4-5. Stick DCEP (Direct Current Electrode Positive) Connections
! Turn off power before mak-
ing connections.
1 Negative (−) Weld Output
Terminal
Connect work lead to negative weld
output terminal.
2 Positive (+) Weld Output
Terminal
Connect electrode holder to posi-
tive weld output terminal.
2
1
4-6. Electrical Service Guide
. Actual input voltage cannot exceed -10% of minimum, or +10% of maximum input voltages indicated in table.
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-
tions are for a dedicated circuit sized for the rated output and duty cycle of the welding power source.
In dedicated circuit installations, the National Electrical Code (NEC) allows the receptacle or conductor rating to be less than the rating
of the circuit protection device. All components of the circuit must be physically compatible. See NEC articles 210.21, 630.11, and
630.12.
Input Voltage (V)
Three-Phase, 40% Duty Cycle
380 − 440 +/− 10%
Input Amperes (A) At Rated Output 16
Max Recommended Standard Fuse Rating In Amperes
1
Time Delay Fuses
2
20
Normal Operating Fuses
3
25
Min Input Conductor Size In mm
2
(AWG)
4
2.5 (14)
Max Recommended Input Conductor Length In Meters (Feet) 45 (149)
Min Grounding Conductor Size In mm
2
(
AWG)
4
2.5 (14)
Reference: 2011 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” . See UL 248.
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amps), and UL class “H” ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.15(B)(16). If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable