User Manual

13
12
WALLMOUNT CONFIGURATION
The wallmount configuration allows the user to mount the UPS on the wall. There is
a wallmount bracket kit available for the UPS. The kit includes two wall mounting
brackets, ten retaining screws, and the wallmount template. WARNING: Use two or
more people when installing the UPS. Use CAUTION, the UPS is extremely heavy.
The UPS's side panels have mounting bracket screw holes for attaching the wall
mounting brackets.
1. Once the location and position of the UPS has been determined, lay the UPS do-
wn flat.
WARNING: The UPS must be installed in the proper up-right position. If the UPS is
not installed in the proper up-right position the Batteries will be damaged. Once the
UPS is placed on the wall, looking at the front panel the YELLOW Battery discon-
nected label on the top cover of the UPS MUST be on your left hand side.
2. Align the mounting brackets with the mounting bracket screw holes and attach w-
ith the six retaining screws.
3. Use the template to mark the screw hole position on the wall. CAUTION, you sh-
ould always were protective gear for your hands and eyes when operating power
tools.
4. Attach the four retaining screws to the wall and make sure that all of the retaining
screws are screwed into structural material. Then clean the area of any loose m-
aterial. Do not tighten the retaining screws all the way, leave approximately 3/8" of
the retaining screws sticking out.
5. Position the UPS, so that the mounting bracket keyed holes line up with the four
retaining screws. Slide the UPS down until its resting securely on the four retai-
ning screws.
6. Tighten the four retaining screws to secure the UPS to the wall.
7. The LCD panel can be rotated to read in the up-right position. Remove the front
panel from the UPS. On the backside of the front panel, push the LCD panel out-
wards, the panel will pop out. Position the LCD panel so that it reads in the up-
right position. Re-install the front panel on the UPS.
8. The Wallmount Configuration is complete. See Connecting your Equipment.
TOWER CONFIGURATION
The tower configuration allows the user to install the UPS in the up-right position
next to a tower computer. The tower brackets are provided with the UPS. WARNING:
Use two or more people when installing the UPS. Use CAUTION, the UPS is ex-
tremely heavy.
1. Once the location of the UPS has been determined, place the tower brackets in
the desired location.
WARNING: The UPS must be installed in the proper up-right position. If the UPS is
not installed in the proper up-right position the Batteries will be damaged. Once the
UPS is placed in the tower brackets, looking at the front panel the YELLOW Battery
disconnected label on the top cover of the UPS MUST be on your left hand side.
2. Slide the UPS into the tower brackets. Make sure that the UPS is stable.
3. The LCD panel can be rotated to read in the up-right position. Remove the front
panel from the UPS. On the backside of the front panel, push the LCD panel out-
wards, the panel will pop out. Position the LCD panel so that it reads in the up-
right position. Re-install the front panel on the UPS.
4. The Tower Configuration is complete. See Connecting your Equipment.
DESKTOP CONFIGURATION
The desktop configuration allows the user to install the monitor, the computer and
the UPS in one single stack. WARNING: Use two or more people when installing the
UPS. Use CAUTION, the UPS is extremely heavy.
1. Once the location of the UPS has been determined, lay the UPS down flat on the
desk.
2. Stack the computer and then the monitor on top of the UPS. NOTE: Do not stack
the UPS on top of the computer. The UPS is heavy and may damage the other
equipment.
3. The Desktop Configuration is complete. See Connecting your Equipment.