User Manual

19
18
WEAK/BAD BATTERY
The UPS automatically tests the battery’s condition and will illuminate the Weak/
Bad Battery icon and sound the alarm. This alarm will be repeated until the
batteries pass a self test. If the battery is weak, bad or disconnected, the
Weak/Bad Battery icon will illuminate and the alarm will beep three times every
five-minutes until the battery is reconnected or replaced. It is recommended
that the UPS be allowed to charge overnight before performing a battery test to
confirm a Weak/Bad Battery condition.
OVERLOAD
When the amount of load attached to the UPS exceeds 110% of its power
rating; the Overload icon will flash Off and On, all of the LEDs in the Load Level
Bar Graph will be illuminated and the UPS will sound a constant alarm. This
alarm will remain on until the excess load is removed or the UPS’s self protec-
tion circuit shuts the UPS down. If the UPS shuts down because of an Over-
load condition, the UPS must perform an Inverter function or a Self Test to
clear the Overload Alarm.
ALARMS
ON BATTERY
When the UPS is operating on the batteries, the On-Battery icon will illuminate
and the audible alarm will sound once every ten-seconds. The alarm will stop
once the UPS returns to the AC normal mode.
LOW BATTERY WARNING
The UPS will sound two beeps every five-seconds when the battery reserve
runs low. This condition will continue until AC returns or the UPS shuts down
from battery exhaustion.
UPS FAULT
When the UPS detects a hardware fault, the Fault icon will illuminate and the
UPS will sound a constant alarm. The fault condition, in some instances, may
be reset by turning the UPS off and then on.
RJ11 REPO (Remote Emergency Power Off) PORT
Connect one end of the RJ11 cable to the REPO port and the other end of the
RJ11 cable to the EPO switch. In the AC or the Battery mode short pin4 to
pin5 for approximately 0.5-seconds to shutdown the UPS. The UPS must be
turned off and then back on again to restart the UPS. The LCD will display
EPo for this function.
NOTE: The LCD backlight will illuminate for 1-minute when the UPS switches
to the Battery mode. When the UPS has an event and/or an error code the
LCD backlight will turn on and remain on to alert the user that an event has
occurred.
Error Code: E01. UPS is shut-
down.
Symptom / Error Code
Cause / What To Do
Press the On/Off/Test button and release after one beep.
UPS will not turn on.
Reset the input circuit breaker by pressing the plunger back in. If
the input circuit breaker trips after UPS restarts, reduce the load on
the UPS.
UPS operates in battery mode
only, even though there is AC
present.
The AC normal icon is illumi-
nated, but there is no output.
Disconnect the computer cable from the UPS, press the On button.
If UPS works normally, the software has control of the UPS.
Charge the batteries for 8-hours and retest. If the runtime is still
less than expected, the batteries may need to be replaced.
UPS does not provide
expected runtime.
The AC Normal icon is blink-
ing.
The UPS is in either the Boost or the Buck mode. It is performing
its intended function.
The UPS has an internal problem. Call for service.
Fault icon is illuminated and a
constant alarm.
Error Code: E02. Overload
icon is illuminated and a con-
stant alarm.
Check the specifications and remove part of the load. If the UPS
shuts down because of an Overload, the UPS must perform an
Inverter function or a Self Test to clear the Overload Alarm.
The UPS has detected a short-circuit on its output. Check the at-
tached load.
Error Code: E03. UPS is shut-
down.
The internal or ambinet temperature has exceeded the temperature
ratings. Check the specifications.
Error Code: E04. Input Over
Current Protection Warning.
Check the specifications and remove part of the load.
Error Code: E11: Inverter/Out-
put Failure Shutdown.
The UPS has an internal fault. Call for service.
Error Code: E12. DCBUS
OVP Shutdown.
The UPS has an internal fault. Call for service.
Error Code: E13. Fan Fail
Warning.
The fan has either failed or has stopped due to exessive dirt. If the
fan has failed, call for service. If the fan is dirty, use a can of "Canned
Air" to clean the fan.
Error Code: E14. Charger Fail-
ure Warning.
The charger has failed, call for service.
Error Code: E16. SWF icon
is illuminated.
Have a qualified electrician correct the service wiring.
Error Code: E15. Weak/Bad
Battery icon is illuminated.
Check the battery connections, charge the batteries for 8-hours
and retest, or replace the batteries.
Error Code: E17. Low
Battery Warning.
The UPS's battery reserve is low. This condition will continue until
AC returns or the UPS shuts down from battery exhaustion.
Error Code: E18. Low
Battery Capacity.
Error Code: E05. Input voltage
out of range.
One of the following Errors has occurred E06, E12, or E13. The
AVR and the Battery mode functions will not work. Call for service.
Error Code: E06. Ambient
Over Temperature Protection.
The internal temperature of the UPS has exceeded the safe oper-
ating range for the UPS. Check the specifications.
The UPS's battery capacity is low. Charge the batteries for 24-
hours.
OPTION SLOT
The option slot on the rear panel of the UPS is for option cards. Contact your
local dealer for the available option cards.