ERS1500RTNC Series UPS User's Manual Para Systems, Inc. 1455 LeMay Dr. Carrollton, TX 75007 Phone: 1-972-446-7363 Fax: 1-972-446-9011 Internet: minutemanups.com UPS Sizing: sizemyups.
1. Introduction 2 2. Controls and Indicators 6 3. Installation 7 4. Operation 13 5. Troubleshooting 16 6. Replacing the Battery 17 7. Obtaining Service 21 8. Specifications 22 9. Limited Product Warranty 24 A1.
NOTICE! The output of this device is not sinusoidal. It has a total harmonic distortion and maximum single harmonic as below: Total harmonic 42.8% Single harmonic 26.6% Thank you for purchasing this power protection product. It has been designed and manufactured to provide many years of trouble free service.
ON / OFF / TEST BUTTON: To turn the UPS on: press and hold the On/Off/ Test Button until the alarm sounds one beep and then release. The UPS will perform a five second self-test. Once the UPS has passed its self-test the UPS will provide an output and the load will be powered. To turn the UPS off: press and hold the On/Off/Test Button until the alarm sounds one beep and then release.
CONTROL PANEL 1. 2. 3. 4. 5. 6. 7. 8. RS232 Communications Port is for UPS monitoring and control. USB Communications Port is for UPS monitoring and control. The RJ11/45 are used for phone/fax/modem and network protection. SNMP Card is for UPS monitoring and control (Included). Battery Backup & Surge output receptacles for mission critical equipment. Surge ONLY output receptacles for noncritical equipment. Input power cord is for connecting to the Utility Power.
INSTALLATION Be sure to read the installation placement and all the cautions before installing the UPS. Place the UPS in the final desired location and complete the rest of the installation procedure. These UPSs are shipped with the internal batteries disconnected. The batteries must be connected before putting these UPSs into service. See the Connecting The Batteries procedure to connect the batteries.
2. The LED face plate can be rotated to read in the upright position. Remove the front panel from the UPS. On the backside of the front panel, push the LED face plate outwards the face plate will pop out. Position the LED face plate so that it reads in the upright position. Reinstall the front panel on the UPS. 3. The two rackmount brackets are used for the two tower brackets. Remove the retaining screws and attached the tower brackets as shown. The tower brackets go on both sides of the UPS.
CONNECTING THE UPS TO AN AC SOURCE CAUTION - To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch circuit over-current protection in accordance with the National Electric Code, ANSI/NFPA 70. Plug the UPS into a two pole, three wire, grounded receptacle only. DO NOT PLUG THE UPS INTO EXTENSION CORDS, ADAPTER PLUGS, SURGE STRIPS OR POWER STRIPS. DO NOT CUT THE INPUT PLUG OFF AND ATTEMPT TO HARDWIRE THIS UPS, DOING SO WILL VOID THE WARRANTY.
TEST BUTTON To perform a ten-second user invoked battery test: With the UPS in the AC normal mode, press and hold the On/Off/Test Button until the alarm sounds four beeps, and then release. During the test, the UPS will switch to the Battery mode, the Battery mode LED will illuminate and the alarm will sound. LED Function The UPS provides both visual and audible indicators. There are three visual indicators: an AC mode Green LED, a Battery mode Yellow LED and a Fault condition Red LED.
Symptom Possible Cause UPS will not turn on On/Off/Test button not pressed UPS operates in Input AC circuit breaker is battery mode only, tripped even though there is normal AC present Fault LED is illumi- UPS has detected an internated and the nal fault alarm is constant The AC mode LED The UPS is being conis illuminated, but trolled via its communicathere is no output tions port What To Do Press, hold and then release the On/Off button to start UPS Reset circuit breaker by pressing the plunger back in
CAUTION: Replace batteries with the same number and type as originally installed in the UPS. These batteries have pressure operated vents. These UPSs contain sealed non-spillable maintenance-free lead acid batteries. Model # Battery Module Part # 6. Remove the front panel retaining screws. (FIG. 2) 7. Lay the front panel on top of the UPS. FIG.
10. Disconnect the Battery connectors (red and black). (FIG. 4) 11. Grasp the battery pull tab and gently pull the battery module out of the UPS and set aside. NOTE: Use Caution, the battery module is heavy. FIG. 4 IF THE UPS REQUIRES SERVICE 12. Slide the new battery module into the UPS. 13. Reinstall the battery retaining bracket. 14. Reinstall the two retaining screws for the battery retaining bracket. 15. Verify proper polarity. Reconnect the battery connectors (red and black).
BATTERY SYSTEM SYSTEM SPECIFICATIONS ERS1500RTNC Model Number Battery Type Sealed, Non-Spillable, Maintenance Free, Value Regulated Lead Acid Typical Battery Life 2 to 3 years. Environmental factors do affect battery life. High temperatures, poor utility power, and frequent, short duration discharges have a negative impact on battery life.
A1. DECLARATION OF CONFORMITY Application of Council Directive(s): 2004/108/EC, 2006/95/EC, cTUVus (for UL1778) Para Systems, Inc. (Para Systems) warrants this equipment, when properly applied and operated within specified conditions, against faulty materials or workmanship for a period of one year from the date of purchase. For equipment sites within the United States and Canada, this warranty covers depot repair or replacement of defective equipment at the discretion of Para Systems.
Notes: 26 Notes: 27