Instruction manual

Page 2 XPS/XCT Transducers– INSTRUCTION MANUAL 7ML19981AK01
General Guidelines
XPS/XCT Series - Certificate SIRA 99ATEX5153X
This equipment may be used in hazardous areas associated with all gases with
temperature classes T1, T2, T3 and T4 for the XPS series (XPS-10, XPS-15, XPS-30 and
XPS-40) and T1, T2 and T3 for the XCT series (XCT-8 and XCT-12). The XPS series is only
certified for use in ambient temperatures in the range of - 40°C to 95°C and the XCT
series is only certified for use in ambient temperatures in the range of -40°C to 145°C.
Neither should be used outside of their respective temperature ranges.
Installation shall be carried out in accordance with the applicable code of practice, and
by suitably trained personnel.
These devices should only be supplied from a circuit containing a suitably-rated fuse that
has a breaking capacity of 4000A. This fuse is included in Siemens Milltronics’
transceivers.
Repair of this equipment shall be carried out in accordance with the applicable code of
practice.
The certification of this equipment relies on the following materials used in their
construction:
Manual override can be accomplished by using the disconnect switch provided in the
building installation of the associated controller.
XPS D Series - Certificate SIRA 01ATEX5262X
This equipment may be used in all hazardous dust zones with all conductive and non-
conductive dusts. The Type XPS-10D, XPS-15D, XPS-30D and XPS-40D Series transducers
have a maximum surface temperature of 135°C (275°F) (Temperature Class T4). These
units are certified for use in ambient range of -40 to 95°C (-40 to 203°F). The transducers
should not be used outside this temperature range. The XPS-10D, XPS-15D, XPS-30D and
XPS-40D Ultrasonic Transducers must be installed so the face of the transducer is not
substantially subjected to light.
Installation shall be carried out in accordance with the applicable code of practice, and
by suitably trained personnel.
WARNING: Materials of construction are chosen based on their
chemical compatibility (or inertness) for general purposes. For exposure to
specific environments, check with chemical compatibility charts before
installing.
Material XPS Series XCT Series
Enclosure Kynar®
1
710
1.
Kynar®is a registered trademark of ELF Atochem.
Durapot®is a registered trademark of Cotronics Corporation.
Kynar®710
Encapsulant Stycast LA-9823-76 Durapot® 861-F3 & 864