Manual

PRELIMINARY SPEC SHEET
Diesel Generator Set – 3,000 ekW – 60 Hz
PRELIMINARY 1 of 5 2/6/2006
Information contained in this publication may be considered confidential. www.cat-ElectricPower.com
Discretion is recommended when distributing.
C175-16 Standby
3,000 ekW / 3,750 kVA- 60 Hz – 1800 RPM
480 – 12,470 – 13,200 – 13,800 and 4,160 Volts
System Standard
Air Inlet
Single element canister type air cleaners
Service indicator
Cooling
Radiator with guard (43
o
C ambient temperature)
Coolant drain line with valve
Caterpillar Extended Life Coolant
Exhaust
Dry exhaust manifold
Flanged faced outlets (ANSI / DIN)
Fuel
Secondary fuel filters
Fuel priming pump
Flexible fuel lines
Fuel cooler (optional)
Generator
IE (LV) and PMG (MV, HV)
Class H insulation
Class H temperature (150
o
C rise)
CDVR voltage regulator
Reactive droop
Bus bar connections
Winding temperature sensors std PM @ 480 Volt (opt for LV)
Anti-condensation space heaters (opt for LV)
Bearing temperature sensors – option (opt for LV)
Governing System
Caterpillar ADEM
TM
A4 speed control governor
Control Panels
EMCP 3 (package mounted)
Lube System
Lubricating oil and filter
Oil drain line with valves
Fumes disposal
Gear type lube oil pump
Mounting
Rubber, anti-vibration mounts (shipped loose)
Starting/Charging
24 Volt starting motor(s)
45 Amp charging alternator
Batteries with rack and cables
Battery disconnect switch
General
Right-hand service
Paint – Caterpillar Yellow except rails and radiators gloss black
SAE standard rotation
Flywheel and flywheel housing – SAE No. 0
Note For any additional options, consult the factory
Materials and specifications are subject to change without notice. © 2005 Caterpillar
CAT, CATERPILLAR, their respective logos and “Caterpillar Yellow”, as well as corporate and product All Rights Reserved.
Identify used herein, are trademarks of Caterpillar and may not be used without permission. Printed in U.S.A.