MN1000FUSE Specifications

EP.MERSEN.COM
SP 42
SPECIAL
PURPOSE
S
P
Voltage (VDC) Amperage (A) Catalog Number Reference Number
Watts Loss @ 70%
x I
n
(W)
Watts Loss @ 80%
x I
n
(W)
Watts Loss @ 100%
x I
n
(W)
Interrupting Rating
(kA)
Size (mm)
1000
1 HP10M1 B1018579 0.13 0.18 0.25
50
10x38
(Figure 1)
2 HP10M2* C1018580 0.16 0.25 0.32
3 HP10M3* D1018581 0.66 0.87 1.36
3.5 HP10M3-1/2 H1043977 0.67 0.84 1.31
4 HP10M4* E1018582 0.69 0.80 1.25
5 HP10M5* F1018583 0.59 0.73 1.12
6 HP10M6 G1018584 0.42 0.67 1.05
7 HP10M7 H1018585 0.40 0.64 1.00
8 HP10M8 J1018586 0.77 0.88 1.48
10 HP10M10* L1018588 0.67 0.9 1.5
12 HP10M12* M1018589 0.72 1.0 1.8
15 HP10M15* N1018590 0.9 1.3 2.2
20 HP10M20* P1018591 1.1 1.5 2.8
25 HP10M25* D1023825 1.3 1.8 3.0
30 HP10M30* E1023826 1.63 2.12 3.93
32 HP10M32* H1062170 1.7 2.3 4.0
1 HP10M1CC F10 61616 0.14 0.19 0.27
50
10 x 65
(Figure 2)
2 HP10M2CC G10 61617 0.17 0.27 0.35
3 HP10M3CC H10 61618 0.72 0.95 1.49
3.5 HP10M3-1/2CC J10 61619 0 .74 0.92 1.43
4 HP10M4CC K1061620 0.76 0.88 1.38
5 HP10M5CC L1061621 0.65 0.80 1.23
6 HP10M6CC J1061527 0.46 0.74 1.15
7 HP10M7CC K1061528 0.44 0.70 1.1
8 HP10M8CC L1061529 0.85 0.97 1.63
10 HP10M10CC M1061530 0.74 0.99 1.65
12 HP10M12CC N1061531 0.79 1.1 1.98
15 HP10M15CC P1061532 0.99 1.43 2.42
20 HP10M20CC Q1061533 1. 21 1.65 3.08
25 HP10M25CC R1061534 1.43 1.98 3.3
30 HP10M30CC S1061535 1.63 2.12 3.93
32 HP10M32CC T1061536 1.7 2.3 4.0
HP10M
1000V DC Midget (10x38mm) Photovoltaic Fuses
CATALOG NUMBERS AND ELECTRICAL CHARACTERISTICS
DIMENSIONS
Figure 2
Figure 1
CC terminal (Fig. 2): Recommended crimping tool: T & B Sta-Kon ERG4002 #10 -12 AWG (6-4 mm
2
)
* Available in 176-piece bulk pack (add -B sux to Catalog Number). Order quantity of one (1) -B sux Catalog Number yields 176 fuses.