! Installation must meet all National and
Local Codes − have only qualified per-
sons make this installation.
! Disconnect and lockout/tagout input
power before connecting input con-
ductors from unit. Follow established
procedures regarding the installation
and removal of lockout/tagout
devices.
! Always connect green or green/yellow
conductor to supply grounding termi-
nal first, and never to a line terminal.
See rating label on unit and check input volt-
age available at site.
For Three-Phase Operation
1 Input Power Cord.
2 Disconnect Device (switch shown in the
OFF position)
3 Green Or Green/Yellow Grounding
Conductor
4 Disconnect Device Grounding Terminal
5 Input Conductors (L1, L2 And L3)
6 Disconnect Device Line Terminals
Connect green or green/yellow grounding
conductor to disconnect device grounding ter-
minal first.
Connect input conductors L1, L2, and L3 to
disconnect device line terminals.
7 Over-Current Protection
Select type and size of over-current protec-
tion using Section 4-6 (fused disconnect
switch shown).
Close and secure door on disconnect device.
Follow established lockout/tagout procedures
to put unit in service.
4-7. Connecting 3-Phase Input Power (Continued)
4-8. Connecting To 3-Phase Engine Generator w/400 Volt Output
Installation must meet all National and Local Codeshave only qualified persons make this installation.
. Obtain a 400 volt plug that matches the receptacle on the engine generator. Install the plug on the cord of the welding power source according
to the plug manufacturer’s instructions.
Generator Requirements
Engine generator must provide the correct input amperage (see Section 4-6).
Frequency must be between 50 and 60 Hz
NOTICE − Make sure welding power source is off during engine generator start-up. Do not turn on the welding power source until the generator has
reached normal operating speed.