Q-Series Breaker Specifications

Product Type
QL
QY QZ QDC
Standard Ampere Ratings (A)
Number of Poles
Rated Voltage (V)
VDE (EN 60947-2)
CE
cULus (UL489_CSA)
UL489A
cURus
(UL1077_CSA)
Dual Mounting
(DIN & Mini)
DIN Rail
Surface Clip
Plug-in
Tripping curves
Resistance to shock
Vibration
Operating temperature
Optional Accessories
Features
Approvals
&
Interrupt.
Capacity
(kA)
Mounting
Options
0.1 – 25
1, 2, 3, 1+N, 3+N
120V AC (1p)
120/240V AC(2p)
240V AC (1p)
240/415V AC 2, 4p)
6kA (240/415V AC)
10kA (120/240V AC)
1, 3, 9, KM, OP
IEC 60068-2-27, 5G/30ms half sine wave
IEC 77/IEC 60068-2-6, 3G/10-150Hz
-40°C to +65°C
Aux. switch Trip alarm
Aux. switch + trip alarm Bus bar
Handle lock
Compact 13mm/module width Hydraulic-magnetic technology
Precision tripping Suitable for isolation
Temperature independent trip point Mid trip handle
0.1 – 63 (1 pole)
0.1 – 50 (2 poles)
20 – 100 (2p parallel)
110 – 150 (3p parallel)
1, 2
2, 3p parallel
2 poles in series
80V DC
*125V DC (1, 2p & 2p
parallel)
*250V DC (2p in series)
10kA
10kA
OP, U2, 1, 9
0.1 – 60 (UL 1077)
5 – 50 (IEC 60947-2)
1, 2, 3, 1+N, 3+N
120V AC (1p)
240V AC (1p)
240/415V AC (2, 4p)
277V AC (1p)
277/480V AC (2, 3p)
3kA (240/415V AC)
5kA (1p, 120V ac)
5kA (277/480V ac)
1, 2, 3, 9, OP
0.1 – 63 (1 pole)
0.1 – 50 (2 poles)
20 – 100 (2p parallel)
110 – 150 (3p parallel)
1, 2
2, 3p parallel
2 poles in series
80V DC
*125V DC (1, 2p & 2p
parallel)
*250V DC (2p in series)
10kA
OP, U2, 1, 9
Q–Series Miniature Circuit Breakers
CBE Range
* Polarity Sensitive

Summary of content (4 pages)