5.2. A Single PC System
In this example the PC is a Server station fed by an M359-1 UPS. The specific Server
in this example consumes 500W (including all auxiliary equipment that is fed by the
UPS; like screen, printer, communication (LAN) hardware, etc.) and takes 2 minutes
to shut down in an orderly fashion. We will assume that the system in this example
requires an early warning of about 5 minutes before actual shutdown is initiated.
5.2.1. Calculating the Required Battery Thresholds.
From the "M359-1 Holdup Time Vs Power" plot, the M359-1 can support a
500W load for 35 minutes.
Power Line
PC Server
LAN