MidNite Solar Kid Manual

The KID Solar Charge Controller Instructions
-FUNC: Toggle Test OFF/AUTO This Mode is for testing purposes only, it will turn the
load On and Off at twice per second.
-FUNC: LVD Alarm OFF/AUTO - This mode will turn on if the battery voltage goes below
the AlrmON set point and turn OFF if it goes above the AlrmOFF Set point.
From the Status Menu: Press Menu Back
Scroll to the Right and select Load and Press Enter
Select FUNC: LVD Alarm
Press the Right button to *ON
Press the Save Button
Press SETUP button to adjust the VoltsOn and VoltsOff set points.
Note: the AlrmOn/AlrmOFF setpoints are independent from those on the AUX Port.
-FUNC: NightVarOff OFF/AUTO - Turns the load on for a user selected amount of time after
dusk and before dawn.
From the Status Menu: Press Menu Back
Scroll to the Right and select Load and Press Enter
Select FUNC: NightVarOff
Press the Right button to *Auto
Press the Save Button
Press SETUP button to adjust the how long after dusk and before dawn the load will be turned on.
-FUNC: Hourly OFF/AUTO - In this mode the clock re-adjusts the time every night by using the PV
panels to detect dusk and dawn. The time it is only an estimate and it does not take into account DST.
From the Status Menu: Press Menu Back
Scroll to the Right and select Load and Press Enter
Select FUNC: Hourly
Press the Right button to *Auto
Press the Save Button
Press SETUP button to set the time the load will turn on and off.
To enable reconnect on Float stage go to Reconn and Press the Right key again and the
word FLOAT will appear under Reconn (Float voltage can be configured in the Battery
menu).• Press the Save button to keep the changes on non volatile memory of The KID.
Refer to the battery manufacturers recommended settings.
LBD - Low Battery Disconnect:
The KID includes an adjustable Low battery Disconnect function which allows the user to set an
absolute discharge limit when using a daily function such as Night Light. This will protect the batteries
from being over discharged. This feature includes a reconnect voltage set point. Some users may opt to
have it reconnect when Float has been reached, ensuring that the batteries have been fully charged
after a LBD (Low Battery Disconnect) event. If a LBD state has occurred the blue LED will blink slowly.
To set up these parameters:
Press Menu Back button
Scroll to the right and select <Load> and press Enter
37 | Page 1 0-268-1 REV T