Operating instructions
Table Of Contents
- Contents
- Description of the machine 4
- Guide to the machine 6
- Warning and safety instructions 11
- Opening and closing the door 16
- Automatic mobile unit recognition (Optional) 17
- Areas of application 21
- Dispensing liquid chemical agents 30
- Operation 34
- Data transfer 39
- Maintenance 40
- Periodic checks 40
- Process validation 41
- Routine checks 41
- Cleaning the filters in the wash cabinet 42
- Sprüharme reinigen 44
- Cleaning the control panel 45
- Cleaning the front of the machine 45
- Cleaning the wash cabinet 45
- Cleaning the door seals 45
- Protein test 45
- Mobile units, modules and inserts 46
- Printer (optional) 47
- After sales service 48
- Converting the type of heating 49
- Electrical connection 50
- Plumbing 51
- Technical data 52
- Special features - OXIVARIO 53
- Disposal of your old appliance or machine 55

All electrical work must be carried
out by a suitably qualified and
competent person in accordance
with local and national safety
regulations (BS 7671 in the UK).
–
Connection should be made via a
suitable isolator with an on-off switch
which is easily accessible for
servicing after the machine has been
installed.
–
For extra safety it is advisable to
install a residual current device
(RCD) with a trip current of 30 mA
(in accordance with DIN VDE 0664,
VDE 0100 Section 739).
– Check that the phase rotation is
correct when connecting the
machine. Failure to do so could have
an adverse effect on the circulation
pump and impair the wash quality.
– Equipotential bonding should be
carried out.
–
For technical data see data plate or
wiring diagram supplied.
The machine must only be operated
with the voltage, frequency and fusing
shown on the data plate.
Further notes on electrical
connection are given on the
Installation diagram supplied with
the machine.
The data plate showing relevant test
marks (VDE, DVGW etc.) is located on
the cover located behind the service
panel on the unclean side of the
machine.
The wiring diagram is supplied with
the machine.
WARNING
THIS APPLIANCE MUST BE
EARTHED
50
Electrical connection