User`s manual

11
English
CONNECTING THE BATTERY PACK
(QUALIFIED SERVICE PERSONNEL ONLY)
NOTE: If you are using these Battery Packs with the Enterprise Plus
series UPS, the UPS must be configured so that the UPS will report the
correct estimated runtime in the SentryPlus software and to make the
Battery capacity bar graph LEDs display properly. See the SentryPlus
software User’s Manual to configure the UPS.
1. Make sure that the DC circuit breaker on the rear panel of the Battery Pack
is in the Off position.
2. Turn the UPS off and disconnect the UPS's input power cord from the AC
wall outlet.
3. Remove the External Battery Connector cover from the UPS's rear panel.
4. Verify, before connecting the Battery Pack's external battery cable into the
UPS's external battery connector, that they mate red to red and black to
black. NOTE: The red connector is the battery positive (+) and the black
connector is the battery negative (-). Connect the external battery cable
from the Battery Pack to the external battery connector on the UPS. NOTE:
If connecting more than one Battery Pack see Daisy Chaining.
5. See Connecting the Battery Pack to an AC Source.
NOTE: The EBP72XL's External Battery Cable has a strain relief that
must be attached (with the screw) to the rear panel of the UPS.
EBP72XL's External Battery Cable with strain relief.