User`s manual

9
8
English
English
CONNECTING THE BATTERY PACK
(QUALIFIED SERVICE PERSONNEL ONLY)
NOTE: When using these Battery Packs the UPS must be configured so
that the UPS will report the correct estimated runtime in the SentryPlus
software or the SNMP-NET card. See the SentryPlus software or the
SNMP-NET card User’s Manual to configure the UPS.
1. Be sure to read the installation placement procedure, all of the cautions and
the safety precautions before connecting the Battery Pack(s).
2. Make sure that the DC circuit breaker on the rear panel of the Battery Pack
is in the Off position. CAUTION: If the Battery Pack's DC circuit breaker
is in the On position, the battery voltage will be present at the open end of
the Battery Pack's external battery cable and external battery connector.
3. Press the Off button on the front panel of the UPS.
4. Turn off the input circuit breaker on the rear panel of the UPS.
5. Turn off the Utility input circuit breaker at the service panel.
6. Remove the External Battery Connector cover from the UPS's and the Bat-
tery Pack's rear panel.
7. Verify, before connecting the Battery Pack's external battery cable into the
UPS's external battery connector, that they mate red to red and black to
black. NOTE: The red connector is the battery positive (+) and the black
connector is the battery negative (-). Connect the external battery cable
from the Battery Pack to the external battery connector on the UPS. NOTE:
If connecting more than one Battery Pack see Daisy Chaining.
8. Turn the DC circuit breaker on the rear panel of the Battery Pack to the On
position.
9. The Battery Packs are ready for normal operation, see the UPS User's
Manual for the normal startup of the UPS.
INSTALLATION OF THE CASTER COVERS
(QUALIFIED SERVICE PERSONNEL ONLY)
1. Lock the casters so that the unit will not move.
2. Step 1: There are two A1 cover plates, one for each side of the unit. Insert the
A1 cover plates into the slots and slide towards the rear of the unit.
3. Step 2: There are two A2 cover plates, one is for the front of the unit and the
other is for the rear of the unit. Insert the A2 cover plates into the slots and
push downwards toward the floor.
4. Step 3: There are four retaining screws S1. Install the S1 retaining screws
into the A2 cover plates.
5. Step 4: There is one A3 cover plate. Insert the A3 cover plate into the holes
on the A2 cover plate on the front of the unit and press firmly.