User`s manual
MPS Doc: UPS_AS_UM  Rev (-)  May 23, 2012  Page 4 of 38 
2. Installation and Configuration 
2.1. UPS Configuration 
2.1.1. In order to enable the Application, the UPS must be configured to SNMPv3 
protocol (not the default UPS settings). 
For UPS configuration instructions refer to Milpower document: 
"M359_Console_UM”. (For an alternative configuration procedure that 
does not require special software; refer to Milpower document: 
"M359_CLI_UM"). Both documents are available on Milpower's Website: 
"www.milpower.com". 
2.1.2. The SNMPv3 Standard Security Protocol contains two Usernames and two 
Passwords. In order to enable the Application, the two Usernames must be 
identical to each other and the two Passwords must be identical to each 
other. 
2.1.3. The Password length should be at least eight (8) characters long. 
2.1.4. In order to support a UPS Shutdown by the Application, the UPS's firmware 
version must be 2.02.17 or higher. Refer to Milpower document 
"M359_FUP_1" (available on www.milpower.com) on how to upgrade the 
UPS firmware. 