Operation Manual

1) Air extraction and recirculation mode
with conversion kit DUU 150 if the air is
to be directed upwards out of the wall
unit.
2) Trim the wall unit carcase so that it is
38 mm shorter than the wall unit door.
3) Installation is also possible in a 600
mm wide unit.
4) The exhaust socket can also be fitted
at the back.
5) After installation the wall unit can be
fitted with an interim panel. If this is
done make sure that the slots for the
grease filters and the charcoal filters
remain easily accessible.
6) If the wall unit has a base, openings
must be provided to enable adjustment
of the retaining force of the deflector
plate. For example:
– The wall unit has side sections, as
shown.
– The cooker hood is installed in a
600 mm wide wall unit with units at
either side.
When measuring for the height of the
wall housing unit and the cut-out,
account must be taken of any
accessories fitted, e.g. silencer, XKM
module.
Safety distance between hob and
cooker hood (S)
The following minimum safety
distance must be maintained
between the top of the cooker/hob
and the bottom of the cooker hood
unless a greater distance is
specified by the manufacturer of the
cooker or hob:
Cooking appliance Distance
S
Electric hob 450 mm
Open Grill 650 mm
Deep fat fryer (electric) 650 mm
Multi-burner gas hob with
a maximum total output of
12.6 kW, no burner
exceeding 4.5 kW.
650 mm
Multi-burner gas hob with
a total output of more than
12.6 kW, or a multi-burner
gas hob where one burner
exceeds 4.5 kW.
760 mm
Single gas burner with a
maximum output of 6 kW.
650 mm
Single gas burner with
output exceeding 6 kW.
760 mm
See "Warning and Safety"
instructions for further information.
Appliance dimensions
25