System information
APPENDIX
805 Invalid probe setup
Input file does not start with a comment containing three asterisks. Also, the
following three blocks should be X, Y, Z, or Y, X, Z depending on scan plane.
806 Scan origin expected
Multiple pick segment started without defining the start of the scans within that
segment.
807 Probe file not found
Could not find the selected input file.
808 Setup not selected
Tried to probe without selecting both the input file and the output mode from the
probe setup screen.
809 Bad Z limits encountered
The max Z height is less than the max Z depth value.
810 Stuck digitizing probe
Digitizing may have reached max Z height and part contact is still detected. If the
probe is not actually touching the part, the probe may require maintenance. If it is
touching the part, then the part has to be lowered or the max Z height should be
increased.
812 Input out of range
900 RS232 overrun error (The system sending data may not have the same baud
rate as the CNC.)
Check RS-232 baud rate parameter in PARMS-CTRL.
901 RS232 parity error (The system sending data may not have the same parity as
the CNC.)
Check RS-232 parity parameter in PARMS-CTRL.
902 RS232 framing error (Remote system and CNC may not have the same line
settings or a loose cable.)
Check line settings in PARMS-CTRL for baud rate, parity, and stop bits.
903 RS232 break detected (RS232 cable may be loose.)
Check cabling and connectors for good contact.
950 Obsolete controller software for this system
951 Obsolete acroloop software for this system
952 Obsolete keyboard software for this system