT AND LATCH Alarm Occurs Normal Operation, Relay Energized Alarm Ceases ACK’d Alarm s
IB-23C650 BASIC OPERATION Alarm Messages An alarm is active when the process input (PROC), input 2 (INP2), control output (OUT), or deviation value (DEV) exceeds its alarm limit. When an alarm is active, the alarm indicator flashes and the front panel alarm message for the appropriate high (HI) or low (LO) turns on and flashes alternately with the process display. Any such configured alarm output relay is also active.
IB-23C650 BASIC OPERATION When the alarm finally stops, the alarm indicator will go out. If there is an alarm at one limit that has not been acknowledged (e.g. HI), and then the process subsequently trips the alarm at another limit (LO, HI-HI, or LO-LO), only the highest priority unacknowledged alarm will flash. If the low alarm remains when the alarm is acknowledged, the high alarm will extinguish and the low alarm will assume a steady-on condition.
IB-23C650 BASIC OPERATION STARTUP Procedures may vary from application to application, depending upon individual requirements and controller setup. The initial operating mode (usually manual), the set-point source (usually local), set-point value, and controller output can be configured for specified safe values when power to the controller is first applied. Each time a control application is first started up, check all these items before turn-on.
IB-23C650 BASIC OPERATION 4. Manually adjust output of controller to bring process variable up to final value. Ramping the output should be slow enough to allow the process to respond without overshooting the required control point.
IB-23C650 TUNING TUNING MANUAL TUNING The controller response parameters: Gain (P), Integral (I), and Derivative (D) are adjustable over a wide range of values to accommodate many different process characteristics. After the controller is installed in a specific control application, these response parameters must be tuned to the characteristics of the process so that overall system performance is at its best.
IB-23C650 TUNING Tuning Procedure The following procedure for tuning a controller is applicable to controllers set up for P (gain), PI (gain plus integral), PD (gain plus derivative), and PID (gain plus integral plus derivative) responses. If a recorder is available to record the process variable, it will be helpful in determining optimum controller settings. 1. Start up controller in manual mode as described in the Setup section. 2. When process and set-point are together, switch to automatic mode. 3.
IB-23C650 TUNING Figure 17. Process Recovery Cycle with Optimum Response Settings Increasing the gain setting increases cycle B relative to cycle A. If the controller has gain response only, no further adjustment is required. If the controller has two or three responses, proceed to Step 7. 7. Measure the period (P) of oscillation in minutes. The period is the time required for one complete cycle. 8. Calculate I (integral) and D (derivative) values as follows: a.
IB-23C650 TUNING b. Controller with P and D responses: D= c. 8 Controller with P, I, and D responses: I= D= 9. P (Minutes) 1.5 P (Minutes) P (Minutes) 6 Access TUNE MENU and adjust settings to values determined in Step 8. 10. Repeat Steps 4, 5, and 6 to obtain optimum gain setting.
IB-23C650 TUNING AUTOMATIC TUNING Automatic tuning (autotune) is an on-demand user activated feature which automatically calculates either PI or PID response values based on process reaction during an autotune cycle. This is accomplished by manipulating the controller output to effect a periodic response by the intended process. The autotune cycle requires 6 process oscillations to determine the tuning parameters. The controller output and a typical process response are as shown in Figure 18.
IB-23C650 TUNING Table 13. Autotune Procedure Step Step Description Top Display 1 Displays Menu. UP moves to TUNE **MENU**. DN moves to BASE CFG **MENU**. SCRL to obtain process/set-point display, Step 2. DISPLAYS 2 Process/Set-Point Display. UP increases set-point value. DN decreases set-point value. SCRL to obtain process/output display Step 3. TAG NAME 3 Adjust Starting Output (manual only). UP or DN to adjust output to a safe starting value for the process.
IB-23C650 TUNING Table 13. Autotune Procedure Middle Display Bottom Display Entry Description Installation and Setup Check. Installation, and Setup must be completed before executing auto tune. Note the following: **MENU** • Output limits are applied during autotune execution. • Digital input must be set at [none] or not enabled to use autotune. • Correct control action is essential for successful autotune execution. Control Action Check.
IB-23C650 TUNING Table 13. Autotune Procedure Step Step Description Top Display 4 Autotune Activation. UP enters autotune setup. SCRL to return to Step 2. TAG NAME 5 Output Step Size. UP or DN adjusts output step size. SCRL to Step 6. TAG NAME 6 Hysteresis Value. UP or DN adjusts hysteresis value. SCRL to Step 7.
IB-23C650 TUNING Table 13. Autotune Procedure Middle Display xxx Process Value STEP SIZ Bottom Display Entry Description ATN is displayed to indicate the Autotune point of entry. 10.1 Valid values are 0.1 to 50.0. The controller output will change by plus and minus the output step size from its initial starting value when autotune is executed (refer to Figure 18).
IB-23C650 TUNING Table 13. Autotune Procedure Step Step Description Top Display 7 Process High Trip-Point. UP or DN adjusts process high trip-point value. SCRL to Step 8 or press and hold SCRL to return to STEP SIZ (Step 5). TAG NAME 8 Process Low Trip-Point. UP or DN adjusts process low trip-point value. SCRL to Step 9 or press and hold SCRL to return to STEP SIZ (Step 5). TAG NAME 9 Parameter Tune Selection. UP or DN selects PI or PID tuning. SCRL to start autotune execution Step 10.
IB-23C650 TUNING Table 13. Autotune Procedure Middle Display PROC HI Bottom Display Entry Description 100 Valid values are: -2997 or PROC LO+3 to 30000. Remember, the range shown is for the units decimal position. The process value must be between the high and low trip-point values when autotune is activated.
IB-23C650 TUNING Table 13. Autotune Procedure Step Step Description Top Display 11.1 Increase Step. SCRL to Step 11.2 for a response limited message. Otherwise returns to Process/Set-Point display. TAG NAME 11.2 Proportional Band or Reset High. SCRL returns to Process/Set-Point display. TAG NAME 12 Autotune Failure. SCRL to advance to: Step 12.1 for a process slow message, or Step 12.2 for a decrease step size message. TAG NAME 12.1 Process Slow. SCRL to advance to: Step 12.
IB-23C650 TUNING Table 13. Autotune Procedure Middle Display INCREASE Bottom Display Entry Description STEP SIZ The ratio of process oscillation to hysteresis value is too small for best results. Check tuning constants. If desired, restart autotune with a larger output step size or a smaller hysteresis value. Hysteresis must be at least equal to, and preferably greater than, process noise. RESPONSE LIMITED The controller is using the high limit for proportional band or reset. Check tuning constants.
IB-23C650 TUNING Autotune Completion Autotune will generally result in successful calculation of tuning constants. When a completely successful autotune cycle is completed, the controller will be in the automatic mode using the newly calculated tuning constants, and will display the process variable and the controller set-point. If autotune was activated while in the automatic mode, or in manual without set-point tracking, the set-point will be at the same value it was at prior to autotune.
IB-23C650 TUNING Cancellation During Execution Press the manual key to cancel the autotune cycle during execution by the controller. This will prevent completion and will place the controller in the manual mode. The controller output will be changed to the starting output value prior to the execution of autotune. If the controller is in automatic mode when the cancellation is executed, the controller will cancel the autotune cycle and will change to manual mode.
IB-23C650 TUNING Blank Page 168
IB-23C650 RAMP/SOAK OPERATION RAMP/SOAK OPERATION DESCRIPTION OF RAMP/SOAK PROFILE The Ramp/Soak Profile option complements any type of control implementation by adding a ramp/soak set-point profile with up to 10 ramp or soak segments. The ramp function changes the local set-point up or down at a specified rate. The soak function maintains the set-point at a fixed value for a specified period of time. Figure 19 shows a typical profile and some of its features.
IB-23C650 RAMP/SOAK OPERATION Figure 19.
IB-23C650 RAMP/SOAK OPERATION OPERATION IN AUTOMATIC The ramp/soak sequence is initiated and monitored in the DISPLAYS MENU where the instrument display appears similar to the example below. To access Autotune or remote set-point capabilities, the ramp/soak profile must be turned off. If tune or configuration passwords were configured in the BASE CFG MENU, these codes are required to initiate a reset or segment skip.
IB-23C650 RAMP/SOAK OPERATION After selecting RUN or HOLD at the beginning of the ramp/soak display sequence, scrolling accesses the segment status display as shown below: Segment number Time base Time remaining In this example, 1.4 minutes are left in segment 1 of the profile. The initial value for time remaining in a segment is 0.1 units more than the configured value even though the actual time a segment runs is the configured time.
IB-23C650 RAMP/SOAK OPERATION If the [SKIP] or [RESET] prompts do not appear, a password has been configured in the BASE CFG MENU and is required to access these prompts in addition to making changes in other menus. CONTROLLING RAMP/SOAK PROFILE Control of the ramp/soak profile is accomplished in the DISPLAYS MENU where the ramp/soak functions for reset and skip may be manipulated while ramp/soak is on [RSK] [RUN].
IB-23C650 RAMP/SOAK OPERATION • If the skipped segment is the last segment in the profile and the cycle is configured to repeat, the skip returns the profile to the start of the first segment. This action is the same as a reset except that cycle number is not changed. The controller responds in the manner described for a reset.
IB-23C650 RAMP/SOAK OPERATION Ramp or Soak Hysteresis The hysteresis function provides for setting up a band of process variable values relative to the set-point. For example, a temperature hysteresis value of 10*F provides a band between 290 and 310*F when the set-point is 300*F. The band also applies to the set-point, preventing a profile from starting if the set-point is outside the band.
IB-23C650 RAMP/SOAK OPERATION manual set-point is not at the same value as the ramp/soak profile set-point (the ramp/soak profile is paused at its current set-point value when the controller is put in manual). The switch back to automatic causes the process variable to be under automatic control in response to the ramp/soak set-point.
IB-23C650 TOTALIZER OPERATION TOTALIZER OPERATION DESCRIPTION OF INTEGRATION/TOTALIZATION FUNCTION The integrator/totalizer provides the capability to integrate process signals and display totalized values on the front panel. Signals which have a linear relationship can be integrated and totalized directly. Flow signals, which are proportional to differential pressure, require the application of square law linearization which is available as a standard function.
IB-23C650 TOTALIZER OPERATION • Scale Factor This feature allows custom scaling of the totalized value. The reciprocal of the entered value (0.001 to 30000) is used as the totalizer scale factor. OPERATION OF CONTROLLER USING TOTALIZATION The operating procedure for integration/totalization is very similar to that of a controller without totalization enabled.
IB-23C650 TOTALIZER OPERATION Preset Value The preset value is the number from which the totalizer starts counting after a wrap or when the totalizer was first initiated. This value is typically 0. Leading zeros are not suppressed. Predetermined Count The predetermined count is the value at which the totalizer resets and starts over when the wrap function is enabled. If a totalizer event relay is enabled in the RELAYS MENU, the relay transfers to signal that the predetermined count has been reached.
IB-23C650 TOTALIZER OPERATION EXAMPLES OF TOTALIZER COUNT FACTORS There are three configurable factors that affect what one totalized count equals in actual engineering units and how quickly the totalizer counts. The first factor is the engineering units configured in the TOTALIZE MENU. The other factors are the rate (engineering units time base), and the totalizer scale factor. Table 14 and its notes give several flow examples of how these factors affect the totalizer count.
IB-23C650 TOTALIZER OPERATION Table 14. Examples of Totalizer Count Factors Actual Flow at 100% Configured Engineering Units (Note 1) Scale (Disp. Mult.) Configured Rate Scale Factor (Note 2) 1 Count Equals (Note 3) Minimum Rollover Time (Note 4) 6,000,000 gal/day 0 to 4167 gal/min x1 MIN 1 1 gal 40.0 Hrs 6,000,000 gal/day 0 to 416.7 gal/min x 10 MIN 0.1 1 gal 40.
IB-23C650 TOTALIZER OPERATION 2.) Configured scale factors are 0.001 to 30000. The unscaled total is divided by the configured scale factor to get the scaled count. 3.) The calculation for 1 count is based upon the display multiplier and scale factor. Since the scale factor is a divisor of the count, it has an inverse effect on the display multiplier when calculating count and so a multiplier of 10 times a scale factor of 0.1 equals 1, or 1 count equals 1 unit. 4.
IB-23C650 RATIO BIAS CONTROL RATIO BIAS CONTROL RATIO BIAS CONTROLLER Ratio bias control systems maintain two or more process variables at a predetermined relationship, or ratio. In a ratio bias controller the ratio or bias value is applied to the remote set-point input before the set-point is passed to the PID algorithm. The output of the PID algorithm controls the dependent flow valve in order to maintain the correct ingredient relationship.
IB-23C650 RATIO BIAS CONTROL The independent (wild) flow changes from time to time, and in order to maintain the correct proportions of the blend the other (dependent) flow must be controlled to change in a like manner. The dependent flow must change in the same relationship, or ratio, to changes in the independent flow. The wild flow is not necessarily uncontrolled; it is only wild insofar as the ratio system is concerned.
IB-23C650 RATIO BIAS CONTROL correct ratio value. When the streams do not have the same flow range, the variables must be expressed in engineering units to obtain the correct flow and signal ratio values. Most applications require direct ratio; the dependent variable increases as the independent variable increases. If the signal representing the variable is not linear, it can be linearized using the square root extraction function.
IB-23C650 RATIO BIAS CONTROL Figure 22. Effect of Ratio Adjustment in an Inverse Ratio Control System Figure 23.
Flow Transmitter 2 Process Input Remote Ratio or Bias Remote Set-Point A/M Ratio Bias Station Flow Transmitter 1 Dependent (Controlled) Flow aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
IB-23C650 RATIO BIAS CONTROL A typical A/M Ratio Station application where a plant master steam flow controller provides an input to two boiler masters (A/M ratio stations) is shown in Figure 25.. Each of the two A/M Ratio Stations receive the same process signal from the plant master but their outputs to the combustion control system are different due to different ratios applied to their common process inputs. This is done to balance boiler loading in an effort to optimize boiler efficiency.
IB-23C650 RATIO BIAS CONTROL Instrument Set-up To implement an A/M Ratio Bias Station, enter into the BASE CFG **MENU**, Table 1, and enable A/M Ratio Bias Station at the RAT BIAS ENABLE prompt. If the ratio or bias value is to come from an external source, input two must also be enabled. Configure the station using the RAT BIAS **MENU**, Table 7. The station type can be designated as ratio only, bias only or both ratio and bias.
IB-23C650 RATIO BIAS CONTROL Blank Page 190
IB-23C650 TIME PROPORTIONING CONTROL TIME PROPORTIONING CONTROL DESCRIPTION Time proportioning control permits PID control to be used in applications where the control element is an on/off device. The control output is provided by a mechanical SPDT relay. The local set-point and manual control adjustments are made using front panel keys. Process and set-point values are displayed in engineering units, and the calculated output is displayed in percent of output span.
IB-23C650 TIME PROPORTIONING CONTROL PID Output % of Span 90% 50% On 10% Off 40 50 60 Time – Seconds 70 S-1107-41B Cycle Time 10 Seconds Figure 26.
IB-23C650 CURRENT PROPORTIONING CONTROL CURRENT PROPORTIONING CONTROL DESCRIPTION The controller provides an adjustable dc current output signal for current proportioning (analog) control applications. The maximum output load is 1000 ohms for 20 mA and 400 ohms for 50 mA. Control adjustments, displays, and calculated outputs are similar to the time proportioning controller. The calculated output goes to the output driver which generates the current output signal.
IB-23C650 CURRENT PROPORTIONING CONTROL blank page 194
IB-23C650 DUAL OUTPUT CONTROL DUAL OUTPUT (HEAT/COOL) CONTROL DESCRIPTION The controller can provide dual output (heat/cool) control with each of the three available output types; dual dc current, dual SPDT relay, or dc current and SPDT relay. When the controller is set up for dual control, manual tuning is required. An option board is required when using heat/cool with dual curent output.
IB-23C650 DUAL OUTPUT CONTROL 100% or Cool High Limit 100% or Heat High Limit Cool Action Heat Action Heat Output Cool Output 50% (Displayed Value) Output Off Hysteresis 0% 0% 75% Crossover Output Value 0% 100% Transition Bandwidth Calculated Controller Output (Reverse Control Action) S-1107-248A Figure 27.
IB-23C650 ON/OFF CONTROL ON/OFF CONTROL DESCRIPTION The on/off output calculation diagram is shown in Figure 29. The local setpoint adjustment is made using the front panel keys. The calculated output signal, either ON or OFF is displayed as a percentage. ON is indicated by 100% and OFF is indicated by 0%. When the controller is operating in automatic, the control algorithm receives the active set-point and process input signals.
IB-23C650 ON/OFF CONTROL Active SetPoint Process ON/OFF OUTPUT CALCULATION On/Off Control Algorithm Output Switch Auto Calculated Output Output Driver Relay Output Manual S-1107-265(1) • Span • Differential Gap • Action (Dir/Rev) • Cycle Time (Manual Only) Manual Adjustment Figure 29. On/Off Output Calculation Figure 30.
IB-23C650 POSITION PROPORTIONING CONTROL POSITIONING PROPORTIONING CONTROL DESCRIPTION Positioning proportioning control permits PID control to be used in applications where the control element is an on/off positioning device such as a motorized valve. The controller output is provided by two SPDT relays. One relay actuates opening of the valve, and the other closing of the valve. Positioning proportioning control requires the option board to receive the valve position feedback.
IB-23C650 POSITION PROPORTIONING CONTROL Reasonable values for Position Proportioning Deadband and Preact can be determined using the following procedure. 1. Perform the valve calibration in the BASE CFG MENU. 2. In the TUNE MENU, set the controller gain to 0.1, Reset to OFF. and Preact to 0. Due to the very slow control action with these settings, valve position can now be read by switching to Auto and quickly observing the output display.
IB-23C650 DIAGNOSTICS DIAGNOSTICS INPUT FAILURE AND POWER FAILURE DETECTION The fault detection level for volt inputs is determined by the percent of volt input span value entered in the INPUTS MENU. If there is a process input signal failure, the controller responds as follows: • If the recovery option is manual, the controller in the automatic mode is forced to manual with local set-point and the output value is switched to the fault output value.
IB-23C650 DIAGNOSTICS conditions using the UP key.
IB-23C650 DIAGNOSTICS The following messages may indicate a failure of a component. If the message is temporary, the cause may be some other electrical problem causing a glitch and no action is necessary. If the message does not go away, after cycling the power for example, return your instrument to an authorized service representative. • [MAIN CAL] or [OPTN CAL] Main or Option board factory calibration constants are missing or bad. • [DB CHKSUM] Database checksum error.
IB-23C650 DIAGNOSTICS Problem No display Display of process value is erratic. No control output 204 Possible Cause Action a. No power to controller. a. Turn on power. b. Controller not fully seated in housing. b. Tighten two jack screws in bezel until controller seats. c. Incorrect power connections. c. Check power connections. d. Display ribbon cable not seated on the display board or the processor board. d. Reseat ribbon cable into its connector a.
IB-23C650 CALIBRATION DATA CALIBRATION DATA INTRODUCTION The 2050R base controller (main board) is factory calibrated and does not require calibration data. The main board calibration data procedure is for factory use only and is included for reference only. Option board calibration data is entered after installing the option board. Follow the steps in the BASE CFG MENU to get to the OPTN BRD CALIBRAT entry point. (You must have a non-zero configuration password to get this field.).
IB-23C650 CALIBRATION DATA Table 15. Main/Option Board Calibration (Base Configuration Menu) Step Step Description Top Display 16 Main Board Calibration. UP begins calibration at Step 16.1 (Factory ONLY). SCRL advances to Step 17 (Option Board Calibration). MAIN BRD 16.1 Process Input Voltage Ref. High UP begins entry at most significant digit. Use UP or DN to set the digit, then SCRL to scroll to the next digit. Repeat for all digits. SCRL advances to: Step 16.1.1 if value was changed. Step 16.
IB-23C650 CALIBRATION DATA Table 15. Middle Display CALIBRAT VREF HI Main/Option Board Calibration (Base Configuration Menu) Bottom Display Entry Description NOTE: These are factory calibration values and should be altered only on the advice of authorized service personnel. Changing any or all of the 4 calibration values will cause the instrument to mark the main instrument calibration valid. xxxxxxxx = Any hexadecimal digit. See note on Step 16.
IB-23C650 CALIBRATION DATA Table 15. Main/Option Board Calibration (Base Configuration Menu) Step Step Description Top Display 16.3 Process Input Ma. Resistance Ratio UP begins entry at most significant digit. Use UP or DN to set the digit, then SCRL to scroll to the next digit. Repeat for all digits. SCRL advances to: Step 16.3.1 if value was changed. Step 16.4. otherwise. PROC INP 16.3.1 Are You Sure You Want to Change Process Ma. Res. Ratio? UP selects YES or DN selects NO.
IB-23C650 CALIBRATION DATA Table 15. Main/Option Board Calibration (Base Configuration Menu) Middle Display Bottom Display MR RATIO xxxxxxxx = any hexadecimal number. Entry Description See note on Step 16. SURE? YES This step is present only to guard against NO accidentally changing this critical calibration value. CKT COMP xxxxxxxx = any hexadecimal number. See note on Step 16. SURE? YES This step is present only to guard against NO accidentally changing this critical calibration value.
IB-23C650 CALIBRATION DATA Table 15. Main/Option Board Calibration (Base Configuration Menu) Step Step Description Top Display 17 Option Board Calibration. Constants UP begins calibration at Step 17.1. SCRL advances to step 18, Default Database entry point, in BASE CFG MENU (Table 1). 17.1 Input 2 Voltage Ref. High UP begins entry at most significant digit. Use UP or DN to set the digit, then SCRL to scroll to the next digit. Repeat for all digits. SCRL advances to: Step 17.1.1 if value was changed.
IB-23C650 CALIBRATION DATA Table 15. Middle Display CALIBRAT Main/Option Board Calibration (Base Configuration Menu) Bottom Display Entry Description NOTE: These calibration values should be altered only when installing the option board for the first time. Changing any or all of the 4 calibration values will cause the instrument to mark the option board calibration valid. Calibration data is shipped with the option board. VREF HI xxxxxxxx = Any hexadecimal digit. See note on Step 17.
IB-23C650 CALIBRATION DATA Table 15. Main/Option Board Calibration (Base Configuration Menu) Step Step Description Top Display 17.3 Input 2 Ma. Resistance Ratio UP begins entry at most significant digit. Use UP or DN to set the digit, then SCRL to scroll to the next digit. Repeat for all digits. SCRL advances to: Step 17.3.1 if value was changed. Step 17.4 otherwise. INPUT 2 17.3.1 Are You Sure You Want to Change Input 2 Ma. Res. Ratio? UP selects YES or DN selects NO. SCRL advances to: Step 17.
IB-23C650 CALIBRATION DATA Table 15. Main/Option Board Calibration (Base Configuration Menu) Middle Display Bottom Display MR RATIO xxxxxxxx = Any hexadecimal digit. Entry Description See note on Step 17. SURE? YES This step is present only to guard against NO accidentally changing this critical calibration value. CKT COMP xxxxxxxx = Any hexadecimal digit. See note on Step 17. SURE? YES This step is present only to guard against NO accidentally changing this critical calibration value.
IB-23C650 PARTS AND MAINTENANCE PARTS AND MAINTENANCE PARTS AVAILABILITY The MODCELL 2050 Controller parts available for purchase are: • Termination Assembly (124S2330-1) • CPU Board (ac), for 205_RZ23___A (125U2951-3)* • CPU Board (ac), for EU EMC 205_RZ12___A (125U2951-15) • Display Assembly (125U2955-3)* • Option Board (2050NZ10100A)* * Recommended Spare Parts. The Option Board provides an additional isolated universal analog input and analog output.
IB-23C650 RECORD OF DATABASE DESCRIPTION This section provides tables of the database fields for planning and recording your configuration entries via the configuration menus. The database records provide a reference when entering the configuration and then a record of your configuration. Make copies of these pages as needed. Blank fill-in fields on these tables represent configuration fields that require a selection.
IB-23C650 Data Base Record Middle Display Bot. Disp. Entry aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa Top Display Top Display Middle Display Bot. Disp.
Top Display RIGHT BAR DEV BAR FULL SCL MA. OUTP **MENU** DIG INPT **MENU** OUTPUT MA. HIGH DIGITAL INPUT 1 OUTPUT MA.
218 RAT BIAS **MENU** RAT BIAS LOC_SETP LOC SETP FIXED LOC SETP HI LIMIT LOC SETP LO LIMIT LOC SETP INIT VAL SETPT 2 SETPT 2 ENABLE SETPT 2 FIXED SETPT 2 HI LIMIT SETPT 2 LO LIMIT SETPT 2 INIT VAL SETPT 3 SETPT 3 ENABLE PRESET VALUE SETPT 3 FIXED PREDETRD COUNT SETPT 3 HI LIMIT aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaaaaaa aaaa SETPT 3 LO LIMIT
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa RAMPSOAK **MENU** RAMPSOAK REPEAT SOAK HYST RAMP HYST RAMPSOAK IS ON / OFF RAMPSOAK UNIT TIM RAMPSOAK SEGMENTS SE
ALARMS ALARM 2 **MENU** ALARM 4 PRIORITY BEEP ON OCCUR OF ALARM 4 HYST ALRM ACK REQD ON TUNE **MENU** OVERCFGD DIAG ON TAG NAME P1 RELAY ACTION ON/OFF DIFF GAP P2 RELAY ACTION GAIN HEAT ALARM 1 SETUP GAIN COOL ALARM 1 TYPE AL1 TRIP IN HEAT RESET ENABLE ALARM 1 TRIP RESET HEAT ALARM 1 PRIORITY RESET COOL ALARM 1 HYST ALARM 2 SETUP FIXED MAN RSET TYPE MANUAL RESET 220 Middle Display Bot. Disp.
The Company’s policy is one of continuous product improvement and the right is reserved to modify the information contained herein without notice, or to make engineering refinements that may not be reflected in this bulletin. Micromod Automation assumes no responsibility for errors that may appear in this manual. © 2004 MicroMod Automation, Inc. Printed in USA IB-23C650, Issue 7 3/2010 MicroMod Automation, Inc. 75 Town Centre Drive Rochester, NY USA 14623 Tel. 585-321 9250 Fax 585-321 9251 www.