Instruction manual
LIQUIDRANGER READ ONLY REGISTERS
When a Port Initialization configures a BIC-II product port to suit a LiquidRanger, the product data registers
are assigned as follows.
Status Registers 
LiquidRanger Status registers (read only) indicate the general health of the Milltronics product (and process
monitored). Port 1 Status registers range from 40001 to 40120, corresponding to the AiRanger IV points of
measure 1 to 60. Registers 40001 and 40002 apply to point 1, 40003 and 40004 to point 2, etc.
For instruction purposes, only the point 1 status registers are shown. 
REGISTER # BIT # DESCRIPTION
40001 15 In service
14 Scanned once
13 New reading 
12 On priority
11 Damping
10 Filling bit value 0 = False
 9 Loss of Echo bit value 1 = True
 8 Fail-safe expired
 7 High High alarm
 6 High alarm
 5 Low alarm
 4 Low Low alarm
 3 High High acknowledge
 2 High acknowledge
 1 Low acknowledge
 0 Low Low acknowledge
40002 15 Battery
14 Reserved
13 Reserved
12 Reserved
11 Reserved
10 Reserved
 9 Decimal place (HI)
 8 Decimal place (LO)
 7 Reserved
 6 Reserved
 5 Reserved
 4 Reserved
 3 Reserved
 2 Reserved
 1 Reserved
 0 Reserved
PL-371 9 – 11