11.1.8
Display LED STATUS
P1 Over load or too low voltage protection
11.1.9
Display LED STATUS
P2 Compressor top protection against temperature
Off: 120c; On: 105c
No
Is the power supply right?
Check the outdoor power board
Replace the outdoor power board
Yes
Does compressor operate?
Is refrigerant circulation volume normal?
Gas charging
Is abnormality the same after gas charging
Check refrigerant system (such as clogging of capillary, etc)
Is protector normal?
Check the outdoor main PCB.
Replace protector
No
Yes
Yes
No
No