Enterprise Plus Series UPS User's Manual
English 1. Introduction 2 2. Controls and Indicators 6 3. Installation 9 4. Operation 15 5. Troubleshooting 18 6. Replacing the Battery 19 7. Obtaining Service 22 8. Specifications 23 9. Configurable Parameters & Settings 25 10. Limited Product Warranty 26 A1.
English Thank you for purchasing this power protection product. It has been designed and manufactured to provide many years of trouble free service.
This symbol indicates "Equipment Grounding Conductor" CAUTION! Connect the UPS to a two pole, three wire grounding AC wall outlet. The receptacle must be connected to the appropriate branch protection (circuit breaker or fuse). Connection to any other type of receptacle may result in a shock hazard and violate local electrical codes. Do not use extension cords, adapter plugs, or surge strips.
English NOTICE: This equipment has been tested and found to comply with the limits for a Class B computing device in accordance with the specifications in Subpart J of Part 15 of FCC Rules and the Class B limits for radio noise emissions from digital apparatus set out in the Radio Interference of the Canadian Department of Communications. These limits are designed to provide reasonable protection against such interference in a residential installation.
As a general policy, we do not recommend the use of any of our products in life support applications where failure or malfunction of the product can be reasonably expected to cause failure of the life support device or to significantly affect its safety or effectiveness. We do not recommend the use of any of our products in direct patient care.
English CONTROL PANEL The AC normal (green) LED illuminates in a steady state when the UPS is on and operating in the AC normal mode. The AC normal LED will extinguish when operating in the Battery mode. The On-Battery (green) LED illuminates in a steady state when the UPS is operating in the Battery mode. The On-Battery LED will extinguish when operating in the AC normal, Boost and Buck modes. The Boost (yellow) LED illuminates in a blinking state when the UPS is operating in the Boost mode.
The Battery Capacity Bar Graph (Battery mode only) operates as follows: LED #90: >90% battery capacity (red/yellow) LED will be yellow and illuminated until the battery’s capacity drops below 80% capacity and then it will extinguish. LED #70: >70% battery capacity (green/yellow) LED will be yellow and illuminated until the battery’s capacity drops below 60% capacity and then it will extinguish.
REAR PANEL English 1. 2. 3. 4. 5. 6. 7. The RS232 Communications Interface Port is for UPS monitoring and control. The USB Communications Interface Port is for UPS monitoring and control. The RJ11 REPO (Remote Emergency Power Off) Port is for UPS control. The option slot is for option cards. The External Battery Connector is for connecting External Battery Packs. The output circuit breaker will trip in the event the load exceeds the UPS’s power rating. The Battery Backup output power receptacles.
English INSTALLATION PLACEMENT This UPS series is intended to be install in a temperature controlled environment that is free of conductive contaminants. Select a location which will provide good air circulation for the UPS at all times. Avoid locations near heating devices, water or excessive humidity, or where the UPS is exposed to direct sunlight. Route power cords so they cannot be walked on or damaged.
English CONNECTING THE BATTERIES (QUALIFIED SERVICE PERSONNEL ONLY) Please read all of the WARNINGS and CAUTIONS before attempting to connect the batteries. 1. Remove the UPS from the shipping box and set on the floor or a bench top. 2. Remove the front panel retaining screws. 3. Lay the front panel on top of the UPS. 4. Verify proper polarity. Connect the battery connectors (red and black) together. NOTE: Some sparking might occur, this is normal. 5. Re-install the front panel onto the UPS. 6.
11 English RACKMOUNT CONFIGURATION This UPS comes with mounting brackets for the standard 19" (46.5cm) rack. The mounting brackets to fit a 23" (59.2cm) standard rack are also available. The screws for mounting the UPS to the rack are not included (screw size varies with rack size). 1. Locate the mounting bracket screw holes on the side panels of the UPS, at the front of the UPS. NOTE: The mounting brackets can also be mounted in the middle of the UPS. 2.
English TOWER CONFIGURATION The tower configuration allows the user to install the UPS in the up-right position next to the tower computer. The tower brackets are provided with the UPS. WARNING: Use two or more people when installing the UPS. Use CAUTION, the UPS is extremely heavy. 1. Once the location of the UPS has been determined, place the tower brackets in the desired location. WARNING: The UPS must be installed in the proper up-right position.
13 English WALLMOUNT CONFIGURATION The wallmount configuration allows the user to mount the UPS on the wall. There is a wallmount bracket kit available for the UPS. The kit includes two wall mounting brackets, ten retaining screws, and the wallmount template. WARNING: Use two or more people when installing the UPS. Use CAUTION, the UPS is extremely heavy. The UPS's side panels have mounting bracket screw holes for attaching the wall mounting brackets. 1.
English CONNECTING YOUR EQUIPMENT Plug the equipment into the output receptacles on the rear panel of the UPS. Do not use extension cords, adapter plugs or surge strips on the output of the UPS. Ensure that you do not exceed the maximum output rating of the UPS (refer to the information label or the Electrical Specifications in this manual). CAUTION! DO NOT connect a laser printer to the output receptacles on the UPS, unless the UPS is rated 2000VA or greater.
English SYSTEM OVERVIEW This Line-Interactive UPS protects computers, internetworking, and telecommunications equipment from blackouts, brownouts, overvoltages, and surges. The AVR function continuously corrects the voltages, in-between the brownout and overvoltage transfer points (80 - 164VAC/150 - 271VAC), to a safe usable level. When the UPS is operating in the AVR mode the audible alarm will remain silent and the Boost or the Buck indicator will blink.
English SELF TEST The self test feature is useful to verify the correct operation of the UPS and the condition of the batteries. With the UPS in the AC normal mode, press and hold the On/Off/Test Button for four beeps, then release the button. The UPS will perform a ten-second self test. During the self test, the UPS will switch to battery power and the On-Battery LED will illuminate and the audible alarm will sound.
ALARMS ON BATTERY When the UPS is operating on the batteries, the On-Battery LED will illuminate and the audible alarm will sound once every ten-seconds. The alarm will stop once the UPS returns to the AC normal mode. LOW BATTERY WARNING The UPS will sound two beeps every five-seconds when the battery reserve runs low. This condition will continue until AC returns or the UPS shuts down from battery exhaustion.
English Symptom Possible Cause UPS will not turn on On/Off/Test button not pushed UPS operates in Input AC circuit breaker is battery mode only, tripped even though there is normal AC present Fault LED is UPS has detected an illuminated internal fault Site Wiring Fault Incorrect service wiring LED is illuminated The AC normal The UPS is being LED is illuminated, controlled via its but there is no out- communications port put UPS does not provide expected runtime The batteries may be weak or at the end o
English REPLACING THE BATTERY (QUALIFIED SERVICE PERSONNEL ONLY) This UPS has an easy to replace hot-swappable batteries. Please read all of the WARNINGS and CAUTIONS before attempting to service the batteries. NOTE: If there is a power interruption while replacing the hot-swappable batteries, with the UPS on, the load will not be backed up. WARNING! This Uninterruptible Power Supply contains potentially hazardous voltages. Do not attempt to disassemble the UPS beyond the battery replacement procedure.
English CAUTION: Replace batteries with the same number and type as originally installed in the UPS. These batteries have pressure operated vents. These UPSs contain sealed non-spillable maintenance-free lead acid batteries. Model # Battery Qty/Rating E750RM2U E1000RM2U E1500RM2U E2000RM2U E3000RM2U E1500RMT2U E3000RMT2U 3-12V7.2Ah 3-12V8.5Ah 6-12V7.2Ah 6-12V8.5Ah CSB GP 1272 F2 HR 1234W F2 GP 1272 F2 HR 1234W F2 Part # Panasonic LC-R129 LC-R129 LC-R127.2 LC-R127.
FIG. 3 FIG. 4 21 English 8. Remove the two retaining screws for the battery retaining bracket. (FIG. 3) 9. Remove the battery retaining bracket. (FIG. 3) 10. Disconnect the Battery connectors (red and black). (FIG. 4) 11. Grasp the battery pull tab and gently pull the battery module out of the UPS and set on the floor. (FIG. 4) NOTE: Use Caution, the battery module is heavy. 12. Disconnect the battery positive (red) wire. 13. Disconnect the battery negative (black) wire. 14.
English IF THE UPS REQUIRES SERVICE 1. Use the TROUBLESHOOTING section to eliminate obvious causes. 2. Verify there are no circuit breakers tripped. A tripped circuit breaker is the most common problem. 3. Call your dealer for assistance. If you cannot reach your dealer, or if they cannot resolve the problem call or fax the Technical Support department at the following numbers; Voice phone (972) 446-7363, FAX line (972) 446-9011 or visit our Web site at www.minutemanups.com the "Discussion Board".
English SYSTEM SPECIFICATIONS Model Number E750RM2U E1000RM2U E1500RM2U E3000RM2U E2000RM2U E1500RMT2U E3000RMT2U Line-Interactive, Sine Wave Topology Maximum Power Capacity 750VA 600W 1000VA 800W 1500VA 1200W 2000VA 1760W 3000VA 2560W INPUT Number of Phase Single (1∅ 2W +G) Nominal Voltage 120VAC (208VAC) Acceptable Input voltage 0 - 165VAC (0 - 300VAC) 80 - 164VAC (150 - 271VAC) Voltage Range Frequency Limits 50 or 60 Hz, +/-6Hz, autosensing Low Voltage Transfer Point 80V (150V) reset
BATTERY SYSTEM Battery Type Sealed, Non-Spillable, Maintenance Free, Value Regulated Lead Acid English Typical Recharge Time 8-hours from total discharge Typical Battery Life 3-5 years, depending on discharge cycles and ambient temp System Voltage 36VDC 36VDC 36VDC 72VDC 72VDC 3-12V7.2Ah 3-12V7.2Ah 3-12V8.5Ah 6-12V7.2Ah 6-12V8.
English (These items may require optional software or hardware) Factory Default UPS ID Enterprise Plus Series Function Battery install date Battery life in days User Choices Description Up to 64 charac- Use this function to uniquely ters to define the identify the UPS in your network configuration UPS Date of Date of battery manufacture replacement month/day/year XX/XX/XXXX Up to 5 1826 characters Enter the current date when replacing batteries At first battery replacement, reset to reflect actual n
English Para Systems Inc. (Para Systems) warrants this equipment, when properly applied and operated within specified conditions, against faulty materials or workmanship for a period of three years from the date of purchase. For equipment sites within the United States and Canada, this warranty covers repair or replacement of defective equipment at the discretion of Para Systems. Repair will be from the nearest authorized service center. Replacement parts and warranty labor will be borne by Para Systems.
LIMITED PRODUCT WARRANTY EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL PARA SYSTEMS BE LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Specifically, Para Systems is not liable for any costs, such as lost profits or revenue, loss of equipment, loss of use of equipment, loss of software, loss of data, cost of substitutes, claims by third parties, or otherwise.
A1. DECLARATION OF CONFORMITY English Application of Council Directive(s): 89/336/EEC, 73/23/EEC Standard(s) to which Conformity is declared: EN55022, EN55024 EN61000-6-1, EN61000-6-3 EN61000-4-5 Manufacturer’s Name: Para Systems, Inc.
English Notes: 29
Notes: English 30
Para Systems, Inc. 1455 Lemay Dr. Carrollton, TX 75007 Phone: 1-972-446-7363 Fax: 1-972-446-9011 Internet: minutemanups.com UPS Sizing: sizemyups.