KID Manual

The KID Solar Charge Controller Instructions
36 | Page
1 0-268-1 REV T
-FUNC: PWM Divert OFF/AUTO
This function will divert excess power to the load when extra power
is available and it will maintain 3 stage battery charging. There are 2 parameters that can be adjusted
when Pressing the SETUP button; Offset and Width
Offset:
This is measured in voltage and refers to an offset from the current battery voltage Set point. For
example, if the battery charging stage is Absorb, then the offset is taken from the Absorb set point. It will
be taken in the same manner from the other stages, and it will also take into account if the battery
temperature sensor is plugged in and set up.
Width:
This is measured in voltage and refers to the number of volts the transition will take, from On to
Off and vise-versa.
To use PWM Divert Mode do the Following:
From the Status Menu: Press Menu Back
Scroll to the Right and select Load and Press Enter
Select FUNC: PWM Divert
Press the Right button to *ON
Press the Save Button
Press SETUP button to adjust the Offset and Width set points.
-FUNC: Float ON:
The Load will be turned on when the battery state of charge is Float and it will turn
off when the state of charge is not Float.
To use Float On Mode do the Following:
From the Status Menu: Press Menu Back
Scroll to the Right and select Load and Press Enter
Select FUNC: Float On
Press the Right button to *Auto
Press the Save Button
-FUNC: Float OFF:
The Load will be turned off when the battery state of charge is Float and it will turn
on when the state of charge is not Float.
To use Float Off Mode do the Following:
From the Status Menu: Press Menu Back
Scroll to the Right and select Load and Press Enter
Select FUNC: Float Off
Press the Right button to *Auto
Press the Save Button
-FUNC: Diversion OFF/AUTO
Diversion OFF/AUTO This function will divert excess power,
when available, to the load. This mode is not PWM based. There are 2 parameters that can be adjusted
when Pressing the SETUP button: VoltOn and VoltOff.
To use Diversion Mode do the Following:
From the Status Menu: Press Menu Back
Scroll to the Right and select Load and Press Enter
Select FUNC: Diversion
Press the Right button to *ON
Press the Save Button
Press SETUP button to adjust the VoltsOn and VoltsOff set points.