4-6. Torch Dimensions And Weight
Ref. 801 397-A
3.0 lb (1.4 kg)
1 in.
(25 mm)
8-3/8 in.
(213 mm)
1-3/8 in.
(35 mm)
4-7. Connecting Work Clamp
Ref 803 915-A
. Do not connect work clamp to
the portion of the workpiece
that will fall when cut.
1 Work Clamp
2 Workpiece
Connect work clamp to a clean,
paint-free location on workpiece, as
close to cutting area as possible.
1
2
4-8. Electrical Service Guide For 120 VAC
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These
recommendations are for a dedicated branch circuit sized for the rated output and duty cycle of the welding power source.
50/60 Hz
Single
Phase
Input Voltage (V) 120
Input Amperes (A) At Rated Output 19
Max Recommended Standard Fuse Rating In Amperes
1
Time-Delay Fuses
2
20
Normal Operating Fuses
3
30
Min Input Conductor Size In AWG
4
12
Max Recommended Input Conductor Length In Feet (Meters)
34
(10)
Min Grounding Conductor Size In AWG
4
12
Reference: 2008 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” . See UL 248.
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amps), and UL class “H” ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.
4-9. Extension Cord Data
Input Voltage
Input Power
Phase
Hertz Conductor Size Max. Cord Length
120 V 1 50/60 12 AWG 50 ft (15 m)