Data Sheet

www.minutemanups.com | www.sizemyups.com
© Copyright 2013, Para Systems, Inc. Product specications are subject to change without
notice. Minuteman and Minuteman Platinum Protection Plan are registered trademarks and
EnterprisePlus, EnterprisePlus LCD, and SentryHD are trademarks of Para Systems, Inc. PN-34000470 - 5-13
EnterprisePlus LCD™ UPS Models & Specifications
Note: specications are the same for standard (RT2U) and extended runtime (RTXL2U) models except XL external battery packs
MODELS: STANDARD RUNTIME
EXTENDED RUNTIME
208V
E750RT2U
E750RTXL2U
E1000RT2U
E1000RTXL2U
E1500RT2U
E1500RTXL2U
(E1500RTXLT2U)
E2000RT2U
E2000RTXL2U
E3000RT2U
E3000RTXL2U
(E3000RTXLT2U)
Maximum Power Capacity (VA/Watts) 750/600 1000/800 1500/1200 2000/1760 3000/2560
Topology Line Interactive, True Sine Wave Uninterruptible Power Supply
Power Factor 0.8 0.8 0.8 0.88 0.853
Battery and Surge
Protected Receptacles
8 - 5-15R 8 - 5-15R
8 - 5-15R
(6 - 6-15R)
8 - 5-15/20R, 1 - L5-20R
7 - 5-15/20R, 1 - L5-30R
(6 - 6-15/20R, 1 - L6-30R)
Input Connection (with 10 ft power cord) 5-15P 5-15P 5-15P (6-15P) 5-20P L5-30P (L6-30P)
Mounting/Installation Rackmount/Tower and Wallmount
Input
Number of Phases Single (1Ø 2W +G)
Nominal Voltage•Voltage Range 120VAC (208VAC) • 80-164VAC (150-271VAC)
Frequency Range
Acceptable Input Voltage
50/60Hz +/-6Hz Autosensing
0-165VAC (0-300VAC)
Low Voltage Transfer Point 80V (150V) resets to utility power at 85V (157V) or higher
High Voltage Transfer Point 164V (271V) resets to utility power at 159V (264V) or lower
Input Protection Resettable circuit breaker
Output Non-battery Operation
Voltage Range • Voltage Regulation 120VAC: 101-136VAC • -15.8% to 11.7% (208VAC: 186-236VAC) / -10.6% to +13.5%
Frequency Range •
Efciency (Line Mode)
60Hz/50Hz ±6Hz • >93% at full load 60Hz/50Hz ±6Hz • >97% at full load
Output Battery Operation
Nominal Voltage 120/125VAC (208/240VAC)
Voltage Regulation 120VAC (208VAC) ±5% until low battery warning
Frequency ±0.1Hz unless synchronized to line
Voltage THD <5% at full rated linear load / <12% at full rated non-linear load
Dynamic Response • Transfer Time ±10% @ 100% Load change in 30 ms
Waveform True Sine wave
Overload capacity 110% for 20 seconds, 125% for 10 seconds, 150% shutdown immediately
Protection Over current, Short circuit protection and Latching shutdown
Battery System
Batter y Type Sealed, non-spillable, maintenance free, value regulated lead acid
Typical Recharge Time 8 hours from total discharge to 90%
Typical Battery Life 3-5 years, depending on discharge cycles and ambient temperature
System Voltage 36VDC 36VDC 36VDC 72VDC 72VDC
Battery Module BM0029 BM0029 BM0030 BM0031 BM0032
Runtime: Half •Full Load (minutes) 17 • 8 15 • 5 11 • 4 13 • 5 8 • 3
Surge Protection and Filtering
Surge Energy Rating (Joules) 1000J (800J)
Surge Current Capability 6500Amps total
Surge Response time 0ns(instananeous) normal mode: <5 ns common mode
Noise Filter normal and common mode EMI/RFI suppression
Audible Noise at 1 m (3 ft.) <45dBA <45dBA <45dBA <60dBA <60dBA
Environmental
Temperature: Operating • Storage +32° to +104°F (0° to 40°C) • +5° to +113°F (-15° to +45°C)
Humidity: Operating/Storage 95% non-condensing
Elevation: Operating•Storage 0 to 10,000ft. (0 to 3,000m) • 0 to 50,000ft. (0 to 15,000 m)
Physical
Size: Net (L x W x H) in (mm) 17.4 x 19.0 x 3.5 in (442.0 x 482.6 x 89.0 mm) 24.0 x 19.0 x 3.5 in (610.0 x 482.6 x 89.0 mm)
Size: Shipping (L x W x H) in (mm) 23.6 x 21.7 x 9.1 in (600.0 x 551.0 x 230.0 mm) 39.4 x 23.6 x 9.1 in (1000.0 x 600.0 x 230.0 mm)
Weight: Net
Shipping
41.2 lb (18.7 kg)
49.8 lb (22.6 kg)
44.1 lb (20.0 kg)
52.7 lb (23.9 kg)
72.1 lb (32.7 kg)
88.2 lb (40.0 kg)
78.0 lb (35.4 kg)
93.7 lb (42.5 kg)
External Battery Packs
(XL EXTENDED RUNTIME MODELS ONLY)
Battery Pack BP36RTXL BP36RTXL BP36RTXL BP72RTXL BP72RTXL
Typical Recharge Time 8 hours to 90% after full load discharge
Size: Net (L x W x H) 17.0 x 19.0 x 3.5 in (432.0 x 482.6 x 89.0 mm)
Size: Shipping (L x W x H) 23.6 x 21.7 x 9.1 in (600.0 x 551.0 x 230.0 mm)
Weight: Net • Shipping lb (kg) 56.0 lb (25.4 kg) • 66.1 lb (30.0 kg)
Regulatory Compliance (UPS and Battery Packs)
Safety and Approvals RoHS2 Directive 2011/65/EU, cUL, CE, FCC Class B
Energy Star Certication 1500, 2000, 3000VA Models Only
Warranty • Platinum Protection Three-years parts, labor, & battery (non-prorated); 5-year extended plans available • $100,000
NEW!
RoHS
2