Endeavor Series On-Line UPS User's Manual Para Systems, Inc. 1455 Lemay Dr. Carrollton, TX 75007 Phone: 1-972-446-7363 Fax: 1-972-446-9011 Internet: minutemanups.com UPS Sizing: sizemyups.
English 1. Introduction 2 2. Controls and Indicators 6 3. Installation 9 4. Operation 15 5. Troubleshooting 18 6. Replacing the Battery 19 7. Obtaining Service 22 8. Specifications 23 9. Configurable Parameters & Settings 25 10. Limited Product Warranty 26 A1.
English This symbol indicates "Equipment Grounding Conductor" Thank you for purchasing this power protection product. It has been designed and manufactured to provide many years of trouble free service. CAUTION! Connect the UPS to a two pole, three wire grounding IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS ! AC wall outlet. The receptacle must be connected to the appropriate branch protection (circuit breaker or fuse).
Receiving Inspection After removing your UPS from its carton, it should be inspected for damage that may have occurred in shipping. Immediately notify the carrier and place of purchase if any damage is found. Warranty claims for damage caused by the carrier will not be honored. The packing materials that your UPS was shipped in are carefully designed to minimize any shipping damage. In the unlikely case that the UPS needs to be returned to the manufacturer, please use the original packing material.
English The BATT LOW (yellow) LED illuminates in a steady state when the UPS reaches a low battery condition. The BATT LOW LED is extinguished when the UPS is in the On-Line mode and when the battery is not in a low battery condition. CONTROL PANEL The ONLINE (green) LED illuminates in a steady state when the UPS is on and the inverter is providing the output power. The ONLINE LED will extinguish when operating in the Battery mode.
REAR PANEL English English INSTALLATION PLACEMENT 1. 2. 3. 4. The input power cord (120V models). The AC Power Inlet IEC320 (208V models). The input circuit breaker will trip in the event the load exceeds the UPS’s power rating. The option slot is for option cards. The Battery Backup output power receptacles. The output receptacles are electrically wired into two segments to support the "Load Shedding Function". The locking receptacle does not support the Load Shedding Function.
10 RACKMOUNT CONFIGURATION The UPS comes with mounting brackets for the standard 19" (46.5cm) rack. The mounting brackets to fit a 23" (59.2cm) standard rack are also available. The screws for mounting the UPS to the rack are not included (screw size varies with rack size). 1. Locate the mounting bracket screw holes on the side panels of the UPS, at the front of the UPS. NOTE: The mounting brackets can also be mounted in the middle of the UPS. 2.
DESKTOP CONFIGURATION The desktop configuration allows the user to install the monitor, the computer and the UPS in one single stack. WARNING: Use two or more people when installing the UPS. Use CAUTION, the UPS is extremely heavy. 1. Once the location of the UPS has been determined, lay the UPS down flat on the desk. 2. Stack the computer and then the monitor on top of the UPS. NOTE: Do not stack the UPS on top of the computer. The UPS is heavy and may damage the other equipment. 3.
English English CONNECTING YOUR EQUIPMENT Plug the equipment into the output receptacles on the rear panel of the UPS. Do not use extension cords, adapter plugs or surge strips on the output of the UPS. Ensure that you do not exceed the maximum output rating of the UPS (refer to the information label on the UPS or the Electrical Specifications in this manual). CAUTION! DO NOT connect a laser printer to the output receptacles on the UPS, unless the UPS is rated 2000VA or greater.
English SELF TEST The self test feature is useful to verify the correct operation of the UPS and the condition of the batteries. With the UPS in the AC normal mode, press the ON/ Test/Alarm Silencer Button for 1-beep (2-seconds) to perform a battery test. The UPS will perform a ten-second self test. During the self test, the UPS will switch to battery power and the ON BATT LED will illuminate and the audible alarm will sound.
English English Symptom Possible Cause What To Do Press and release the On/Off/ Test button to start UPS Reset circuit breaker by pressing the plunger back in. If the AC circuit breaker trips after UPS starts up, reduce the load on the UPS Fault LED is illumi- UPS has detected an inter- Call for service nated nal fault The On-Line LED The UPS is being con- Disconnect the computer is illuminated, but trolled via its communica- cable from the UPS and press there is no output tions port the On button.
Model # Battery Qty/Rating ED1000RM2U ED1500RM2U ED2000RM2U ED3000RM2U ED1000RMT2U ED1500RMT2U ED2000RMT2U ED3000RMT2U 2-12V8.5Ah CSB HR 1234W F2 Part # Panasonic LC-R129 Part # Yuasa REW45-12 Part # 4-12V7.2Ah GP 1272 F2 LC-R127.2 NP-7.2-12 4 -12V8.5Ah 6-12V8.
English English IF THE UPS REQUIRES SERVICE 1. Use the TROUBLESHOOTING section to eliminate obvious causes. 2. Verify there are no circuit breakers tripped. A tripped circuit breaker is the most common problem. 3. Call your dealer for assistance. If you cannot reach your dealer, or if they cannot resolve the problem call or fax MINUTEMAN Technical Support at the following numbers; Voice phone (972) 446-7363, FAX line (972) 4469011 or visit our Web site at www.minutemanups.com the "Discussion Board".
BATTERY SYSTEM Battery Type Sealed, Non-Spillable, Maintenance Free, Value Regulated Lead Acid 8-hours from total discharge Typical Battery Life English English Typical Recharge Time 3-5 years, depending on discharge cycles and ambient temp System Voltage 24VDC 48VDC 48VDC 72VDC 2-12V8.5Ah 4-12V7.2Ah 4-12V8.5Ah 6-12V8.
LIMITED PRODUCT WARRANTY English Para Systems Inc. (Para Systems) warrants this equipment, when properly applied and operated within specified conditions, against faulty materials or workmanship for a period of three years from the date of purchase. For equipment sites within the United States and Canada, this warranty covers repair or replacement of defective equipment at the discretion of Para Systems. Repair will be from the nearest authorized service center.
DECLARATION OF CONFORMITY Notes: English English A1. Application of Council Directive(s): 89/336/EEC, 73/23/EEC Standard(s) to which Conformity is declared: EN55022, EN55024 EN61000-6-1, EN61000-6-3 EN61000-4-5 Manufacturer’s Name: Para Systems, Inc.
Notes: English 30