MNXFLEX Specifications
VOLTAGE
600/1000 Volts
TEMPERATURE
105°C Dry, 75°C Wet
Cobra Part
Number
Size
Stranding
*
Insulation Nominal OD
UL Style
***
AMPS
**
Cable Weight
AWG IN IN LBs/MFT
A2006B 6 266 X 30 0.060 0.342 1232-1283-10269 118 136
A2004B 4 420 X 30 0.060 0.386 1232-1283-10269 157 189
A2002B 2 665 X 30 0.060 0.446 1232-1283-10269 213 292
A2001B 1 836 X 30 0.080 0.520 1232-1284-10269 246 350
A2110B 1/0 1064 X 30 0.080 0.575 1232-1284-10269 291 450
A2120B 2/0 1330 X 30 0.080 0.610 1232-1284-10269 336 551
A2130B 3/0 1672 X 30 0.080 0.685 1232-1284-10269 392 672
A2140B 4/0 2109 X 30 0.080 0.745 1232-1284-10269 454 820
AT250MB 250 MCM 2527 X 30 0.100 0.835 1284-1339-10269 510 962
A1350MB 350 MCM 3458 X 30 0.100 0.965 1284-1339-10269 638 1,280
A1530MB 500 MCM 5054 X 30 0.100 1.130 1284-1339-10269 784 1,868
A1750MB 750 MCM 7448 X 30 0.115 1.380 1284-10269 951 2,719
*Extra flexible conductor with soft drawn bare copper to ASTM Specifications B172. Also available in
tinned copper.
**The 105°C cable ampacities are adapted from ICEA P-54-440/NEMA WC51-86(R1991). The
ampacities are provided for informational purposes only. Acceptance of these values by any governing
authority is the responsibility of the end user. Ampacities are based on a single conductor, in free air, at
30°C ambient air temperature.
***6 thru 2 AWG also UL1337, 1 thru 4/0 also UL 1338.
***6 thru 4/0 AWG also UL 10070.
1/0 thru 750MCM "CT" approved 1/0 thru 500MCM FT4 rated