Specifications

Magic Aire Factory Control Options
I0M# 011-200001-003
MicroNet LONMARK® 200 Series Controllers
The I/A Series MicroNet LONMARK 200 Series
Controllers MN 200 is an interoperable, LONMARK-certified
controllers. Controllers are loaded with a pre-engineered application,
that provides control for Magic Aire unit ventilators.
Controllers feature Sensor Link (S-Link) support, LED indication,
screw terminal blocks and are panel mounted in the left end
compartment. These controllers can function in either standalone
mode or as part of a LONWORKS® FTT-10 Free Topology
communications network that must be field provided.
Applications
Designed for new or existing system installations,
the MN controller provides control for:
Unit Ventilators
Connectivity
Controllers offer the advantages of standalone and
networked control. Using an I/A Series MicroNet
Sensor (MN-SX series), the operator can monitor
controller performance and edit operational values.
The WorkPlace Tech Tool software is used to
program the controllers.
Features —
Field programmable using WorkPlace Tech Tool.
Uses LONMARK HVAC profiles for
interoperability.
Capability to function in standalone mode or as
part of a LONWORKS FTT-10 Free Topology
communications network.
Multiple controllers on a LonWorks FTT network
creates a complex network of controllers for virtually
any building control needs.
Proportional (P) damper control and Proportional
Plus Integral (PI) for heating and cooling control.,
and Proportional Plus Integral and Derivative (PID)
control for cooling and heating.
Onboard LED indication without cover removal.
Plenum-rated enclosure allows direct mounting in
plenum.
Protective hinged covers provide access to field
wiring terminals.
Hardware Specifications
Dimensions 4 5/16" high x 4 3/8" wide x 2" deep
(109 mm x 111 mm x 51 mm).
Enclosure
Conforms to NEMA-1 requirements.
Meets UL94-5V flammability for plenum application use.
Power Supply Input
20.4 to 30 Vac, 50/60 Hz.
Maximum Power Consumption 15 VA @ 24 Vac,
50/60 Hz, excluding relay output power.
Surge Immunity Compliance
ANSI C62.41 (IEEE-587, Category A & B).
Agency Listings
FCC, Class B.
UL Listed
UL-916 (File # E71385 Category PAZX).
UL Listed to Canadian Safety Standards (CAN/CSA
C22.2).
European Community – EMC Directive
Emissions EN50081-1.
Immunity EN50082-1.
Mounting 35 mm DIN rail or panel.
Ambient Limits Operating Temperature -40 to 140
°F (-40 to 60 °C).
Shipping and Storage Temperature -40 to 160 °F
(-40 to 71 °C).
Humidity 5 to 95% RH, non-condensing.
Wiring Terminals Screw terminals.
AWG #16 to #24 (1.5 mm2 maximum) wire.
Inputs (from I/A Series MicroNet Sensors)
Space Temperature 32 to 122 °F (0 to 50 °C).
Adjustable Setpoints 40 to 95 °F (4.4 to 35 °C).
Override Pushbutton For standalone occupancy
control or remote status monitoring of local status
condition.
Digital Inputs Dry Contact.
Detection of closed switch requires less than 300 ohms.
Detection of open switch requires more than 100K ohms.
Digital Outputs
7/1/03 Part Number 011-200001-003