Thank you for purchasing this power protection product. It has been designed
and manufactured to provide many years of trouble free service. Please read
this manual before installing your Encomapss BPXL Battery Pack series, models
BP24XL, BP48XL, BP72XL as it provides important information that should be
followed during the installation and the maintenance of the Battery Pack allow-
ing you to correctly set up your system for the maximum safety and perfor-
mance. Included is information on customer support and factory service, if it
is required. If you experience a problem with the Battery Pack please refer to
the Obtaining Service in this manual to correct the problem or collect enough
information so that the Technical Support Department can assist you.
SAVE THESE INSTRUCTIONS - This manual contains important instructions
that should be followed during the installation and the maintenance of the
Battery Pack and the batteries.
CAUTION! The maximum ambient operating temperature for this Battery Pack
series is 40°C (“0 ~ 40°C” for Ambient Operation).
The external vents and openings on the Battery Pack are provided for ven-
tilation. To ensure reliable operation of the Battery Pack and to protect the
Battery Pack from overheating, these vents and openings must not be blo-
cked or covered. Do not insert any object into any of the vents or opening
that may hinder the ventilation.
Install the Battery Pack in a well ventilated area, away from excess moistu-
re, heat, dust, flammable gas or explosives.
Leave adequate space (at least 20cm) in the front and at the rear of the
Battery Pack for proper ventilation.
Do not install the Battery Pack with its front or rear panel facing down at
any angle.
Do not install the Battery Pack laying on its side panels.
Before usage, you must allow the Battery Pack to adjust to room temper-
ature (20°C~25°C or 68°F~77°F) for at least one hour to avoid moisture
condensing inside the Battery Pack.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS !
CONSIGNES DE SÉCURITÉ IMPORTANTES
SAUVEGARDEZ CES CONSIGNES!
Veuillez lire ce manuel avant l'installation de l'onduleur modèles BP24XL,
BP48XL, BP72XL. Il contient de l'information importante qui doit être respectée
au cours de l'installation et de l'entretien de l'onduleur et des batteries. Cette
information vous permettra de correctement installer le système pour atteindre
son rendement maximum en toute sécurité.
Chapter 1: Introduction
WARNING: Risk of Electrical Shock. Hazardous live parts inside these
Battery Packs are energized from the battery.
WARNING: These Battery Packs contains potentially hazardous voltages.
Do not attempt to disassemble the Battery Pack beyond the battery replace-
ment procedure. These Battery Packs contains no user serviceable parts.
Repairs and battery replacement must be performed by QUALIFIED SER-
VICE PERSONNEL ONLY.
CAUTION! This Battery Pack series is ONLY intended to be installed in an
indoor temperature controlled environment that is free of conductive contami-
nants. This Battery Pack series is not intended for use in a computer room as
defined in the Standard for the Protection of Electronic Computer/Data Pro-
cessing Equipment ANSI/NFPA 75.
CAUTION! DO NOT install these Battery Packs with its front or rear panel
facing down at any angle or laying on its side panels.
CAUTION! To de-energize the Battery Pack:
1. If the UPS is On press and release the Off button.
2. Disconnect the UPS from the wall outlet.
3. Turn off the DC breaker on the rear panel of the Battery Pack.
4. Disconnect the battery cable from the rear panel of the UPS.
5. To de-energize the Battery Pack completely, disconnect the batteries.
WARNING: Qualified Service Personnel ONLY must perform the Installa-
tion and Servicing of these Battery Packs. MINUTEMAN accepts no liabilities
and is not limited to: injury to the User or Service Personnel, or damages to;
the Battery Pack, or the connected equipment caused by the incorrect instal-
lation or servicing of the Battery Pack and/or UPS system. These Battery
Packs MUST be operated with their respective UPS models, see the table
below:
UPS
BP BP72XL
EC3000LCD
BP24XL BP48XL
EC1000LCD EC1500LCD
EC2000LCD