ED6-Parallel/Redundant Cable Kit User’s Manual Para Systems, Inc. 1455 LeMay Drive Carrollton, TX 75007 Phone: 1-972-446-7363 Fax: 1-972-446-9011 Internet: minutemanups.com UPS Sizing: sizemyups.
Table of Contents 1 Important Safety Instructions .................................................. 2 2 ED6-PARALLEL Package Contents ......................................... 4 3 Product Introduction................................................................. 5 4 Installation ................................................................................. 5 5 Basic Parameter Check ............................................................ 5 6 Wiring ................................................
1. Important Safety Instruction 1.1. An Important Notice 1.1.1. To ensure safety in all applications where a UPS (Uninterruptible Power Supply) system and a MTBS (Maintenance Bypass Switch) are hardwired to the electrical supply A Qualified Electrical Contractor must perform the installation of the UPS and the MTBS.
2. ED6-PARALLEL Package Contents 3. Product Introduction 2.1. Package Contents: 3.1. The ED6-PARALLEL kit is used when connecting the UPSs in Parallel/Redundant or N+1 applications. The ED6-MTBS2 and ED6-MTBS-4 (Maintenance Bypass Switch) should be used in all Parallel/Redundant and can be use in N+1 applications where the application requires the UPS output voltage to be 208/240VAC only. The MTBS CANNOT be used in N+1 applications where the output voltage is 120VAC. 2.1.1.
.5. Press the “ON button” and the “Down arrow key” < ↓ > (on the front panel) simultaneously for three seconds to enter the Setting mode. 5.6. See Table 1.0 for the default values and the options available. Use the down arrow key to scroll through the items, note the settings. 5.8. If any changes were made press the “Save key” to save the settings. NOTE: The new settings WILL NOT be saved unless the “Save Key” is pressed. 5.9. Once finished with the Setting mode the LCD will display “LINE OFF”.
* Output voltage default value depends on the country or user requested value. ** Single unit: ID number must be “01”, or UPS will have an Er17 error occurred. *** Single unit: Parallel function must be “OFF” (P 01), or UPS will have an Er21 error occurred. Figure 2 ED12000RM: Input: 208/240V, Output: 208/240V, Total capacity 12KVA. 2 – ED6200RM, 2 – EDBP6000RM, 1 – ED6-MTBS2, 1 - ED-PARALLEL 6. Wiring 6.1.
Figure 3 Figure 4 ED18000RM: Input: 208/240V, Output: 208/240V, Total capacity 18KVA. 3 – ED6200RM, 3 – EDBP6000RM, 1 – ED6-MTBS4, 1 - ED-PARALLEL ED24000RM: Input: 208/240V, Output: 208/240V, Total capacity 24KVA.
Figure 5 Figure 6 ED12000T: Input: 208/240V, Output: 208/240V, Total capacity 12KVA. 2 – ED6200T, 1 – ED6-MTBS2, 1 - ED-PARALLEL ED18000T: Input: 208/240V, Output: 208/240V, Total capacity 18KVA.
Figure 7 Figure 8 ED20000T: Input: 208/240V, Output: 208/240V, Total capacity 20KVA. 2 – ED10200T, 1 – ED6-MTBS4, 1 - ED-PARALLEL ED24000T: Input: 208/240V, Output: 208/240V, Total capacity 24KVA.
Figure 9 Figure 10 ED6200RM N+1: Input: 208/240V, Output: 208/240V, Total capacity 6KVA. 2 – ED6200RM, 2 – EDBP6000RM, 1 – ED6-MTBS2, 1 - ED-PARALLEL ED6000RM N+1: Input: 208/240V, Output: 120/208/240V, Total capacity 6KVA.
Figure 11 Figure 12 ED6200T N+1: Input: 208/240V, Output: 208/240V, Total capacity 6KVA. 2 – ED6200T, 1 - ED-PARALLEL ED6000T N+1: Input: 208/240V, Output: 120/208/240V, Total capacity 6KVA.
Figure 13 Figure 14 ED10200T N+1: Input: 208/240V, Output: 208/240V, Total capacity 10KVA. 2 – ED10200T, 1 - ED-PARALLEL ED10000T N+1: Input: 208/240V, Output: 120/208/240V, Total capacity 10KVA.
7. Setup 7.1. Make sure that the input wires, output wires, battery cables and the RJ45 communication cables are properly connected and secure. 7.2. Set two (2) and only two (2) of the terminal resistors on the rear panel of the UPSs used in the Parallel/Redundant or N+1 operation to the “On” position and the other terminal resistors must be set to the “Off” position; otherwise, the Parallel/Redundant or N+1 operation of those UPSs might cause damage to the UPSs and/or the connected equipment. 7.7.
8. Obtaining Service 9. Limited Product Warranty 1. Call your dealer for assistance. If you cannot reach your dealer, or if they cannot resolve the problem call or fax MINUTEMAN Technical Support at the following numbers; Voice phone (972) 446-7363, FAX line (972) 446-9011 or visit our Web site at www.minutemanups.com the "Discussion Board". Please have the following information available BEFORE calling the Technical Support Department. a. Your name and address. b. Where and when the unit was purchased.