ELECTRICAL SPECIFICATIONS
Electrical Specifications
Rated Output
Model
VA Watts
Freq.
HZ
Input
VAC/A
Output
VAC/A
Battery
System
VDC
Back Up
Full Load
Time
(Min)
Half Load
Max Heat
Dissipation
BTU/HR
AT650 650 455 60 120/6.0 120/5.4 24 6 15 311
GS650 650 455 50 220/3.3 220/3.0 24 6 15 311
AT800 800 560 60 120/7.4 120/6.7 48 8 20 382
GS800 800 560 50 220/4.0 220/3.6 48 8 20 382
AT1200 1200 840 60 120/11.1 120/10.0 48 7 18 573
GS1200 1200 840 50 220/6.1 220/5.5 48 7 18 573
AT1600 1600 1120 60 120/14.8* 120/13.3* 72 8 20 765
GS1600 1600 1120 50 220/8.1 220/7.3 72 8 20 765
AT2300 2300 1610 60 120/21.3 120/19.2 72 4 10 1099
GS2300 2300 1610 50 220/11.6 220/10.5 72 4 10 1099
* Input/Output specifications above for model AT1600 are applicable when a 20-ampere power
plug (NEMA 5-20P) is utilized (non-standard). For a NEMA 5-15P plug (standard), derate input to
120VAC/12 Amperes and derate output in "AC Normal" mode only to 120VAC/10.8 Amperes.