MODEL: DRY 300i & 500i Silver
EN Thank you for your decision to purchase our device. Please read this user manual carefully before starting to use the device. Please keep the instructions of this practical quide in order to get a quick know-how. We do not take any responsibility or provide warranty in case of damage, loss or damnification caused by incorrect usage or usage for other purposes, not specified in this manual. Contents: 1. Safety measures 2. Usage specification 3. Instructions for use 4. Instructions for maintenance 5.
EN 3. INSTRUCTIONS FOR USE 3.1. Humidity regulation with an inbuilt digital humidistat located in the cover of the equipment The inbuilt humidistat is located in the cover of the device. It reads the humidiy of the incoming air, and depending on the set value, switches on the compressor. In indoor swimming pool halls, the correct air humidity should range between 55% and 65 %.
EN 3.4. Compressor regulation The compressor´s operation starting is for securing its protection, delayed by min. 3 minutes. Depending on the humidity of environment, it may last even longer. The user must not manipulate with the setting element of a time relay. 4. MAINTENANCE INSTRUCTIONS It is necessary to make sure that the intake- and exhaust outlet are not covered. It is forbidden to place towels or clothes on the exhaust outlet, to dry them.
EN 6.4. Position assuring of the device The design of the device enables its safe mounting and proper fixation even if lifted accidentally. There are slots for safety screws accessible after dismounting a front fibreglass cover, located in the top corners of the rear plate. There is an arrow that indicates safety screw slots in the rear plate. The safety screw is fixed through a slot in the rear plate into a wall fastener.
EN DEVICE LOCATION Device location must be in accordance with HD 384.7.702 S1 and IEC 60364-7-702 standard. It is recommended to locate the device outside zones 0,1 and 2. In case the device is located into zones 2 or 1, HD and IEC standards´requirements must be satisfied.
EN DRY 300i Silver swimming pool dehumidifier parameters SIDE VIEW FRONT VIEW SLIPPING OUT FROM A CONSOLE PREVENTING POSITION SECURING (FROM BEHIND) SLIPPING OUT FROM A CONSOLE PREVENTING POSITION SECURING (FROM BEHIND) CONSOLE CONDENSATE DRAIN (FROM THE BEHIND) PIPE WITH AN INTERNAL DIAMETER OF MINIMUM 16 mm POWER SUPPLY (FROM THE BEHIND) 2 CYSY WIRE 3C x 1.
EN WIRING DIAGRAM OF MICROWELL DRY 300i SILVER ELECTRIC CIRCUIT DIAGRAM AND WIRING DIAGRAM OF MICROWELL DRY 300i SILVER LOW PRESSURE PRESSOSTAT HIGH PRESSURE PRESSOSTAT COMPRESSOR DIGITAL HYGROSTAT THERMAL PROTECTION FAN BACK-UP MECHANICAL HYGROSTAT FAN CONDENSOR CONTINUOUS OPERATION CYCLIC OPERATION THERMOSTAT -1°С SWITCHING RELAY FAN MODE SWITCH FAN CONDENSOR HIGH PRESSURE PRESSOSTAT 2,5 MPa LOW PRESSURE PRESSOSTAT 0,2 MPa COMPRESSOR CONDENSOR TERMINAL BOARD FAN TIME RELAY 3 min.
EN 7. Technical data TECHNICAL DATA UNITS m2 For swimming pools with max.