EDBP10000T Battery Pack User's Manual Para Systems, Inc. 1455 Lemay Dr. Carrollton, TX 75007 Phone: 1-972-446-7363 Fax: 1-972-446-9011 Internet: minutemanups.com UPS Sizing: sizemyups.
English TABLE OF CONTENTS 1. Introduction 2 2. Controls 6 3. Installation 7 4. Replacing the Battery 11 5. Obtaining Service 15 6. Specifications 16 7.
English 1. INTRODUCTION Thank you for purchasing this power protection product. It has been designed and manufactured to provide many years of trouble free service. IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS ! tion of these Battery Packs, with the UPS equipment and the connected equipment, the user must ensure that the combined sum of the AC leakage current does not exceed 3.5mA.
English 1. Cut the banding straps and discard them. 2. Lift the cardboard carton upwards off the packaging crate. 3. Cut the banding strap. Remove the ramp and the corner post. Remove the side blocks. Use a screwdriver to remove the end stop. 4. Place the ramp against the pallet. Remove the metal bracket and insert as shown to secure the ramp to the pallet. 5. Push the unit slowly down the ramp. WARNING: Qualified Service Personnel ONLY must perform the Installation and Servicing of these Battery Packs.
3. INSTALLATION English English 2. CONTROLS INSTALLATION PLACEMENT REAR PANEL These Battery Packs are intended to be install in a temperature controlled environment that is free of conductive contaminants. Select a location which will provide good air circulation for the Battery Pack at all times. Avoid locations near heating devices, water or excessive humidity, or where the Battery Pack is exposed to direct sunlight. Route power cords so they cannot be walked on or damaged.
English 1. Lock the casters so that the unit will not move. 2. Step 1: There are two A1 cover plates, one for each side of the unit. Insert the A1 cover plates into the slots and slide towards the rear of the unit. 3. Step 2: There are two A2 cover plates, one is for the front of the unit and the other is for the rear of the unit. Insert the A2 cover plates into the slots and push downwards toward the floor. 4. Step 3: There are four retaining screws S1.
4. REPLACING THE BATTERY (QUALIFIED SERVICE PERSONNEL ONLY) Please read all of the WARNINGS and CAUTIONS before attempting to service the batteries. WARNING! This Battery Pack contains potentially hazardous voltages. Do not attempt to disassemble the Battery Pack beyond the battery replacement procedure. These Battery Packs contain no user serviceable parts. Repairs and Battery replacement must be performed by QUALIFIED SERVICE PERSONNEL ONLY. CAUTION: Do not open or mutilate batteries.
EDBP10000T Battery Qty/Rating 40 - 12V9.0Ah Yuasa Part # NPW45-12 CSB Part # HR 1234W F2 BATTERY REPLACEMENT PROCEDURE (QUALIFIED SERVICE PERSONNEL ONLY) PLEASE READ THE CAUTIONS AND WARNINGS BEFORE ATTEMPTING TO REPLACE THE BATTERIES 1. Turn Off all of the DC circuit breakers on the rear panel of the Battery Packs. 2. Disconnect all of the battery cables from the UPS and the Battery Pack. 3. Remove the retaining screws for the top cover on the rear panel of the Battery Pack. 4.
FIG. 4 5. OBTAINING SERVICE English English 22. Remove the battery-retaining brackets. 23. Remove the defective batteries and set aside. 24. Install the new batteries in the same position as the original batteries. 25. Re-install the battery-retaining brackets. NOTE: DO NOT pinch the battery wires between the batteries and the batteryretaining brackets. 26. Re-install the battery-retaining bracket retaining screws. 27. Observer polarity. Reconnect all of the battery jumper wires. 28. Observer polarity.
English SYSTEM SPECIFICATIONS Model Number Format EDBP10000T Rack/Tower Convertible BATTERY SYSTEM Battery Type Typical Recharge Time Typical Battery Life Sealed, Non-Spillable, Maintenance Free, Value Regulated, Lead Acid 24-hours from total discharge 3-5 years, depending on discharge cycles and ambient temperature System Voltage 240VDC System Current 30 Amps Battery Qty/Rating 40 - 12V9.
English NOTES: 18