DC-GFP

You do not ground the battery negative when using the DC-GFP since the DC-GFP is now the
battery negative to earth ground bond. In the case of a fault current from either PV+ or PV- to
earth, the 1/2 amp section of the device will open and at the same time open the PV+ circuit path.