Installation Instructions

a.Aligntheswingmotoronthepaneltothetubingjointsofthebodyproperly.(Refertochart11)
b.Fixhooksofthepanelatswingmotoranditsoppositesidestothehooksofcorrespondingwater
receiver.(Refertochart11)Thenhangtheothertwopanelhooksontocorrespondinghangersof
thebody.(Refertochart11)
(3)Installthepanel
Donotcoilthewiringoftheswingmotorintothesealsponge.
7
Chart14
Loosenuppernut
Adjustlowernut
Gapnotallowed
Chart13
Leakage
Ceiling
Pollution
Watercondensation
Cross-screwdriver
Outletjoint
Tubingjoint Hookpanel
SwingMotor
Hook-bolt
Water-receiver
Chart11
panelsponge
Chart12
body
Ceiling
panel
panelfoam1
airout
Fan
panelfoam2
outletfoam
c.Adjustthefourpanelhookscrewstokeepthepanelhorizontal,andscrewthemuptotheceiling
evenly.(Refertochart11)
d.RegulatethepanelinthedirectionofthearrowinChart11slightlytofitthepanel'scentertothe
centeroftheceiling'sopening.Guaranteethathooksoffourcornersarefixedwell.
e.Keepfasteningthescrewsunderthepanelhooks,untilthethicknessofthespongebetweenthe
bodyandthepanel'soutlethasbeenreducedtoabout4~6mm.Theedgeofthepanelshould
contactwiththeceilingwell.(Refertochart12)
MalfunctiondescribedinChart13canbecausedbyinappropriatetightnessthescrew.
Ifthegapbetweenthepanelandceilingstillexistsafterfasteningthescrews,theheightofthe
indoorunitshouldbemodifiedagain.(Refertochart14-left)
Youcanmodifytheheightoftheindoorunitthroughtheopeningsonthepanel'sfourcorners,ifthe
liftoftheindoorunitandthedrainpipeisnotinfluenced(refertochart14-right).
(4)Hangtheair-ingridtothepanel,thenconnecttheleadterminatoroftheswingmotorandthatof
thecontrolboxwithcorrespondingterminatorsonthebodyrespectively.
(5)Relocatetheair-ingridintheprocedureofreversedorder.
(6)Relocatetheinstallationcover.
a.Fastentheropeofinstallationcoverontheboltoftheinstallationcover.(Refertochart15-left)
b.Presstheinstallationcoverintothepanelslightly.(Refertochart15-right)
Chart15
Installationcover
,
srope
TapScrew
Slidethefoursliders
inthecorresponding
channelwheninstalling
thecover
CAUTIONS