LEHE7416-00
FEATURES DESCRIPTION
C27 SUB-BASE
FUEL TANK BASE
Griffin
Diesel Generator Set
750-900 kVA 50 Hz
650-800 kW 60 Hz
UL 142 listed
Designed and built to comply with NFPA 30,
37, 110
Tank design provides capacity for thermal
expansion of fuel
Direct reading fuel level gauge
Fuel supply dip tube is positioned so as not
to pick up fuel sediment
Fuel return and supply dip tubes are separated
by an internal baffle to prevent recirculation
of heated return fuel
Fuel fill – 101.6 mm (4 in), lockable flip top cap
Primary tank level detection switch in
containment basin
Primary and secondary tanks are leak tested
at 20.7 kPa (3 psi) minimum
Welded steel containment basin (minimum
of 110% of primary tank capacity)
Interior tank surfaces coated with a solvent-
based thin-film rust preventative
Heavy gauge steel gussets suitable for lifting
package
Gloss black polyester alkyd acrylic enamel
exterior paint over epoxy based primer
Primary tanks are equipped with customer
connections for remote fuel transfer, return
and vent
Dual wall, secondary containment
Heavy construction 6 mm (0.24 in) steel plate
side channels and 4 mm (0.16 in) sheet steel
tank design
Rear and right side stub-up access
Emergency vents on primary and secondary
tanks are sized in accordance with NFPA 30
Leak detection switch
Compatible with enclosures (weather
protective and sound attenuated)
The sub-base fuel tank mounts below the
generator set wide base
OPTIONS
Manual fuel transfer pump
Low fuel level switch (alarm and shutdown)