User`s manual

6
7
REAR PANEL
INSTALLATION PLACEMENT
The PRO-E series is intended to be install in a temperature controlled environ-
ment that is free of conductive contaminants. Select a location which will pro-
vide good air circulation for the UPS at all times. Avoid locations near heating
devices, water or excessive humidity, or where the UPS is exposed to direct
sunlight. Route power cords so they cannot be walked on or damaged.
Operating Temperature (Maximum): 0 to 40 degrees C (+32 to 104 degrees F)
Operating Elevation: 0 to 3,000m (0 to 10,000 ft)
Operating and Storage Relative Humidity: 95%, non-condensing
Storage Temperature: -15 to +45 degrees C (+5 to +113 degrees F)
Storage Elevation: 0 to 15,000m (0 to +50,000 ft)
INSTALLATION
Be sure to read the installation placement and all the cautions before installing
the UPS. Place the UPS in the final desired location and complete the rest of
the installation procedure. USE CAUTION: The UPS is heavy. Use the
appropriate number of personnel when installing the UPS.
CONNECTING YOUR EQUIPMENT
Plug the equipment into the output receptacles on the rear panel of the UPS.
Do not use extension cords, adapter plugs, power strips or surge strips on the
output of the UPS. Ensure that you do not exceed the maximum output rating
of the UPS (refer to the UPS's back panel or the Electrical Specifications in this
manual).
English
English
CAUTION!
DO NOT connect a laser printer to the output receptacles on the
UPS, unless the UPS is rated 2000VA or greater. A laser printer
draws significantly more power when printing than at idle and
may overload the UPS.
5
4
3
2
1
10
8
6
7
9
5
4
3
2
1
8
6
7
9
1. The Information/Rating Label.
2. The Battery Backup and Surge output power receptacles are NEMA 5-15R
type (IEC 320 C13 sockets for 230V models).
3. The USB Communications Interface Port is for UPS monitoring and control.
4. The RS232 Communications Interface Port is for UPS monitoring and
control.
5. The Dipswitches are for setting the Inverter output voltage.
6. The input power cord has a NEMA 5-15P Plug (IEC 320 C14 socket for 230V
models).
7. The input circuit breaker will trip in the event the load exceeds the UPS’s
power rating.
8. The RJ11/RJ45 modular connectors are used for 10 Base-T Network/Fax/
Modem protection.
WARNING: The 230V models are NETWORK PROTECTION ONLY.
9. The Surge ONLY output power receptacles are NEMA 5-15R type (IEC 320
C13 sockets for 230V models).
NOTE: The Surge ONLY output power receptacles are only on the following
models: PRO500E, PRO700E, PRO500iE, PRO700iE.
10. The Site Wiring Fault (SWF) LED illuminates when the UPS detects an
improperly wired AC wall outlet (120V models only).
120V Models
230V Models