User`s manual
MPS Doc: UPS_AS_UM  Rev (-)  May 23, 2012  Page 32 of 38 
6.2. Over Temperature Shutdown 
If configured, the Application may trigger the Shutdown Procedure when the UPS is 
about to shut down by its Over Temperature protection. 
Notes: 
1.  An Over Temperature failure is a rare event, triggered by a combination of abnormal 
conditions such as above spec ambient temperature, a prolong overload, a blocked 
cooling air path, a failed cooling fan, etc. The Over Temp threshold is set sufficiently 
high such that it eliminates false trips, but once it does trip, in order to prevent 
irreversible damage, the UPS will shut itself off within 3 minutes. 
2.  If the system cannot tolerate an un-orderly shutdown even in the unlikely event of an 
Over temp failure, then the settings of "Windows Shutdown Delay" + the time it 
actually takes your PC to shutdown should be shorter than 3 minutes. If this is 
impossible, you may need to disable the Over Temp protection by driving the UPS to 
Battle Mode (see the UPS User Manual "M359_SNMP_UM"). But caution!!! When 
the in Battle Mode, an Over Temp failure may result in an irreversible damage to 
the UPS!!!  
If the Application detects that the UPS is about to shutdown due to an Over 
Temperature (and the Over Temperature Shutdown is enabled), the battery icon 
will change to Red and a message balloon will inform the user about the imminent 
shutdown: 
And the following Windows shutdown window will be displayed: 
Windows XP shutdown dialog box 
Windows 7 shutdown dialog box 










